Type MRTP
Supervision for AC Pilot Circuits

http://slidepdf.com/reader/full/mrtp-r6026l 1/8
7/18/2019 MRTP R6026L

Midos Type MRTP


Supervision for AC Pilot Circuits

Figure 1:
 Type MRT P relay
withdrawn from case

Features
• Alarm and indication of open
circuit, cross connected and short
circuit pilots.
• Alarm and indication of 
supervision supply failure.
• Suitable for pilot circuits insulated
to 5kV or 15kV.

• Separate indication of short insulated for 15kV. The injection circuit between terminals 17 and 18
circuit and open circuit pilots. filters are then assembled as part of  by-passes the ac pilot current and
the isolation transformers and have directs a dc current from the
Models available to be isolated from the supervision supervision circuit around the pilot
MRTP 01 Pilot supervision with module. The isolation transformer circuit. To enable crossed pilots to
injection filter provides the necessary 15kV be detected and ensure correct
MRTP 02 Injection filter isolation barrier. indication for pilots which become
MRTP 03 Pilot supervision.  The supervision circuit MRTP 01, as short circuited at the remote end, it
shown in Figure 2, requires a low is necessary to include a second
Application voltage ac supply which is injection filter in the pilot circuit as
 The MRTP type relay as shown in connected to terminals 27 and 28. shown for the remote line end. This
Figure 1, provides supervision for filter ensures that remote short
ac circuits such as pilot wires  The inputwith
provided transformer
a primary canwinding
be to circuits eliminate sufficient resistance
interconnecting protective relays. It suit the available supply. The in the pilot loop to cause a
provides indication should the pilot secondary voltage is converted to a detectable current change.
wires become open or short clipped sine wave of constant A change in the dc supervision
circuited, reverse connected or in amplitude by a zener diode current is indicative of a pilot fault
the event of insulation deterioration. connected in a bridge rectifier and causes a corresponding change
circuit. The dc voltage developed in the ac current supplied by the
Description across the zener diode is used to supervision relay. The measuring
Figure 2 shows the arrangement for power the measuring circuit which circuit monitors this ac current and
supervision of pilots insulated for in turn measures the current flowing initiates a PILOT FAILURE alarm,
5kV. It requires the pilot circuit to be into the injection filter. The clipped after a time delay, if a sufficient
terminated
element bywill
that a resistor
provideora other
path for sine wavefilter
injection voltage
and is rectified inisthe
a capacitor change takes place.
the dc supervision current. charged to the peak value to  The ac supervision supply is also
produce a constant level dc voltage. monitored and, in the event of a
Figure 3 shows a similar A capacitor connected in the pilot failure, a time delayed SUPPLY
arrangement for pilot circuits FAILURE alarm is initiated.

http://slidepdf.com/reader/full/mrtp-r6026l 2 2/8
7/18/2019 MRTP R6026L

17 17

MBCI Pilots MBCI

18 18
17 18 17 18
19
v v
v
v 20
Case earth MRTP02

20 v OP
RL2 RL7
Supply
19 v I L2 Reset 1
fail
27 OP
AC auxiliary AC RL1 RL3 RL6 1
power Pilot
supply 28 supply
L1
I L2 Reset 1
S/C RL4-1 3
5 Output
Case earth 13 OP RL8
DC Pilot 2 contacts
1 2 Vx Reset 1
14 power O/ C RL4-2 4 change state
supply
3 4 for pilot fail
RL4 6
5 6 2
7 8 1 7
10 RL5-1 9
9
11 12
MRTP 01 11 Output
RL5 8 contacts
13 14 +VE
2
RL5-2 10
change state
15 16 RL1 RL2 RL3 RL1 RL2 RL3
Case for supply fail
17 18 earth –1 –1 Start –2 –2 –2 12
–1

19 20
21 22
23 24
25 26
Note 1:
27 28
(a) CT shorting links make before (b) (c) disconnect
(b) Short terminals break before (c)
Module terminal block
viewed from rear (c) Long terminal

Figure 2:
Application diagram: pilot supervision/ injection filter type MRTP 01 (5kV insulation)

Pilot isolation
P6 S2 S1 transformer P1
17 P5 v
17
P4 v
P3 X2 X1
P2
MBCI Pilots MBCI
v
v X1 X2 P2
P3
P4
S1 P5
S2 v P6
18 18
v S1 S2
Supervision isolation
P1 P2 transformer

20 OP
RL2 RL7
Supply
19 I L2 Reset 1
fail
27 OP
AC RL1 RL3 RL6 1
Case earth AC auxiliary Pilot
supply 28 power
supply L1
I
L2 Reset 1 S/C RL4-1 3
1 2 Output
OP 5
3 4 13 RL8
contacts
DC Reset 1 Pilot 2
5 6 Vx power change state
14 supply O/ C RL4-2 4
7 8 for pilot fail
RL4 6
9 10 2
11 12 1 7
13 14 RL5-1 9
15 16 MRTP 03 11 Output
18 RL5 8 contacts
17 +VE
Case 2
10 change state
RL5-2
19 20
earth RL1 RL2 RL3 RL1 RL2 RL3 for supply fail
–1 –1 –1 Start –2 –2 –2 12
21 22 t 
23 24
25 26
Note 1:
27 28
(a) CT shorting links make before (b) (c) disconnect

Module terminal block


viewed from rear
(b) Short terminals break before (c)
(c) Long terminal

Figure3:
Application diagram: pilot supervision relay type MRTP 03 (15kV isolation)

http://slidepdf.com/reader/full/mrtp-r6026l 3 3/8
7/18/2019 MRTP R6026L

Technical Data

Ratings
AC Supervision Voltage Rated voltage (Vn) Operating range (V)
110 88-127
127 102-146
220 176-253

240
260 192-276
208-299
DC Auxiliary Voltage Rated voltage (Vx) Operating range (V)
  24/ 27 19.0- 33.0
  30/ 34 24.0- 41.0
  48/ 54 37.5- 66.0
110/ 125 87.5- 150.0

Frequency 50 or 60Hz

Burdens   Burden at rated voltage

DC Burden Quiescent 2 LEDs Output


(Vx) operated operated
  24/ 27 0.2W 1.5W 3W
  30/ 34 0.5W 1.5W 6W
  48/ 54 0.5W 1.7W 6W
110/ 125 1W 3W 6W
AC Burden 5.3VA at any rated voltage setting

Settings
Range of pilot loop resistance 0-10,000 ohms
A variable resistance accessible from
the front of the relay, allows the
calibration to be changed to suit the
pilot circuit resistance.
Supply failure alarm below 70% Vn approx.
 Time delay for alarm 6-10s

Contacts 2 changeover on the pilot fail element


2 changeover on the supply fail
element

Contact rating
Make and carry for 0.2s 7500VA subject to maxima of 30A
and 300V ac or dc
Carry continuously 5A ac or dc
Break ac – 1250VA
dc – 50W resistive
  25W, L/ R = 0.04s
subject to maxima of 5A and 300V
DC supervision current in pilots
= 1.5mA (typical)
Maximum allowed continuous ac pilot
current = 50mA
Maximum allowed short time ac pilot
current = 1500mA

http://slidepdf.com/reader/full/mrtp-r6026l 4 4/8
7/18/2019 MRTP R6026L

Durability
Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum

Indications Non-volatile red led trip indicators are


used for supply fail, pilot fail short
circuit and pilot fail open circuit. If the
auxiliary supply is lost the led will
return to the same state when the
supply is restored.
A green led is used to give an
instantaneous indication of pilot fault
to assist commissioning the relay.

High Voltage Withstand


Dielectric withstand 2kV rms for 1 minute between all
IEC 60255-5: 1977 terminals and case earth.

2kV rms for 1 minute between


terminals of independent circuits
including contact circuits, with
terminals on each independent circuit
connected together.
1kV rms for 1 minute across open
contacts of output relays.

High voltage impulse 5kV peak, 1.2/ 50µs, 0.5J between all
IEC 60255-5: 1977 terminals and case earth and between
adjacent terminals.

Electrical Environment
High Frequency Disturbance
IEC 60255-22-1: 1988 Class III 2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of the
same circuit.
No additional tolerances are required
for the operating time or the unit’s
thresholds.
Electrostatic Discharge
IEC 60255-22-2: 1989 Class II 4.0kV discharge in air with cover in

place.
IEC 60801-2: 1991 Level 2 4.0kV point contact discharge with
cover removed.
No additional tolerances are required
for the operating time or the unit’s
thresholds.
Fast Transient Disturbance
IEC 60255-22-4: 1992 Class IV 4.0kV, 2.5kHz applied directly to
auxiliary supply and watch-dog relay.
IEC 60801-4: 1988 Level 4 4.0kV, 2.5kHz applied directly to all

inputs.
No additional tolerances are required
for the operating time or the unit’s
thresholds.

http://slidepdf.com/reader/full/mrtp-r6026l 5 5/8
7/18/2019 MRTP R6026L

EMC Compliance
89/ 336/ EEC
EN 50081-2: 1994
EN 5082-2: 1995 Compliance to the European
Commission Directive on EMC is
claimed via the Technical Construction
File route. Generic Standards were
used to establish conformity.

Product Safety
73/ 23/ EEC Compliance with the European
Commission Low Voltage Directive.
EN 610610-1: 1993/ A2: 1995 Compliance is demonstrated by
EN 60950: 1992/ A11: 1997 reference to generic safety standards.

Atmospheric Environment
 Temperature
IEC 60255-6: 1988 Storage and transit –25ºC to +70ºC
Operating –25ºC to +55ºC
IEC 60068-2-1: 1990 Cold
IEC 60068-2-2: 1974 Dry Heat
Humidity
IEC 60068-2-3: 1969 56 days at 93% RH and 40ºC
Enclosure Protection
IEC 60529: 1989 IP50 (dust protected)

Mechanical Environment
Vibration
IEC 60255-21-1: 1988 Response Class 1
Endurance Class 1

Information required with order

Type of relay
Pilot supervision with injection filter
Injection filter }
MRTP 01 5kV circuits
MRTP 02
Pilot supervision MRTP 03
Pilot isolation transformer
with injection filter HN0068001 15kV circuits
Supervision isolation transformer
(For dimensions see Figures 5 & 6)
AC Voltage rating
ZC0243003

}
DC Voltage rating

Additional Information

Associated publications
R6001 MIDOS System
R6004 MMLG/ MMLB/ Test plug/ block
R6011 MBCI Translay ‘S’ differential
feeder protection

http://slidepdf.com/reader/full/mrtp-r6026l 6 6/8
7/18/2019 MRTP R6026L

Cases 52
4 holes Ø4.4
97 23.5
 The MRTP type relay is housed in a
size 4 case as shown in Figure 4.

168 159

Push button
projection 10 max. 99
Panel cut-out:
Flush mounting fixing details

32 212 25 min.

177 157 max.

Reset

77 11
Flush mounting
All dimensions in mm

Figure4:
Case outline size 4

P1 2.5 1.5
1.2 1.0 0.9 S1 S2

172mm
X1 X2

340mm
6 fixing holes, M6 clearance

64.5mm

154mm

30mm 116mm 9mm


176mm

Figure 5:
Pilot isolation transformer with filter with
insulation for 15kV

19mm 134mm 19mm 69mm

98mm

2 off M5 studs 2 off fixing holes M5 2 off M5 studs

52mm 69mm

50mm 52mm
19mm

Figure 6:
Pilot supervision isolation transformer with
insulation for 15kV

http://slidepdf.com/reader/full/mrtp-r6026l 7 7/8
7/18/2019 MRTP R6026L

ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
 Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: enquiries@pcs.alstom.co.uk Internet: www.gecalsthomgpc.co.uk
©1998 ALSTOM T&D Protection & Control Ltd

Our policy is one of continuous development. A ccordingly the design of our products may change at any time. W hilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for i nformation purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication R6026L 119820 GSP Printed in England.