You are on page 1of 1

Humidity

Control
Department Editor: Kate Torzewski

APPLICATIONS
Compressor
Heater
Dehumidification by cooling or dessication Condenser
Receiver
has a variety of applications, including:
Desiccant
Preventing moisture regain. Nearly all Fan Cooling wheel
coil
materials have some affinity for moisture
based on surface characteristics and Process air Dry air
the amount of surface exposed to humid Heater
air. Moisture regain occurs when moist
Condensate pan
particles stick together. Drive motor
160 160
Preventing condensation. Air holds water 100% 100%
vapor in proportion to its temperature. Cold
Specific humidity, grains/lb

Specific humidity, grains/lb


relative humidity relative humidity
surfaces of pipes, vessels, valves and heat
exchangers condense moisture unless the 120 120
air around them is dried to a dewpoint 75% 75%
below the temperature of the cold surface.
Preventing corrosion. The exposure of metal 80
50% 50% 80
surfaces to atmospheric corrosion can be
reduced by surrounding the surfaces with Enter
dry air. Dehumidifiers also keep humidity Enter 40 25% 40
low in process control rooms, preventing
the corrosion of electrical contacts and Leave 25% Leave
sensitive electrical components. 10 10
Drying heat-sensitive products. Typically,
drying time is reduced by heating a prod- 10 20 30 50 60 70 80 10 20 30 50 60 70 80
uct. If the product is susceptible to damage Air temperature, oF Air temperature, oF
by heat, drying time can be reduced by FIGURE 1."JSUISPVHIBDPPMJOH FIGURE 2."JSUISPVHIBEFTJDDBOU
using dehumidified air, which reduces the EFIVNJEJGJFS EFIVNJEJGJFS
vapor pressure of air above the wet surface. both operating cost and initial equipment
— a fivefold reduction in the air moisture
COOLING beyond what can be achieved with a stan- cost. Below 50°F, precautions need to be
dard-grade air conditioning system. taken to avoid freezing the condensed
water on the cooling coil. Consequently,
A common method for dehumidification is This equipment uses differences in vapor
desiccants are more economical than cool-
the use of air conditioning. Figure 1 shows pressure to remove moisture from air by
ing-based systems at lower dewpoints.
a typical vapor-compression cooling-based chemical attraction. The surface of dry
dehumidification process. Air to be dried desiccant has a very low vapor pressure, Relative humidity sensitivity. When a pro-
passes through a cooling coil, which lowers compared with the much higher vapor pres- cess needs a low moisture level in absolute
the temperature of the airstream below its sure of humid air. terms, but can tolerate a high relative
dewpoint. As the air cools, it loses its capac- humidity, cooling-based dehumidification
Water vapor moves out of the humid air
ity to hold water vapor. The water condenses without desiccants is cost effective. By con-
onto the desiccant surface to eliminate the
on the cooling coil surface, and falls to the trast, in processes that demand a low rela-
vapor pressure difference, as shown in
drain pan as liquid. The air is then drier in tive humidity in addition to a low dewpoint,
Figure 2. Eventually, the desiccant surface
absolute terms, but it also has a relative hu- desiccant systems are used for humidity
collects enough water vapor to equal the
midity close to 100%. If low relative humidity control, with supplementary cooling systems
vapor pressure of the humid air. Then the
is needed in addition to a lower absolute to keep temperature within acceptable lim-
desiccant must be dried (reactivated) by ap-
amount of moisture, the air can be heated its. When a product is sensitive to relative
plying heat before it is recycled to remove
after it leaves the cooling coil. humidity but not to temperature, a desiccant
more moisture from the air stream.
For industrial purposes, cooling-based dehumidifier is used without a cooling unit
dehumidification units are optimized for re- to maintain a constant relative humidity.
COOLING VS. DESSICATION
moving moisture rather than removing heat. Temperature tolerance. If the application
These units provide deep cooling of small In most chemical process applications, both can tolerate a wide temperature range,
amounts of air rather than slight cooling technologies work best together. Cooling- then dehumidification alone may suffice. In
of large amounts of air, condensing more based dehumidification handles the mois- most cases, both temperature and moisture
moisture. Standard refrigeration equipment ture load occurring at high dewpoints, and must be maintained within set limits, so both
can produce dewpoints of +40°F (4°C) on a desiccant-based dehumidification removes cooling and desiccant equipment are used
reliable basis. the moisture load at low dewpoints. The op- in a combination to maintain control.
timal mix of the two technologies depends
DESSICATION
on the characteristics of the application.
Factors to consider include the following: References
In a desiccant system, the process airstream 1.Harriman, L., Don’t Sweat It, Dehumidify,
passes through a desiccant medium. The Dewpoint control level. When the required Chem. Eng., August 1997, pp. 80–87.
desiccant adsorbs moisture directly from moisture-control level is relatively high 2.Soleyn, K., Humidity Control: Preventing
the airstream. Desiccant dehumidifiers can (above a 50°F dewpoint), cooling-based Moisture Contamination, Chem. Eng., October
produce dewpoints below 0°F (–18°C) dehumidification is economical in terms of 2003, pp. 50–51.

You might also like