Professional Documents
Culture Documents
IV USED TABLES 8 of 8
STEP#1: FIELD DATA
A,r
STEP#7: YES
GPR < Etouch
NO
NO STEP#9:
Em<Etouch
YES
NO STEP#10:
Es<Estep
YES
STEP#12: DETAIL
DESIGN
I
Amm 2 Eqn.: 40 Page : 43
TCAP 10 4 K 0 Tm IEEE Std. 80 - 2000
ln
t c r r K T
0 a
Where:
Material Proposed
Ta = Ambient temperature in °C 40 °C
TCAP = thermal capacity per unit volume from Table 1 3.58 J/(cm³°C)
AC Substation Grounding
Design Calculations PAGE 2 / 8
Spreadsheet
STEP#3: TOUCH & STEP VOLTAGE CRITERIA
0.157
Estep70 (1000 6Cs s ) Eqn. 30, Page 27, IEEE 80 2000
ts
0 .09 1 Eqn. 27, Page 23, IEEE 80 2000
s
Cs
2 hs 0 .09
Where:
K = -0.92
Cs = 0.71
Length Breadth
Preliminary Layout of Grid = 70 70
D = Conductor Spacing = 5m
AC Substation Grounding
Design Calculations PAGE 3 / 8
Spreadsheet
AC Substation Grounding
Design Calculations PAGE 3 / 8
Spreadsheet
STEP#5: GRID RESISTANCE
1 1 1
Rg 1 Eqn. 52, Page 65,
LT 20A 1 h 20/ A IEEE 80 2000
Where:
Rg = Grid Resistance
Rg = 0.67 W
Where:
IG = 9415 A
GPR I G Rg
Where:
Rg = Grid Resistance
GPR = 6354.8 V
If Action
GPR < The Preliminary grid design is safe
Etouch70
GPR > The Preliminary grid design is not safe , Continue to Step#8: Calculation of mesh and step
Etouch70 voltages
[[[[[[ The Initial Design is not Safe and continue to Step#8 ]]]]]]
AC Substation Grounding
Design Calculations PAGE 4 / 8
Spreadsheet
STEP#8: CALCULATION FOR ACTUAL DERIVED STEP & MESH VOLTAGE
A Mesh Voltage
IG K m K i
Emesh ( Design ) Eqn. 80, Page 91,
Lr
L C 1 . 55 1 . 22 L IEEE 80, 2000
L2 l 2 R
x Ly
Ki = 0.644 + 0.148 n
Where:
n = na x nb x nc x nd
na = 2 x LT / Lp
na = 15.0
n = 15.00
Ki = 2.86
Where:
Kii = Corrective wieghting factor that adjusts the effect of inner conductors on the corner mesh
1
K ii 2
Eqn. 82, Page 93
IEEE 80, 2000
(2 n) n
Kii = 0.62
Where:
Kh = 1.22
Km = 0.65
AC Substation Grounding
Design Calculations PAGE 5 / 8
Spreadsheet
(CONTINUED) STEP#8: CALCULATION FOR ACTUAL DERIVED STEP & MESH VOLTAGE
B Step Voltage
Estep ( Design )
Ks Ki I G Eqn. 92, Page 94
0 . 75 L C 0 . 85 L R IEEE 80, 2000
Where:
1 1 1 1 0 .5 n 2
Ks Eqn. 94, Page 94, IEEE 80, 2000
2 h D h D
Ks = 0.440
Ki = 2.864
= 724 Volts
STEP#9: COMPARING THE COMPUTED MESH VOLTAGE FROM STEP#8 WITH THE TOLERABLE TOUCH
VOLTAGE FROM STEP#3
If Action
Em < Etouch Continue to Step#10: Comparing the computed step voltage from step#8 with the tolerable
step voltage from step#3
Em > Etouch Preliminary Design modification
STEP#10: COMPARING THE COMPUTED STEP VOLTAGE FROM STEP#8 WITH THE TOLERABLE STEP
VOLTAGE FROM STEP#3
If Action
Es < Estep Safe Design - Design is completed
Es > Estep Back to Step#4: Initial Design modification
AC Substation Grounding
Design Calculations PAGE 6 / 8
Spreadsheet
Results Summary
Size of Conductor 10 mm
B GROUND RODS
C HUMAN SAFETY
AC Substation Grounding
Design Calculations PAGE 7/ 8
Spreadsheet
Used Tables
TCAP
Material
ar factor K0 at
Fusing rr Thermal
Description Conductivity Temperature 20°C(m W .c
at 20°C (0°C) Capacity
(%) Tm (°C) m) [J/(cm³.°C]
Copper annealed
1 1 100 1 0.00393 1 234 1 1083 1 1.72 1 3.42
soft - drawn
Copper, commercial
2 2 97 2 0.00381 2 242 2 1084 2 1.78 2 3.42
hard - drawn
Copper-clad steel
3 3 40 3 0.00378 3 245 3 1084 3 4.4 3 3.85
wire
Copper-clad steel
4 4 30 4 0.00378 4 245 4 700 4 5.86 4 3.85
wire
Copper-clad steel
5 5 20 5 0.00378 5 245 5 1084 5 8.62 5 3.85
rod
6 Aluminium EC Grade 6 61 6 0.00403 6 228 6 657 6 2.86 6 2.56
Aluminium 5005
7 7 53.5 7 0.00353 7 263 7 652 7 3.22 7 2.6
alloy
Aluminium 6201
8 8 52.5 8 0.00347 8 268 8 654 8 3.28 8 2.6
alloy
Aluminium-clad steel
9 9 20.3 9 0.0036 9 258 9 657 9 8.48 9 3.58
wire