Professional Documents
Culture Documents
AS-J-600-HMFM DUPLEX
PSA Oxygen System
Instruction Manual
Invoice Date:
Start-up Date:
AirSep Representative
Company:
Contact:
Address:
Country: Fax:
Phone: Telex:
Before you attempt to install, operate, or repair the plant, read and
thoroughly understand this operating manual. Improper operation can
result in severe bodily injury, damage to the plant, or poor performance.
1.0 Introduction
1.1 General
This instruction manual provides description of the AirSep Corporation AS-J-600-
HMFM PSA Oxygen System as well as instructions for its installation, operation,
and maintenance. The Appendix of this operating manual also includes pertinent
drawings and component literature.
To ensure safe operation and proper plant maintenance, AirSep Corporation
recommends that you keep this operating manual readily available for reference.
2.0 Safety
2.1 General
Oxygen, the most abundant of the elements, makes up approximately 50 percent of
the earth’s crust. In its free state, oxygen forms approximately one-fifth of our air by
volume. Although classified as a non-flammable gas, oxygen supports combustion.
As an active element, it combines directly or indirectly with all elements except the
rare gases. Oxygen is an invisible gas that is colorless, odorless, and tasteless.
To ensure your safety, thoroughly read and familiarize yourself with this entire
section of this operating manual. In addition, AirSep Corporation strongly
recommends that you review this section periodically.
3.1 General
The AirSep Corporation AS-J-600-HMFM DUPLEX PSA Oxygen System is a
self-contained system designed to continuously supply oxygen or to fill
oxygen cylinders with high-pressure oxygen at the design purity. Refer to the
process and instrumentation diagram, located in the Appendix of this
operating manual, for a flow schematic of the plant. Refer to the following
paragraphs for a general description of the operation of the plant:
The PSA system can be used to supply oxygen to the application at a
pressure of 65-70 psig or to fill cylinders at a pressure of 2200 psig using an
oxygen compressor. The general process of the PSA system begins as
atmospheric air enters the air compressor for pressurization and is then
stored in the air receiver tank. The air receiver tank delivers the air to the
oxygen generator. The oxygen generator separates the air into oxygen and
waste gases, and delivers feed oxygen to the oxygen receiver. The feed
oxygen flows from the oxygen tank to the oxygen compressor, which
increases the pressure of the product oxygen. Finally, the high-pressure
product oxygen flows to the oxygen cylinder filling station (mounted on the
oxygen compressor skid) to fill the oxygen cylinders.
A bypass piping is also provided to get the oxygen supply at 65-70 psig from
the oxygen generator directly without using the oxygen compressor. In this
case, a provision for backup supply of cylinders (filled before using the
continuous supply of the oxygen) is also available. The regulator (PR-3) for
the back-up supply cylinders is set for approximately 65 psig. (Refer to the
Process and Instrumentation diagram in the Appendix A) so in the event of
continuous oxygen supply pressure falling below 65 psig, the back up supply
cylinders starts supplying oxygen to the application for a limited period of
time.
A sample of the product oxygen flows from the oxygen receiver to an oxygen
analyzer inside the control panel of the AS-J, which continuously monitors
purity during operation.
The PSA Oxygen System can pressurize multiple oxygen cylinders
simultaneously. The plant operates automatically after start-up: When the
oxygen cylinders become full, the oxygen compressor shuts down to allow
removal of filled cylinders and connection of empty cylinders. At the same
time, the oxygen generator and the air compressor continue operation for a
certain time period to maintain the purity of the product oxygen within the
range specified in the Appendix of this operating manual. The system
behaves in a similar fashion when the application stops using continuous
supply of oxygen i.e. when the oxygen compressor is not used and the PSA
system is supplying oxygen to the customer’s application directly.
Equalization Valve
Manual Product
Valve
Muffler
Feed Valve
Coalescing Filter
Pressure Indicator
(PI 10)
Manual Oxygen
Sample Valve (V-15)
Vacuum Pump
Connections and
Connections and Pressure Gauge
Pressure Gauge for for Backup Oxygen
Export Oxygen Cylinders
Cylinders
Oxygen Cylinder
Rack
Vacuum Gauge
On/Off Switch
Connection Ports
for Cylinder
Evacuation Hoses
The touch screen on the oxygen generator control panel uses a series of screen
pages to perform the following functions:
◼ Provides a normal start-up system
◼ Monitors and controls the operation of the process valves
◼ Monitors signals coming from pressure transducers
◼ Provides an alarm system to indicate malfunctions in the PSA Oxygen
Generating System
◼ Provides a fail-safe shutdown in the event of loss in product
concentration
The main Human/Machine Interface (HMI) consists of the Schneider Electric
Magelis Touch screen. The Magelis has a 5.7” screen, which is touch-sensitive.
In order to make the software simple to use, the various screens follow a
consistent template design. Each screen consists of two components: the title bar
and the information display.
Title Bar
Local
Message
Display
Maintenance
Screen
The title bar serves two purposes. It identifies the screen that is currently being
displayed. It also acts as the main navigational tool.
No matter which screen is being currently displayed, touching the AirSep logo will
display the Main System Control screen.
The “Information Display” changes depending on the screen currently displayed.
However, they all share three basic components: Monitoring Devices, Message
Displays, and Interface Mechanisms. Monitoring Devices are components that are
used to relay real-time information about the system, like pressure graphs. Message
Displays are used to relay information pertaining to the system in a text format.
These displays are also used to present help pages that can be used to better
understand the unit. Interface Mechanisms are screen items that can be used to
interface directly with the system. These are in the form of buttons, switches, or
icons.
The Main System Control Screen is the primary source for information on the whole
unit. In the top left corner of the information display are the buttons that will start and
stop the oxygen generator.
Every time an alarm or shutdown condition is displayed on the ‘Local Message
Display’ (Refer to Figure 4.3), rectify the cause and press the ‘Alarm Reset’ icon to
bring the system into normal mode before starting.
The ‘Local Message Display’ icon displays the different status of the generator
namely Stopped, Running, Standby, and Alarm. This display will also show the
recent alarms if you push and hold.
This window will populate with the most recent, highest priority message of the
system. The priorities are listed here, from highest to lowest:
Priority List
I. Runtime Power Loss
II. Emergency Stop
III. Stopped
IV. Shutdown: High Bed Pressure
V. Shutdown: Low Instrument Air
VI. Shutdown: Low Oxygen
VII. Standby
VIII. Stop Sequence Activated
IX. Alarm: High Bed Pressure
X. Alarm: Low Oxygen Concentration
XI. Running
The icons ‘Oxygen Generator’ and ‘Output Parameters’ take the user to
dedicated screens described later in this section. Lastly, by touching ‘Screen
Cleaning’ icon at the bottom right corner of the information display, a blank
screen for cleaning purpose is displayed and the ‘Maintenance’ icon will
display a screen that provides guidelines for the general maintenance of the
unit. The ‘Silence Horn’ icon bypasses the horn for 10 minutes during an
alarm or shutdown condition.
Figure 4.4 below shows the layout of all the screens in HMI for easy navigation.
Oxygen Generator
Receiver Calibration
Figure 4.4: HMI Navigation Layout
Permanent Purity
The ‘Oxygen Generator’ Screen (Figure 4.5) is the and primary source of
information pertaining to the actual oxygen generation process. The adsorber
Horn Bypass
vessels (also called beds – Bed A is the bed on your left while facing the
control panel and Bed B is on your right while facing the control panel) are
shown in the center of the screen and the oxygen receiver vessel is shown
on the right hand side of the screen. The receiver has a numeric pressure
display. Additionally, the diagram shown will animate to indicate which valves
are currently being actuated. The ‘AUTO/MAN’ icon selects the operating
mode for the oxygen generator. In the AUTO position, the oxygen generator
cycles on and off to meet oxygen demand.
When the pressure in the product output manifold increases to approximately the
maximum pressure specified in the Appendix A, the oxygen generator stops oxygen
production after a timed delay and enters standby mode. To prevent short cycling
and maintain concentration, the oxygen generator continues to operate for five
additional cycles after increased pressure in the product output manifold. This five-
cycle delay to shutdown functions only in the AUTO mode.
When the pressure in the product output manifold decreases to approximately the
minimum pressure specified in the Appendix A, the oxygen production begins.
In the MANUAL position, the oxygen generator cycles continuously. The symbol
‘A’ at the right side of the ‘AUTO/MAN’ switch appears only when the oxygen
generator is in AUTO mode.
The ‘MANUAL DRAIN’ icon activates the drain valve when pressed.
The ‘Parameters and Output’ Screen (Figure 4.6) is the main location to observe
the several parameters of the oxygen generator. The bed pressures, oxygen
receiver pressure, oxygen concentration, and the number of working hours are all
displayed here via Message Displays.
The ‘Bed Pressure Graphs’ icon takes to the Bed Pressure Graphs Screen as
shown.
The ‘Output Parameter Graphs’ icon takes to the screen that displays the graphs
between oxygen pressure Vs time and the oxygen concentration Vs time. The
‘Next Pen’ icon changes the scale of the ordinate to suit the respective displayed
pressure.
The ‘Calibrate Pressure Transducers’ icon displays a screen dedicated to the
pressure transducers calibration and settings as shown below.
The pressure transducers for the beds and the product oxygen pressure are
factory calibrated and should not require any calibration for a long period.
However, if the need arises, follow the procedure below for calibration.
1. The three-way valve (V-A) (Figure 4.9) handle shows the direction of flow path.
In Figure 4.9, direction of flow path is from oxygen generator to pressure
transducer. Close this manual three-way valve (V-A), so that the flow path is
from the atmosphere to the pressure transducer.
2. Take out the plug, if any, from the port A (Figure 4.9) and attach a manual air
pump having an accurate pressure gauge.
3. Press the ‘Calibrate 0 psig’ icon when the gauge on the manual air pump reads
0 psig.
4. Manually pump the air so that the pressure reading on the gauge is 100 psig.
5. At this point, press the ‘Calibrate 100 psig’ icon on the calibration screen to
finish the calibration procedure.
6. Press and hold the “SET” button until it pops back out. This will save the
calibration.
7. Release pressure and check a few points in the range and ensure the reading
is close. If it is off return to step 3.
Direction of flow
path shown from
oxygen generator
to pressure
transducer
Oxygen
Generator Port A (shown open
Manifold to atmosphere
unless calibrating)
Connection
V-A
8. Disconnect the manual air pump from the port A and put the plug, if any, back
to the port A.
9. Open the manual three-way valve (V-A), so that the flow path is from the
oxygen generator to the pressure transducer as shown in Figure 4.9.
Press the ‘NEXT’ icon to navigate the calibration screen for Bed B and the oxygen
receiver pressure transducer.
5.0 Installation
5.1 Unpacking
To unpack the PSA Oxygen Generating System, follow these guidelines:
1) Inspect the shipping container, and open it immediately upon receipt.
2) If the exterior of the container is severely damaged, note it on the
freight bill before you sign it.
3) Unpack the system, and remove and discard the protective wrapping
and packaging from all the components.
4) Thoroughly inspect each component for damage.
5) Open each component cabinet, and inspect the interior for loose or
damaged parts.
6) Inspect all wiring to ensure that no wires are broken and no
connectors are off their terminals.
If a wire is disconnected, refer to the respective component manual,
located in the Appendix of this operating manual, to reconnect the wire.
All the necessary electrical connections that have to be made are tagged.
Make the appropriate electrical connections for the power supply to
the oxygen system. Refer to the power distribution diagram given in
the Appendix A of the operating manual.
15) Connect one lead from the voltmeter to the ground bus, and connect
the other lead to the neutral bus. Make sure the voltmeter reading
indicates zero voltage between the ground and neutral buses.
6.1 General
This section of this instruction manual provides the procedures for initial start-
up, normal operation, and shutdown of the system. The Appendix of this
instruction manual includes specific operating instructions and maintenance
procedures for each major component. Read and thoroughly understand all
component manuals before you attempt to start the system.
2) Provide electrical power from the main power supply to the MAIN breaker in
the main breaker panel.
3) Set the MAIN breaker to I (ON).
4) After the above two steps set the rest of the circuit breakers to I (ON), one at
a time.
5) Make sure all electrical components receive electrical power.
6) Refer to the following chart to set the position of the manual valves before
initial start-up. Make sure each valve is fully open or fully closed, as
indicated in the chart.
Normal
Valve Start- Operating
Component Valve Description No. up Position
Positio
n
Air Compressor Manual Outlet valve V-8 Open Open
Air Receiver Manual Inlet Valve V-9 Open Open
Manual Drain Valve V-10 Closed Closed
Manual Outlet Valve V-12AB Closed Open
Oxygen Generator Manual Inlet Valve# N/A Open Open
1 and 2 (V-1) and
(V-2)
Manual Product N/A Closed Open
Valve (V-3)
Oxygen Receiver Manual Inlet Valve V-13 Open Open
Manual Oxygen V-15 Open Open
Sample Valve
Manual Vent Valve V-16 Closed Closed
Manual Outlet Valve V-14 Open Open
Customer Supply V-20 Closed Variable
Valve
Manual Valve to V-19 Closed Variable
Oxygen Compressor
Hospital Piping Manual Outlet Valve V-35 Closed Variable
1) Check the oil level in the air compressor, and add oil if necessary.
2) Ensure all the shipping brackets have been removed.
3) Pull outward or rotate fully counterclockwise the emergency stop button on
the air compressor control panel to release the button from the depressed
position.
4) Start the air compressor.
If the power is turned off unexpectedly, the unit will stop cycling.
If your application is using oxygen when the power is off, the
oxygen receiver will depressurize.
4) If the oxygen purity monitoring board is provided then ensure that all the
manual valve on the oxygen sample line are open and the pressure regulator
at the inlet of the purity monitoring board is set at ~1 psig. The regulator is set
from factory and should not require any further adjustment. The oxygen
sample is typically taken from the oxygen receiver.
5) Press the ‘ALARM RESET’ icon on the Oxygen Generator Control Screen (if
visible). The generator will only start if there is no shutdown condition
existing. However, during start-up, a low purity alarm may exist. If a shutdown
condition exists, pressing the ‘ALARM RESET’ will not reset the system. The
‘ALARM RESET’ icon disappears once all the alarm and shutdown conditions
have been rectified.
Please note that during initial start-up or start-up after a long period, the
oxygen purity can be lower than the low purity alarm and/or shutdown
setpoint and a ‘low purity’ alarm may exist. However, the oxygen
generator ignores the oxygen purity shutdown setpoint for the first 60
minutes after start-up. If the oxygen purity after 60 minutes of operation
is still below the low purity shutdown setpoint, the oxygen generator
shuts down.
The low purity cut-off valve (V-17) will only open when the oxygen purity is
above the shutdown set point to allow the product oxygen to flow to your
application.
6) Set the AUTO/MAN icon on the ‘Oxygen Generator Screen’ to manual mode.
7) Press the ‘START’ icon on the ‘Main System Control Screen’.
8) Close the manual product valve (V-3) (refer to Figure 4.2 for location of
valve). The manual product valve on these units has been configured to
enable a predetermined amount of flow through the valve when closed. This
allows the product pressure to build up even when the valve is closed.
9) Press the manual drain button and make sure the exhaust from the filter drain
does not contain water or oil. If the exhaust contains water or oil, press and
hold the manual drain button on the control panel until the exhaust no longer
contains liquid.
10) Allow the oxygen generator to operate until the oxygen receiver pressure on
the ‘Parameters and Output’ screen (Figure 4.9) registers approximately 45
psig and then fully open the manual product valve (V-3).
11) To purge oxygen at less than design purity from the oxygen receiver, while
the oxygen generator is running in manual mode, open the manual vent valve
(V-16) on the oxygen receiver to vent gas.
12) Allow the oxygen generator to operate until the designed purity level is
reached. Fully close the manual vent valve (V-16) if the low purity oxygen gas
no longer discharges from the receiver.
13) Set the AUTO/MANUAL icon on the ‘Oxygen Generator’ screen to auto
mode.
14) Observe the oxygen receiver pressure on the ‘Parameters and Output’
screen (Figure 4.9). When the pressure in the oxygen receiver increases to
approximately the auto-standby upper setpoint pressure, the oxygen
generator runs for five more cycles (approx. 15 min.) and then enters
standby. When delivery of product oxygen reduces the pressure in the
oxygen receiver below auto standby lower setpoint pressure, the oxygen
generator begins to cycle.
15) After the oxygen receiver pressurizes and the oxygen generator enters the
standby mode, the generator is ready to deliver oxygen to your application.
16) After the oxygen receiver pressurizes and the oxygen generator enters the
standby mode, the generator is ready to deliver oxygen. At this stage, load
the oxygen cylinders for filling.
1) Use the vacuum pump system to evacuate the contents of the cylinders to be
filled. (Refer to Section 6.8 Evacuating Cylinders.)
2) Place the empty oxygen cylinder(s) to be filled in the cylinder rack, and chain
them in place. (Refer to Section 4 — Oxygen Cylinder Filling Station.)
3) Connect a cylinder filling hose to each oxygen cylinder, and tighten.
4) Slowly open fully (rotate handle counterclockwise) the manual valves on the
cylinder filling manifold to each oxygen cylinder.
5) Slowly open fully the manual valve on each oxygen cylinder.
Make sure the set point of the discharge pressure switch on the
oxygen compressor does not exceed the pressure rating of the
cylinders being filled.
1) Make sure the pressure gauge on the product oxygen receiver registers 65-
75 psig. (Refer to Section 4 —Oxygen Generator.)
2) Fully open the manual inlet valves (V-19) to the oxygen compressor.
3) Make sure the pressure gauge on the oxygen compressor pressure
regulator (PR-1) registers the pressure as specified in the Appendix A.
4) Press the START button on the oxygen compressor to begin to fill empty
cylinders. Make sure HAND/OFF/AUTO switch is in AUTO mode.
5) When the cylinders in the rack become fully pressurized, the oxygen
compressor automatically shuts down.
16)
The PSA oxygen generating system can also be used for a regulated supply of
oxygen at 65-70 psig using the bypass to the oxygen compressor. Following
procedure describes the oxygen supply from the bypass piping after filling the back
up cylinders.
- Fill up the back up cylinders (cylinders that get attached to the manual
valve assembly of the cylinder filling station not having check valves)
as described above.
- Allow the oxygen compressor to stop when the back up cylinders fully
pressurized. Set the HAND/OFF/AUTO switch to OFF to ensure
safety.
- At this stage, open the valve (V-20) and then the valve (V-35) to start
a regulated flow of oxygen at 65-70 psig to the customer application.
The pressure regulator PR-3 is set such that if the pressure in the bypass piping
drops below 65 psig, it allows the constant flow of the oxygen through the back up
cylinders for a certain period of time.
1) Place the oxygen cylinder to be evacuated in the cylinder rack below the
vacuum pump, and secure it in place.
2) Connect cylinder evacuation hose to an empty, depressurized oxygen
cylinder and open the connection port ball valve.
6.9 Shutdown
The procedure in this section to shut down the system protects components that
use automatic controls and isolates the oxygen in the vessels and piping to
maintain the purity of the oxygen and facilitate the subsequent restart of the
system.
If the cylinders are not full, start the oxygen compressor and fill the cylinders. When
the oxygen compressor stops, the oxygen generator runs for few more minutes
(approx. 10-20 min.) and then enters standby mode. When the oxygen generator
stops producing oxygen, the air receiver pressurizes and the air compressor
unloads.
1) Allow the oxygen compressor to stop when the high pressure oxygen
cylinders are full, then fully close the manual valve on the oxygen receiver
(V-20).
4) Make sure the AUTO/MANUAL icon on the HMI of the oxygen generator is
set to AUTO.
5) Allow the oxygen receiver to re-pressurize fully. When the oxygen receiver
re-pressurizes, after a time delay of five cycles, the oxygen generator stops
cycling and enters the standby mode.
7) Close the manual valve for the oxygen sample (V-15) to the oxygen purity
monitoring board.
8) Fully close the manual outlet valve (V-12) on the air receiver, then allow the
receiver to pressurize fully.
9) When the air receiver fully pressurizes, the air compressor will first unload.
Press the O (stop) button on the air compressor control panel to stop the air
compressor.
7.0 Maintenance
7.1 General
The PSA Oxygen Cylinder-Filling System requires only minimal
maintenance. Use the following charts as guides to provide preventive
maintenance at the specified intervals. Please note that the tables below
are summary of scheduled maintenance required on the components.
Please, refer to the component manuals, located in the Appendix of this
operating manual, for detailed information on how to maintain each
component.
8.0 Troubleshooting
The system operates with air, oxygen, and oil under pressure.
Shut down the system and slowly relieve the pressure of the air,
oxygen, and oil before removal of valves, caps, plugs, fittings,
bolts, hoses, connections, gauges, sensors, or filters.
Air Compressor
Problem Probable Cause Solution
Air compressor does not No electrical power to air Provide electrical power to
start. compressor. main breaker panel, and set
MAIN breaker and air
compressor circuit breaker
to l (ON).
Emergency stop button Pull outward or rotate
locked in depressed position. counterclockwise
emergency stop button to
release it from depressed
position.
Air compressor malfunction. Refer to air compressor
manual, located in Appendix
of this operating manual, for
additional information.
Air compressor does not Leak(s) in piping, Use soapy water to check
stop within 30 minutes of connections, or hoses. piping, connections, and
oxygen generator shutdown. hoses for leaks. Repair or
replace leaking item(s), or
reconnect fittings as
necessary.
Air compressor malfunction. Refer to air compressor
manual, located in Appendix
of this operating manual, for
additional troubleshooting
information.
Air Compressor (continued)
Problem Probable Cause Solution
Air compressor produces Air compressor malfunction. Refer to air compressor
feed air at incorrect manual, located in Appendix
pressure. of this operating manual, for
additional information.
Air compressor unloads and Obstruction(s) in feed air Locate and remove
remains unloaded. piping. obstruction(s).
Manual valves on feed air Fully open manual valves
piping or air receiver closed
or not fully open.
Air compressor stops Electrical power loss. Provide electrical power to
unexpectedly. main breaker panel, and set
MAIN breaker and air
compressor circuit breaker
to l (ON).
Air compressor malfunction. Refer to air compressor
manual, located in Appendix
of this operating manual, for
additional information.
Oxygen Generator
Problem Probable Cause Solution
Oxygen generator does not No electrical power to Provide electrical power to
cycle. oxygen generator. main breaker panel, and set
MAIN breaker and oxygen
generator circuit breaker to l
(ON).
Oxygen generator is in Allow oxygen receiver to
standby mode and oxygen depressurize during normal
receiver fully pressurized. operation, or fully open
manual vent valve (V-16) on
oxygen receiver.
‘START’ icon not pressed. Press the ‘START’ icon.
Oxygen generator Refer to oxygen generator
malfunction. manual, located in Appendix
of this operating manual, for
additional information.
Oxygen generator does not Oxygen receiver not fully Allow Oxygen receiver to
stop cycling in AUTO mode. pressurized. repressurize fully. Note: You
may need to fully close
manual outlet valve and
manual oxygen sample
valve.
Manual vent valve on Fully close manual vent
oxygen receiver not fully valve on oxygen receiver.
closed.
Oxygen compressor Shut down oxygen
continues to use oxygen compressor according to
from oxygen receiver. Section — Shutdown and
Oxygen Conditions
Problem Probable Cause Solution
Automatic low purity Low purity oxygen in low Refer to start-up procedure
shutdown occurs/low pressure oxygen receiver in Section— Start-up —
oxygen purity. not vented completely Initial.
during start-up.
Inadequate sample flow to Fully open manual oxygen
oxygen analyzer board. sample valve on low
pressure oxygen receiver
and ensure that the sample
oxygen regulator (mounted
below the control panel) is
set at 1 psig.
Oxygen analyzer board Replace the board.
malfunctions.
Incorrect feed air pressureRefer to “feed air pressure
to oxygen generator. less than…” problem in
troubleshooting chart.
Oxygen generator Refer to oxygen generator
malfunctions. manual, located in Appendix
of this operating manual, for
additional information.
Inadequate pressure in Manual vent valve (V-16) Fully close manual vent
oxygen receiver. not fully closed. valve.
Leak(s) in oxygen hoses or Use ‘soapy water’ to check
connections. hoses and connections for
leaks. Repair or replace
leaking item(s), or
reconnect fittings as
necessary.
Oxygen receiver overdrawn. Check oxygen pressure and
flow to oxygen compressor.
Oxygen generator Refer to oxygen generator
malfunctions. manual, located in Appendix
of this operating manual, for
additional information.
Oxygen Compressor
Problem Probable Cause Solution
Oxygen compressor does No electrical power to Provide electrical power to
not start. oxygen compressor. main breaker panel, and set
MAIN breaker and oxygen
compressor circuit breaker
to l (ON).
Inadequate pressure in low Refer to “inadequate
pressure oxygen receiver. pressure in oxygen
receiver…” problem in
troubleshooting chart.
Automatic low purity oxygen Refer to “automatic low
shutdown prevents oxygen purity shutdown occurs/low
delivery to oxygen oxygen purity” problem in
compressor. troubleshooting chart.
Cylinders are full. Replace the filled cylinders
with evacuated empty
cylinders.
Oxygen compressor Refer to oxygen compressor
malfunction. manual, located in Appendix
of this operating manual, for
additional information.
Oxygen compressor Leak(s) in oxygen hoses or Use ‘soapy water’ to check
operates continuously. connections. hoses and connections for
leaks. Repair or replace
leaking item(s), or
reconnect fittings as
necessary.
Oxygen compressor Refer to oxygen compressor
malfunctions. manual, located in Appendix
of this operating manual, for
additional information.
AirSep PSA
Oxygen System: AS-J-600-HMFM DUPLEX
Oxygen output:
Site conditions:
Elevation:
Chiller:
Oxygen generator:
Oxygen Analyzer:
B Appendix: Warranty/Returns
Product Warranty
AirSep Corporation (“AirSep”) warrants to the party purchasing from AirSep (the
“original purchaser”) the AS-J-600-HMFM DUPLEX PSA Oxygen System to be free
from defect in parts and workmanship for one year from the date of start-up, not to
exceed eighteen (18) months from the date of shipment to the original purchaser,
under normal use, maintenance and operation*. TO THE EXTENT PERMITTED
UNDER APPLICABLE LAW, ALL WARRANTIES WITH RESPECT TO SUCH UNIT
SHALL ONLY EXTEND TO AND BE FOR THE BENEFIT OF THE ORIGINAL
PURCHASER AND SHALL NOT BE ASSIGNABLE TO, EXTEND TO OR BE FOR
THE BENEFIT OF ANY OTHER PARTY. AirSep’s obligations under this warranty
are limited, at AirSep’s option, to the repair, replacement or refunding the purchase
price of any such system of equipments (or part thereof) found by AirSep to be
defective in parts or workmanship; provided, however, that AirSep shall have no
obligation hereunder with respect to a defective part unless it receives written
notice of such defect prior to the expiration of the applicable warranty period as
referenced above.
Each unit of equipment for which a warranty claim is asserted shall, at the request
of AirSep, be returned on a prepaid basis with proof of purchase date to the AirSep
factory specified by AirSep at the expense of the original purchaser. Replacement
parts shall be warranted as stated above for the unexpired portion of the original
warranty. This warranty does not extend to any unit or part subjected to misuse,
accident, improper maintenance or application, or which has been repaired or
altered outside of the AirSep factory without the express prior written authorization
of AirSep.
Notwithstanding anything to the contrary contained herein, during the applicable
warranty period, as specified above, AirSep will pay the cost of return freight
charges to the original purchaser, provided an authorized AirSep representative
approved return of the unit or parts, for any equipment found by AirSep to be
defective. For warranty repairs performed during the first 90 days from the date of
invoice, AirSep will pay freight both ways. After the applicable parts warranty
period has expired, the original purchaser is responsible for freight both ways.
* Please refer to the appropriate product documentation for applicable installation and operating
requirements.
Limits of Liability
THE FOREGOING WARRANTY IS THE ONLY WARRANTY MADE BY AIRSEP
WITH RESPECT TO THE SYSTEM (OR ANY PART THEREOF) AND IS IN LIEU
OF ANY OTHER WARRANTY, EXPRESSED OR IMPLIED, IN FACT OR IN LAW,
INCLUDING WITHOUT LIMITATION ANY WARRANTIES OF MERCHANTABILITY
OR FITNESS FOR ANY PARTICULAR PURPOSE. IT IS EXPRESSLY
UNDERSTOOD THAT THE SOLE AND EXCLUSIVE REMEDY FOR ANY DEFECT
IN PARTS OR WORKMANSHIP IS LIMITED TO ENFORCEMENT OF AIRSEP’S
OBLIGATIONS AS SET FORTH ABOVE, AND AIRSEP SHALL NOT BE LIABLE
TO ORIGINAL PURCHASER OR ANY OTHER PARTY FOR LOSS OF USE OF
THE EQUIPMENT, LOST PROFITS OR FOR ANY OTHER SPECIAL, INDIRECT,
INCIDENTAL, OR CONSEQUENTIAL DAMAGES (EVEN IF AIRSEP HAS BEEN
ADVISED OF THE POSSIBILITY OF SUCH DAMAGES).
2) Write the RGA number clearly on the outside of the shipping container.
Oxygen Generator
AS-J 1 AirSep Corporation
AS-D+ – AS-P Oxygen Generator With HMI
Instruction Manual
Oxygen Compressor
2V3 1 Rix Industries
2V3
Operating Instructions and Parts List