8" Ø PIPE

13'' MAX
3"

4"
12''

4"

8"

PLAN VIEW

HSS 6" X 6" X 1/4" A500 Gr.B


TYP. (Fy=46 ksi),TYP.
1/4
1
4'' THK. END PLATE TYP.
TYP.
12" x 8" x 1/2" THICK A36
C.S. PLATE TYP.
KINETICS RSP 12" x 8" x 3/4" 4''
VIBRATION ISOLATION PAD TYP.

MIN. 2.25" NOM.


EMBED. TYP.

1
2" Ø HILTI KWIK HUS-EZ ANCHOR,
w/ MIN 214" NOM. EMBED, KEEP MIN
6" EDGE DISTANCE. SPECIAL 6" MIN. EDGE
INSPECT. PER ESR-3027. TYP. (6) DISTANCE
LOCATIONS PER PALTE
12" MAX PIPE SLEEVE OR
CORE BY OTHERS TYP.
1/8" GAP
FIRE STOP MIN. 412" THICK, MIN 3750 PSI
(NON-FLAMABLE MATERIAL) LWC SLAB BY OTHERS
BY OTHERS. TYP.
ELEVATION VIEW 2 - PHD FIG. 550 RISER CLAMPS ONLY
AT LEVEL 14

8" - PIPE RISER


NOTES:
1. APPROVAL FROM ENGINEER OF RECORD REQUIRED MAIN ANCHOR SUPPORT
PRIOR TO INSTALLATION.
2. DRAWING NOT TO SCALE MAX LOADS FOR BOTTOM MAIN ANCHORAGE
3. REFER TO PIPE RISER ELEVATION DRAWING FOR
ANCHORAGE LOCATION AND TYPE LOCATION:
4. REFER TO PIPE RISER ELEVATION DRAWING FOR FLOOR 1) DEAD LOAD = 4200 LBS.
ELEVATIONS. 2) PRESSURE THRUST = 7020 LBS (DOWNWARD)
5. POST INSTALLED ANCHORS TO BE INSTALLED IN MAX LOADS FOR TOP MAIN ANCHORAGE
CONCRETE AGED A MINIMUM OF 28 DAYS, UNLESS LOCATION :
OTHERWISE SPECIFIED IN THE ICC ESR REPORT
1) DEAD LOAD = 350 LBS.
6. TENSILE STRENGTH OF WELD ELECTRODE SHALL NOT
BE LESS THAN 70 KSI CONFORMING TO AWS 2) PRESSURE THRUST = 2900 LBS (UPLIFT)

REV # SHEET NUMBER


PROJECT
CALIFORNIA MARKET CENTER -
(BLDG. B)
LOS ANGELES, CA
DATE
5/18/2020
D1
International Seismic Application Technology CONTRACTOR
14848 Northam Street, La Mirada, CA 90638 SOUTHLAND INDUSTRIES DRAWN BY
877-999-4728 (Toll Free) 714-523-0845 (fax) JOB NUMBER
www.isatsb.com MOD 173956