You are on page 1of 1

5/8" DIA MOUNTING

HOLES(TYP)
NOTES: 1,748 1,573
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL 81 13/16"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,334, OPERATING - 5,762. 3 1/8"
3. CENTER OF GRAVITY FROM ORIGIN: X= 63.1", Y= 50.6" . 1 1/16" (TYP)
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. 1" NOMINAL DEFLECTION SPRING ISOLATORS (NOT SHOWN) WILL
1,285 1,157
INCREASE OVERALL UNIT HEIGHT BY APPROXIMATELY 6". ORIGIN
7 5/8" 117 3/16"
13/16"
Y TOP VIEW

POWER ENTRY CG X
13 1/2" WIDE X 7" HIGH
46 3/8"

VIEW B-B
BOTTOM OF PANEL

94 3/16"
B B 6"
(WATER
INLET)
2X 6"
(WATER OUTLET)

42 3/4"

2X 15"

30 3/4" (2) RIGGING HOLES


18 5/8" EACH SIDE 23 1/8"
TO CLR CONN
23 1/8" 38 5/8"
88 1/4" BASE WIDTH
89"
142 1/4"
FRONT VIEW RIGHT VIEW
POWER: SINGLE POINT NON-FUSED DISCONNECT SWITCH

Project Name : Arlington Service Center Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.62-EG3
MODEL: YLAA0091HE17 Contractor : UNIT Dwg. Lev. : 01/08
A JOHNSON CONTROLS COMPANY
NOT FOR CONSTRUCTION For : N/A TAG: YLAA Dwg. Scale : NTS