Professional Documents
Culture Documents
5. Calibrating Valve Position (for a Position Proportional Controller Only) 6. Initializing Parameters List of Alarm Types
The following operating procedure describes an ex- Control output terminal Values in parentheses are setpoints The following operation describes a procedure of inputting a feedback signal from a control valve to calibrate the full closed and full Be sure to follow the steps below after a change of setting has been made to the data item PV Input Type, PV Input Range or The table below shows the alarm types and alarm actions.
ample of changing time proportional PID relay out- Time proportional PID relay (0)/on-off(3) output........................... 1 - 2 - 3 open positions of the valve automatically. To calibrate the valve position, you need to carry out wire connections and bring the controller PV Input Scale. In the table, codes 1 to 10 are not provided with stand-by actions, while codes 11 to 20 are provided with stand-by actions.
put (0: factory-shipped value) to current output (2). Current (2)/time proportional PID voltage pulse (1) output................. 16 - 17 into manual mode. For connections, see “6. Terminal Wiring Diagrams” in Installation User’s Manual and for entering the
For details on the output terminals for heating/cooling control, see
manual mode, see “8. Switching between AUTO and MAN” in Operations User’s Manual . CAUTION Alarm action
Alarm type code
Alarm action
Alarm type code
“6. Terminal Wiring Diagrams” in the Installation User’s Manual . Alarm type
Contact Contact
Alarm type
Contact Contact
“Open/close” shows status of relay contact, closes opens “Open/close” shows status of relay contact, closes opens
1. Bring the operating display into view (display
7. Press the key once to display “ON”. Initializing the above parameter setpoints may initialize the registered operating/setup parameter setpoints. Check
and “lit” and “unlit” shows status of lamp
if alarm if alarm
and “lit” and “unlit” shows status of lamp
if alarm if alarm
appears at power on). occurs occurs occurs occurs
that they are correct. If any of them has been changed to its initial value, set it to a required value.
1. Bring the operating display into view (display 6. Press the key several times to display the
S ET/ EN T
parameter
RE M
MAN
PV Displays PV
target setpoint-1 “1.SP”.
A/ M A /M
AL1 2 3 4 AL1 2 3 4
PV. Hysteresis Hysteresis
“OT”.
S ET /EN T SE T/EN T
“1.SP”. Hysteresis
Displays RE M Displays RE M
2 Closed Open Closed 7
A/M A/ M
MA N MAN
Deviation high (lit) (unlit) (lit)
8. Press the key once. The controller target setpoint-1 parameter PV low limit Closed (lit) Open (unlit)
2. Press the key for more than 3 seconds to
SE T/EN T
2. Press the key for more than 3 seconds to call 7. Press the or key to display the required open or closed). A/M A/ M
Target SP
S ET/ EN T
S ET/E N T SE T/E NT
up the menu “OP.PA”. setpoint. The figure below shows an example of Hysteresis Closed Hysteresis
PV PV Hysteresis
setting to current output (4 to 20 mA DC). (lit)
2. Press the key for more than 3 seconds to call 7. Press the key to display “ON”.
S ET/E N T
limit
RE M
“OP.PA”.
M AN M AN
limits PV
Displays menu Blinks during symbol “D-U”. AL1 2 3 4 AL1 2 3 4
PV Deviation setpoint 13 Deviation setpoint 18
Displays REM RE M
change. PV PV Target SP
“OP.PA”. Target SP
MA N MAN
symbol “D-U”. A L1 2 3 4 A L1 2 3 4
A/M A/M
S ET/ EN T S ET/ EN T
change. 4 9
“OP.PA”.
MAN MAN
SE T/E NT SE T/E NT
symbol “D-U”. Deviation low Closed (lit) Open (unlit) De-energized Closed
3. Press the key once to display the menu “STUP”.
A L1 2 3 4 A L1 2 3 4
Press the
S ET /EN T
5 10
PV PV
Displays menu The indication “STUP”. momentarily becomes blank (which is normal),
De-energized on
Closed Open (lit) De-energized Closed
deviation high (unlit) Open (lit)
REM
MA N
“STUP”.
RE M
MAN
“ON” blinks. indicating the parameters have been initialized. limit alarm Deviation
on PV low limit (unlit)
RE M
Displays menu RE M
A L1 2 3 4 A L1 2 3 4
PV setpoint 15
Alarm setpoint PV
20
M AN
“STUP”.
M AN
PV PV Target SP
AL1 2 3 4 A L1 2 3 4 A/ M A /M
Sensor
Displays menu Upward (hour/minute) 21
S ET /EN T SE T/EN T
A /M A/ M REM RE M
grounding Sensor grounding alarm 25
“STUP”. alarm
MA N MAN
4.
A L1 2 3 4 A L1 2 3 4
Press the key once to display the menu “SP”. 10. Calibration is complete when the indication Fault diagnosis
SE T/E N T
Displays target
RE M REM
A /M A/M MA N
M AN
Hysteresis Hysteresis
If the controller shows “ERR”, check the feedback setpoint “1.SP”.
SE T/E NT SE T/E N T
“I/O”. Press the key twice to display the menu “VALV”. S ET/ EN T
Alarm setpoint SP Alarm setpoint Output value
This returns you to the display shown at power on
Note 1: The fault diagnosis output turns on if there is an input burnout, A/D converter failure, or reference junction compensation (RJC)
PV
Displays (figure below). 5. Press the key once to display the menu “INIT”.
failure. For input burnout or A/D converter failure, the control output is set to the setpoint of the Preset Output Value (operating
menu “I/O”. Displays parameter PO).
PV Displays PV
REM
PV. Note 2: The FAIL output is on under normal operation and turns off if there is a failure.
menu “VALV”. PV
Displays
M AN
Displays
A L1 2 3 4
RE M
MAN
RE M
MA N menu “INIT”.
A/M A L1 2 3 4 target setpoint-1 AL1 2 3 4
RE M
MA N
“1.SP”. C
Stand-by Action
S ET/ EN T
Normal Abnormal
A L1 2 3 4
A/ M A /M
S ET/ EN T SE T/E NT
A/M
Treated
S ET/E N T
as normal The alarm
It is effective in the following cases output turns on.
6. Press the key once to display the parameter
SET /EN T
parameter -7
6 )............PV high limit alarm if the PV value is below the
(however, except for remote setpoint)
AL1 2 3 4
1 Time proportional PID voltage pulse output (terminals 16 - 17 ) “V.AT”. alarm. Alarm-2 (terminal numbers -7
5 )............PV low limit alarm
2 Current output (terminals 16 - 17 ) - the alarm type is changed low limit of the alarm setpoint.
When you have changed alarm type, the alarm setpoint will be initial- Alarm-3 (terminal numbers 4 - 7 )............PV high limit alarm
A/M
S ET/ EN T
3 On/off control relay contact output (terminals 1 - 2 - 3 ) ized; set the alarm setpoint again. Alarm-4 (terminal numbers 34 - 35 )............PV low limit alarm
The following 4 to 12 are displayed only for heating/ cooling type controllers.
Power-on Time
4 Heating-side relay output (terminals 1 - 2 - 3 ), 1. Bring the operating display into view (display 6. Press the key once to display the parameter
SET /EN T
SE T/E N T SE T/EN T
(2.SP), proportional band (heating-side proportional band) (2.P), integral time (heating-side integral time) (2.I), derivative
8 Heating-side pulse output (terminals 16 - 17 ), time (heating-side derivative time) (2.D), cooling-side proportional band (2.Pc), cooling-side integral time (2.Ic), and cool-
cooling-side pulse output (terminals 46 - 47 )
7. Press the or key to display the required ing-side derivative time (2.Dc).
2. Press the key for more than 3 seconds to
SET /EN T
cooling-side current output (terminals 46 - 47 ) SPN=1 1.SP 1.P 1.I 1.D 1.Pc 1.Ic 1.Dc
SPN=2 2.SP 2.P 2.I 2.D 2.Pc 2.Ic 2.Dc
A/M A/M
SE T/E N T S ET/E N T
A /M A/M
SE T/E NT S ET/ EN T
A L1 2 3 4
setpoint-1 “1.SP”. A L1 2 3 4
A/ M A/M
S ET /EN T SE T/E N T
5. Press the key once to display the menu “ALM”. 10. See “5. Setting Alarm Setpoints” in
Operations User’s Manual when setting an
PV Displays alarm setpoint.
menu “ALM”.
REM
MA N
AL1 2 3 4
A/M
S ET/ EN T
IM 05D01C12-02E (2)