I. System Description:
SAFELOK Standards and ledgers with base at the bottom and U head jack at the top to
provide the supporting grid under the beam.
Primary Decking is SW150-75 Alum. beams and Secondary Decking are Aluminum Beam
SW150-75 with cladding plywood to provide the beam bottom formwork decking.
Beams side shutters timber by site.
II. Dimensions:
1. Cladding :(Plywood18mm)
Considering 1.0m width
MATERIAL PROPERTIES VALUE UNIT
Bending Stiffness, 𝐸𝐼 3.23 kN.m²/m
Moment of Resistance, 𝑀 = 𝑓𝑍 0.834 kN.m/m
Shear Load, 𝑞𝐴 15.55 kN/m
IV. Loads:
DESIGN PARAMETERS
1.0 Concrete Density = 25.0 kN/m³
2.0 Live Load = 2.50 kPa
3.0 Formwork Weight = 0.50 kPa
4.0 Impact Load = 20% From Weight of Concrete
TECHNICAL DEPARTMENT PAGE 4 OF 7
RIYADH BRANCH REV. 0
CALCULATION SHEET DATE: 09-NOV-20
PREPARED BY: DENNIS
CLIENT NAME: SSEM DESIGN: BEAM
PROJECT TITLE: MASHTAL PUMP STATION DWG REF. NO.: UNI20-R-300
LOCATION: QASSIM BRAIDAH, KINGDOM OF SAUDI ARABIA DRAWN & DESIGN BY: DSM
Note: Formwork use only: face contact material continuous over four or more supports with L
< 610mm and width of support B wider than 2t.
𝑤𝐿
𝑀=
10
V. Lateral Stability
6.4.4 Lateral stability (BS 5975: 1996)
6.4.4.1 General
To ensure the lateral stability of falsework structures, including beam grillages, they should be
designed to be able to resist at each phase of construction the applied vertical loads and the greater of
either:
a) horizontal forces equivalent to 2.5 % of the applied vertical loads considered as acting at the
points of contact between the vertical loads and the supporting falsework; or
b) the horizontal forces that can result from wind, erection tolerances, non-verticality, concrete
pressures, water and waves as described in 6.3.1.3, dynamic and impact forces as described in 6.3.1.4
and the forces generated by the permanent works as described in 6.3.1.5.
A. From dead load:
F = 1.23(0.85)(1.2)(1.50) = 1.88 kN
* Bracing tubes to transfer total force of 1.88 kN
* Swivel coupler capacity 5.0 kN
* No of required couplers = 1.88/5.0 = 0.38 ≈ 1 coupler <= 1.0 actual tubes no. in the bay.
DESIGN CALCULATION
2.2m thk. x 4.6m High Wall Double Side Wall
Project Information Ref. Dwg. No. Rev. Shts. NO
Proj. Title: MASHTAL PUMP STATION
UNI20-R-300 0 1 of 10
Engineering Location: Qassim, Kingdom of Saudi Arabia
Department Client: SSEM Design by: Date
Calculation Sheets Address: Riyadh, Kingdom of Saudi Arabia DSM 09-11-20
GENERAL:
Using Steel Soldier System a Steel Grade ASTM A36 specification / 3.20mm. thick plate minimum yield
stress of 248.2 Mpa. The premise of this design is to design a wall formwork to ensure & determine the
capacity of all elements are safe and most economical for intended dead loads & live load.
The system has major components the steel soldier, aluminum beams, ( Tie System ) which includes
tie rods, waler plates, wing nuts,etc & the horizontal butting.
See all Soldier System Accessories - Brochure Ref.: Guide For Shoring & Formworks.
REFERENCE DOCUMENTS:
1. Formwork ( A guide to a Good Practise ) 2nd. Edition 1995 - Concrete Society
2. Load Certificate ( Fugro Suhaimi Ltd. )
C. PLYWOOD :
Properties of PlywoodReference:
: Formwork ( A Guide to a Practice ) Section 3.2.2 page 38
Appendix G
See Attachment :
The Structural Properties of the Plywood BIRCH
Plywood thickness: 18 mm @ 1.0m.
Moment of Resistance, M = 0.834 kN-m/m
Bending Stiffness, EI = 3.23 kN-m²/m
Shear Load, qA = 15.55 kN/m
Deflection, L/300 = 1.00 mm
D. TIE ROD :
Tensile Strength = 90 kN ( See Fugro Suhaimi Test Report )
Diameter = 16 mm
DESIGN CALCULATION
2.2m thk. x 4.6m High Wall Double Side Wall
Project Information Ref. Dwg. No. Rev. Shts. NO
Proj. Title: MASHTAL PUMP STATION
UNI20-R-300 0 2 of 10
Engineering Location: Qassim, Kingdom of Saudi Arabia
Department Client: SSEM Design by: Date
Calculation Sheets Address: Riyadh, Kingdom of Saudi Arabia DSM 09-11-20
0.00
0 10 20 30 40 50 60
𝐹
θ = 82 ° 0.00
𝜃 0 10 20 30 40 50 60
Uplift Force, 𝐹 = 𝐹 cos 𝜃 = 34.07 kN
To Prevent Uplift Force need Tie the Soldier Using Tension 𝐹
Rod (see drawing)
Free Body Diagram of Soldier (Horizontal Member)
Due to the Uplift Force, 𝐹
Diagram A 𝐹 = 34.07
∎𝑜
𝐿 𝐿 𝑇
𝑅 𝑇
Soldier to Soldier Connection
L1 = 1.532 m L2 = 0.337 m
Check Connection Soldier To Soldier(Using M16(8.8))
Diameter of Bolt = 16 mm
Area of Bolt, (A) = 402.12 mm² double Determine the value of T from Diagram A.
Allowable Shear Stress of Bolt shear
+ ∑ 𝑀 = 0]
𝐹 = 0.35𝐹𝑦 𝐹𝑦 = 0.8𝐹 = 640 Mpa
Where, Fu(Ultimate Strength of Bolt) 𝑇 𝐿 −𝐹 𝐿 + 𝐿 = 0
Fu = 800 MPa Fv = 224 Mpa 𝑇 = 41.57 kN Tension
Allow. Shear of Bolt
𝑉=𝐹 𝐴 Determine the value of R
V = 224 * 402.12 +↑ ∑ 𝐹 = 0]
= 90.08 kN
Total Shear of Bolt is 2*V = 180.15 KN 𝑅 −𝑇+𝐹 =0
Since, 𝑅 = 7.49 kN Comp.
Actual Allow.
34.07 < 180.15
kN kN
Therefore, Bolt Connection is Safe
DESIGN CALCULATION
2.2m thk. x 4.6m High Wall Double Side Wall
Project Information Ref. Dwg. No. Rev. Shts. NO
Proj. Title: MASHTAL PUMP STATION
UNI20-R-300 0 6 of 10
Engineering Location: Qassim, Kingdom of Saudi Arabia
Department Client: SSEM Design by: Date
Calculation Sheets Address: Riyadh, Kingdom of Saudi Arabia DSM 09-11-20
7.0 Check Tension Rod (Due to Wind Load)
See calculation of Wind Below
CASE 1 (Wind Direction) CASE 2 (Wind Direction)
27.17 27.17
𝑅 𝑅 4.8
𝑅 𝑅
4.8
∎𝐴 ∎𝐵
𝑇 0 0 𝑇
Diagram B Diagram C
Soldier Shoring 1 Soldier Shoring 1
R1 = 27.17 kN (tension) α 58 R1 = 27.17 kN (Compression) α 58
Vertical Component of R1 Vertical Component of R1
𝑅 = 𝑅 sin 58 = 23.04 kN 𝑅 = 𝑅 sin 58 = 23.04 kN
Soldier Shoring 2 Soldier Shoring 2
R2 = 4.8 kN (tension) 𝛽 34 R2 = 4.8 kN (Compression) 𝛽 34
Vertical Component of R2 Vertical Component of R2
𝑅 = 𝑅 sin 34 = 2.68 kN 𝑅 = 𝑅 sin 34 = 2.68 kN
From Diagram B From Diagram B
+ ∑ 𝑀 = 0] + ∑ 𝑀 = 0]
Moment Arm of R1v @ A Moment Arm of R1v @ B
x1 = 2.293 m x1 = 0.493 m
Moment Arm of R2v @ A Moment Arm of R2v @ B
x2 = 1.618 m x2 = 0.182 m
Moment Arm of T @ A Moment Arm of T @ B
x3 = 2.068 m x3 = 1.532 m
𝑅 𝑥 −𝑇 𝑥 +𝑅 𝑥 =0 eq. 1 −𝑅 𝑥 +𝑇 𝑥 +𝑅 𝑥 =0 eq. 2
Substitute all the value from eq.1 Substitute all the value from eq.2
T = 27.65 kN (tension) T = 7.10 kN (tension)
V = 190 KPh
Basic Wind Speed
V = 52.8 m/sec. Qassim Braidah
𝛼
d1 1.752 m d2 2.76 m 4.70
Horizontal Force of R1 d2
Rh1 = 14.40 kN 𝛼 = 58 °
Horizontal Force of R2 Rh2
Rh2 = 3.98 kN 𝛽 = 34 ° 𝛽
3.91
Calculate the Resultant Force on Each Soldier
Axial Force of R1 Axial Force of R2
𝑅 𝑅
𝑅 = 𝑅 =
cos 𝛼 cos 𝛽
R1 = 27.17 kN R2 = 4.8 kN
2𝜋 𝐸 Cc = 126.12
𝐶𝑐 =
𝐹𝑦
𝐹𝑡 = 0.33𝐹𝑢
When KL/r < Cc (Short Column)
Allowable Fa is:
𝐾𝐿/𝑟 𝐹
𝐹 = 1− 𝑒𝑞. 1 Fa 115.58 MPa
2𝐶 𝐹. 𝑆.
5 3(𝐾𝐿/𝑟) 𝐾𝐿/𝑟
𝐹. 𝑆. = + − F.S. 1.85
3 8𝐶 8𝐶
12𝜋 𝐸
𝐹 = 𝑒𝑞. 2 Fa 233.79 MPa
23 𝐾𝐿/𝑟
Since, KL/r < Cc Use equation 1
66.37 126.12
Therefore,
Fa = 115.58 MPa
Analysis
Downward Force Due to Wind Load
R R
R = 27.17
R = 4.8
𝛼 = 58° 𝛽 = 34°
R R
𝑅 = 𝑅 sin 𝛼 𝑅 = 𝑅 sin 𝛽
18.38
Design Number of Anchor Bolt
From Hilti Catalouge
18.38
N =
3.3 capacity/bolt
N = 5.57 say 6.0 nos