Professional Documents
Culture Documents
The microprocessor-controlled Positioner EP200 is used for analog (4 ... 20 mA) control and
feedback of pneumatic actuators. It offers extended functionality of advanced positioner, such
as Autostart for the determination of the best control parameters, and comfortable in-the-field
operation.
Additional equipment:
• Integrated inductive limit switches, independent of device electronics
• Easy local operation with three key pads
• Multi-Lingual full text graphical LCD
• Load 300 Ω
• Low air consumption
• Stroke 8 to 120 mm (optional up to 260
mm
• Angle range up to 95 degree
• Supply air pressure up to 6 bar (90 psig)
• Single acting or double acting
• Position Feedback 4-20 mA and Alarm,
galvanically separated
• Mechanical travel indicator
• Reverse polarity protection and Interlock
diode
• Autostart with self-calibration
• Attachment to rotary actuators according
to VDI/VDE 3845
• Protection class IP 65 and NEMA 4X
Accessories:
• Gauge attachment for supply air and
outputs
• Booster relays
E00003-A-02
2 EP200 Master Instruction
TABLE OF CONTENTS
CHAP: CONTENT PAGE CHAP: CONTENT PAGE
9 DECOMMISSIONING . . . . . . . . . . . . . . . 31
2 LABELS . . . . . . . . . . . . . . . . . . . . . . . . . . 5
10 SAFETY REQUIREMENTS . . . . . . . . . . . 32
3 DESIGN. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1 Accessories . . . . . . . . . . . . . . . . . . . . . . . . 7 11 TROUBLE-SHOOTING GUIDE . . . . . . . . 33
12 MAINTENANCE . . . . . . . . . . . . . . . . . . . . 38
4 MOUNTING TO ROTARY ACTUATORS. . 8
13 OPTIONS . . . . . . . . . . . . . . . . . . . . . . . . 39
5 SYSTEM CONFIGURATION . . . . . . . . . . 10 13.1 Limit switch . . . . . . . . . . . . . . . . . . . . . . . 39
5.1 Application . . . . . . . . . . . . . . . . . . . . . . . . 10 13.2 Additional Inputs / Outputs . . . . . . . . . . . . 40
5.2 Split Range . . . . . . . . . . . . . . . . . . . . . . . 10
14 DIMENSIONS . . . . . . . . . . . . . . . . . . . . . 41
E00003-A-02
EP200 Master Instruction 3
1 METHOD OF OPERATION
1.1 General
y
The intelligent positioner EP200 1 and the pneumatic ac-
tuator 2 form a control loop with the setpoint value w (from
master controller or control system), the output pressure y
and the position x of the actuator on valve 3 . 2
w
The positioner can be attached to both linear and rotary
actuators. x
Actuators with spring force are controlled by a single acting 1
positioner. Actuators without spring force are controlled by a
double acting positioner.
For the supply air, we recommend the
FOXBORO ECKARDT FRS923 filter regulator.
3
,
1. '
' ! "
)
y1 Output
1
Input w pressure
4...20 mA , 2 y2 to actuator
analog
% m + #
$
7
x Position
c o n s t.
of actuator
&
1.3 Operation
With the intelligent positioner with input signal 4-20 mA, the The pneumatic amplifiers are supplied with supply air s
supply takes place via the power signal adjacent to the 1.4 to 6 bar (20 to 90 psig).
input. The position x of the actuator is sent to the control unit 11
by the position sensor (conductive plastic potentiometer)15.
By means of voltage converter 7, derivation of the internal
Optional inputs / outputs 21 (two binary outputs; a 4-20 mA
supply of the electronics takes place. The power value is
output and alarm; control inputs for ‘Open/Close’ and ‘Hold
measured, in A/D transformer 9 converted, and directed via
last value’) enable additional diagnostic indications and
switch 10 to digital controller 11 .
possible intervention.
The mechanical limit switch 22 (optional) enables indepen-
The output of controller 11 drives the electro-pneumatic
dent alarm signals.
converter (IP-module) 12, controlling a pre-amplifier 13, the
single acting (or double acting) pneumatic power amplifier Adjusting, start-up of the positioner as well as the demand
14. The output of the amplifier 14 is the output pressure y for internal information can be made using the local keys 17
to the actuator. with indication given by LCD 18 .
E00003-A-02
4 EP200 Master Instruction
INITIALIZE:
Upon power-up or Reset (pressing of the 3 keys simultan-
eously), several self-tests are conducted. Individual steps in
the self-test process are indicated by the LCD.
OUT OF SERVICE:
If no error occurs the device moves to OUT OF SERVICE,
The EP200 in delivered condition is configured in such a
if it is still in a delivery condition; AUTOSTART has to be
way that it will remain OUT OF SERVICE after power-up
performed. If AUTOSTART was done already, the device
until moving to IN OPERATION via the manually initiated
will go to IN OPERATION.
function AUTOSTART.
If faults are detected, the code of the faulty self-test will In the device state OUT OF SERVICE, the menu entering
remain (see page 33). If error reoccurs after reset, the mode remains active at all times. If a device has been IN
device is probably defective and should be sent in for OPERATION already and is removed from an actuator and
repair. mounted to another, it is recommended to take the device
out of operation via RESET CONFIG (Menu 9.1) prior to
DEVICE FAULT: disconnecting the device from the first actuator.
Device faults are detected during cyclical self-test. This enables the next actuator to be started in the delivered
The device can no longer be operated. condition (see chapter 8).
This could be caused by a jammed menu key, defective
program memory, etc. (see chapter “Trouble-shooting”). CALIBRATE:
By reset this state disappears until the same error is During an AUTOSTART function the device is in condition
detected again. CALIBRATION. The actuator is moved up- and downward
If a device error occurs repeatedly, the device should be several times, and the device could be busy for a few
sent in for repair. minutes. Subsequently, the device moves to IN OPERATION.
IN OPERATION: MESSAGE:
After performing an AUTOSTART, the device moves to The EP200 continuously supervises important device
IN OPERATION. functions. In the event that limit values are exceeded or
It will always, even after restarting or resetting, move back operational problems occur, messages are signaled via the
to IN OPERATION. LCD.
The message with the highest priority will be indicated first.
With key DOWN additional messages can be called up,
with key UP the measuring values can be retrieved. It is
possible at all times to reach the menu by pressing the
menu keys to possibly eliminate the problem by performing
suitable menu functions. Further references may be found
in chapter “Trouble-shooting”.
Possible operator interventions are described in chapter:
START-UP.
E00003-A-02
EP200 Master Instruction 5
Definitions
Angle range is the rotary range of rotary actuator.
0 % position is the mechanical impact at actually closed valve (caution if using handwheel and mechanically adjust-
able stroke limitation!)
100 % position is the mechanical impact at actually open valve.
Closing limit is a lower limit set via software. In normal operation the valve will not close more than set here.
Attention: In the event of failure of the auxiliary energy no controlling is possible, therefore the springs in
the actuator will move the valve into safety position (for single-acting actuator).
Opening limit is a upper limit set via software. In normal operation the valve will not close more than set here.
Attention: In the event of failure of the auxiliary energy no controlling is possible, therefore the springs in
the actuator will move the valve into safety position (for single-acting actuator).
Normal operation (= IN SERVICE) means that the position is controlled to the 4–20 mA input signal.
2 LABELS
A
A Nameplate
Nameplate (Example)
E00003-A-02
6 EP200 Master Instruction
8 1 0 2 1
3 DESIGN
4
3 b
3
3 a
2 1 0 9 1 1 2 6
1 2 4
6
1 2
1 3
7
1 4
1 9 1 6 a
1 5
2 0
E00003-A-02
EP200 Master Instruction 7
3.1 Accessories When mounting, check the proper seating of the O-rings
and bolt on the accessories with the two M8 bolts. Unused
outputs are closed by means of plastic plugs.
3 x
G 1 /4
y (y 1 )
s
(y 2 ) L
B
H
L x B x H =
1 0 1 ,5 x 6 0 x 1 0 0 ,5 m m
C o d e L E X G -G 1
B o o s te r fo r p o s itio n e r
y 1
s
3 x
G 1 /4
y 2
L x B x H =
1 2 1 x 3 9 x 8 1 m m
C o d e L E X G - M 1
C o n n e c tio n m a n ifo ld fo r p o s itio n e r
w ith p r e s s u re g a u g e s fo r
s u p p ly a ir s , o u tp u ts y 1 a n d y 2
y 1
s 3 x
y 2 G 1 /4
3 x G 1 /8 fo r
G a u g e *
L x B x H =
1 0 0 x 3 0 x 4 5 m m
C o d e L E X G -N 1
C o n n e c tio n m a n ifo ld p o s itio n e r
w ith th re a d s G 1 /8 fo r p re s s u re g a u g e s
fo r s u p p ly a ir s , o u tp u ts y (y 1 ) a n d (y 2 )
(s u p p lie d w ith o u t p re s s u re g a u g e s )
y (y 1 )
* U n u s e d th re a d s fo r p re s s u re g a u g e s a re
s c lo s e d b y m e a n s o f p la s tic lo c k s c r e w s .
3 x
(y 2 ) G 1 /4
E00003-A-02
8 EP200 Master Instruction
B * R
manual feeding of compressed air.
Without electrical power, y1=zero and y2=supply.
1 .9 7
in
5 0
The side outputs I (or I and II) are used. The rear output I is
closed by means of a lock screw.
Pneumatic connections: Do not use Teflon tape for seal-
ant. The fine fibres could disturb the function of the EP200.
Use only Loctite® #243 for sealant 1). Coupling piece
Screw-type glands for electrical connections are used as Reference points B*
1 4
.5 5
needed. Any unused threaded holes are closed by plugs. see illustration left
8
.3 1
Caution! Prevent accumulation of water in the instrument
in this mounting position by sealing cable entry against L R
water. Provide a continuous supply of dry instrument air.
B * B *
.3 9
1 0
M 4
.6 7
1 7
1 3 ,5
.5 3
4 ,5 + 0 ,2
.1 7
.1 8
4 ,2 + 0 ,1
6 ,5
.2 6
E00003-A-02
EP200 Master Instruction 9
4.2 Preparation of the actuator
The feedback shaft 9 of the EP200 has no mechanical This is achieved by placing an appropriate number of
stop, therefore may spin 360 degrees. The permissible washers 5 on the feedback shaft stub 9 before attaching
rotation angle range is between +50 and –50 degrees the coupling piece. Two washers should result in a
around the arrow at the housing concerning the flat area of clearance of 1 mm.
the feedback shaft (also see detail below). Now screw and tighten the threaded pin in the coupling
First turn the feedback shaft 9 with the flat area to the 50 % piece against the flat part of the feedback shaft (do not
position marked with the arrow 10. screw against thread!).
Finally turn the feedback shaft in such a way that the
• For attachment to a counter-clockwise or left turning ac-
arrow of the coupling piece points to the arrow of the EP200
tuator turn the feedback shaft 45° counter-clockwise to
housing.
the 0 % position. See Fig. L.
Beginning and end positions of the actuator drive shaft 1
• For attachment to a clockwise or right turning actuator
and feedback shaft 9 are marked in the illustrations below
turn the feedback shaft 45° clockwise to the 0 % position.
by arrows for the respective direction of rotation.
See Fig. R.
The feedback shaft is now in the normal position corres-
Now do not adjust the feedback shaft any longer! ponding to the failsafe position of the actuator.
Then screw the threaded pin 4 into a threaded hole of the
coupling piece 3, so that the threaded pin points to the flat 4.3 Mounting of positioner
area of the feedback shaft, while the catch of the coupling EP200 and actuator are in failsafe position.
piece is aligned with the groove in the drive shaft 1. Attach the EP200 on the console in such a way that the
Now place the prepared coupling piece with two washers catch of coupling piece 3 is guided into the groove of shaft
5 on the feedback shaft 9 of the positioner against the 1. Use threaded pin 2 to center and align the positioner to
stop. Note: the actuator. Be careful not to shift shafts 1 and 9 and that
When the product temperature rises, the drive shaft 1 be- both shafts are exactly flush.
comes longer. Therefore, the coupling piece must be Fasten the positioner to the bracket by means of 4 lock
mounted so that approx. 1 mm (0.04 in.) of clearance re- washers and 4 screws M6 x 12.
sults between the drive shaft and the coupling piece.
EP200 EP200
Direction
of rotation
0 → 100 %
of feedback
shaft 9
Direction
Rotary actuator of rotation Rotary actuator
0 → 100 %
Mounting if actuator of actuator Mounting if actuator
is left-rotating shaft 1 is right-rotating
E00003-A-02
10 EP200 Master Instruction
5 SYSTEM CONFIGURATION
The safety requirements must be observed!
E P 2 0 0
R
L
E00003-A-02
EP200 Master Instruction 11
6 ELECTRICAL CONNECTION
The safety requirements in chapter 10 must be observed! The screw terminals are suited for wire cross- sections of
up to 0.3–2.5 mm2 (22–14 AWG).
The cable is guided through gland 1. Do not insert cable
At the side of the screw terminals are integrated test sockets
from top; if necessary use opening relocated by 90°. The
Ø 2 mm (0.08 in).
gland is suitable for cable diameters of 6–12 mm
(0.24–0.47 in).
For enhancement of EMC-protection by connection to a
Tightly seal cable entry. Unused cable glands are to be
local ground the internal and external ground terminal 4
tightly sealed by means of filler plugs.
can be used.
The input line is connected to screw terminals 3 marked
11+ and 12–. Note: When connecting shielded cable connect the cable
shield only to the system! Do not connect the cable shield to
Terminal Signal the positioner!
11+ Input Setpoint value w (4...20 mA)
12– Input Setpoint value w (4...20 mA) There are no jumpers in the device.
1 4 3 1 2
1 3
1 1 1 2
+
1 4
3 1 3 2
+
+ +
4 1 4 2 5 1 5 2
1 5
4 0
E00003-A-02
12 EP200 Master Instruction
8 START-UP To view the menu or the device status is the full text LCD
display.
General
Before starting the positioner the EP200 has to be mounted The display on the LCD is in plain text:
to the actuator; power and air supply must be connected.
The supply air connection must have sufficient capacity and SRD Main Menu
pressure of 1.4 - 6 bar (20...90 psig) and should not exceed
1 Mounting
the maximum operating pressure of the actuator.
2 Autostart
3 Valve Action
Attention: Configuration may interfere with operation of
the actual process ! Note: If there is no response using the local key-pad
(message 1 appears) make sure that the Write Protection is
not set ! Remove the write protection using the special
The EP200 is generally set by the 3 local keys with housing
FDT/DTM configuration software.
cover open.
During configuration it is recommended that there is no flow
through the valve. Warning: When pressing the buttons during configuration,
For Initial Start-up it is to configure 'Actuator system, do not touch the rear part of the positioner at any time!
Mounting side' (see menu 1) , then a Autostart or a short Risk of injury !
Autostart (see menu 2 and 10).
After selection of the gear ratio, plug the Travel indicator 12
on the pointer shaft in the desired position.
When placing the housing cover, note that the vent opening
is directed downward. 8.2 Operation
After Power ON
INIT: After power on of the input signal, or after reset, the
8.1 Setting by means of local keys EP200 initializes, and the various components of the
The setting is made with the three buttons: electronics are checked and started. (The stored data of the
positioner not affected, and remains unchanged).
The current status is stated on the LCD in clear text.
Initialization after positioner start-up takes approx. 3 sec,
then the EP200 goes
• into operation (Autostart has already been done) or
• to configuration, selection of LCD text language
(default is Enlish language) ...
E00003-A-02
EP200 Master Instruction 13
8.3 Configuration
MENU: The various specifications for configuration are Manual Operation
arranged in menus: Through twice pressing of keys UP+DOWN (together), the
Menu Description EP200 goes into manual operation mode, where the valve
1 Actuator system, mounting side position can be set manually (see Menu 8). Exit of menu by
2 Autostart, Short Autostart pressing twice of key M.
3 Valve function
4 Characteristic of setpoint
5 Limits and Alarms Diagnostics during Operation
6 Parameter for position controller If the diagnostics determines an occurrence, this is indica-
ted in the bottom line:
7 Manual setting of pneumatic output
8 Manual setting of valve position
9 Calibration functions for workshop 87.5 %
Valve position
Ctrl diff error
In Operation MESSAGE: The EP200 recognizes an occurrence which
After accomplished autostart, the EP200 automatically goes the user must eliminate by taking suitable steps in order to
IN OPERATION. (Additional parameters can be configured continue with operation. This can be e.g. a wrong
through pressing of menu key M.) configuration or missing supply air.
On the LCD display the process variable is indicated.
ERROR: During self-testing the EP200 recognized an error
and is no longer operable.
87.5 %
Valve position
Other menu structure and representation
On the following pages, the further operation of the menu
and the presentation with the full-text LCD is treated in
Through pressing of keys UP or DOWN, additional infor-
detail.
mation can be retrieved from the EP200:
Valve position
Travel position
Input current
Digital setpoint
Stem setpoint
Input pressure
Output pressure1
Temperature
Travel sum
Valve cycles
Operation hours
TAG Number
TAG Name
Certain data and menus are available only with the
corresponding options.
E00003-A-02
14 EP200 Master Instruction
A u to s ta rt o r S h o rt A u to s ta rt
i.e .
IN S E R V IC E
s a v e a n d b a c k to m e n u
E n te r m e n u
M
M e n u P a ra m e te r
b a c k M 1 1
2
3 2
4 C h a r a c te r is tic c u r v e E n te r P a ra .*
5
6 D N U P 3
D N 7
U P
8 4 lin e a r D N
9 M e q u a l p e rc e n ta g e D N U P
1 0 in v e r s e e q u a l p e r c e n ta g e U P
C a n c e l S a v e *
c u s to m iz e d
w ith o u t s e le c tio n
s a v e 5
..
..
* L o c a l k e y s D O W N a n d U P s im u lta n e o u s ly
• Enter the Menu mode by pressing the M key, and Menu • Leave Menu mode by pressing M key again.
1 appears. If device remains in menu mode it still is OUT OF SER-
VICE and AUTOSTART has to be initiated.
• Select the desired Menu item by pressing the UP or If the instrument is IN OPERATION, the display with the
DOWN key, see table. Each press of the key moves valve position appears.
one menu item forward (or back). If a menu was selected and no further keys are pressed
thereafter, the EP200 switches automatically back to
operation after some minutes.
• Pressing the UP+DOWN (together) key confirms the se-
lected menu item and enters the Parameter change
mode for the selected menu item.
To set a parameter see table Parameter on next page.
E00003-A-02
EP200 Master Instruction 15
M e n u s tr u c tu r e fo r E P 2 0 0
M a in M e n u
M e n u / F a c to ry D e s c r ip t io n
D is p la y c o n f ig u r a t io n
1 M o u n t in g
1 .1 L in le f t L in e a r a c tu a to r , le f t-h a n d o r d ir e c t m o u n t in g
1 .2 L in r ig h t L in e a r a c tu a to r , r ig h t- h a n d m o u n t in g
1 .3 R o t c c lo c k w R o ta ry a c tu a to r, o p e n in g c o u n t e r - c lo c k w is e
1 .4 R o t c lo c k w R o ta ry a c tu a to r, o p e n in g c lo c k w is e
2 A u to sta rt
2 .1 E n d p o in t s A d a p t a t io n to th e m e c h a n ic a l s t o p s o n ly
2 .2 S t a n d a r d A u to sta rt re c o m m e n d e d fo r s t a n d a r d a p p lic a t io n
2 .3 E n h a n c e d O p t im iz e d c o n tro l b e h a v io u r c o m p a re d to S ta n d a rd A u to sta rt
2 .4 S m o o t h r e s p . E x te n d e d A u to sta rt, D a m p e n e d c o n t r o l b e h a v io u r f o r e .g . s m a lle r a c t u a t o r s
2 .5 F a s t r e s p . E x te n d e d A u to sta rt, U n d a m p e n e d c o n tro l b e h a v io u r f o r e .g . la r g e r a c t u a t o r s
3 V a lv e A c t io n
3 .1 P o s it io n e r A c t io n o f P o s it io n e r :
3 .1 .1 D ir e c t V a lv e o p e n s w it h in c re a s in g s e t p o in t v a lu e
3 .1 .2 R e v e r s e V a lv e c lo s e s w it h in c re a s in g s e t p o in t v a lu e
3 .2 F e e d b a c k A c t io n o f F e e d b a c k u n it :
3 .2 .1 D ir e c t In c r e a s in g c u rre n t w it h in c r e a s in g v a lv e p o s it io n
3 .2 .2 R e v e r s e D e c re a s in g c u rre n t w it h in c r e a s in g v a lv e p o s it io n
4 C h a ra c te r
4 .1 L in e a r L in e a r c h a ra c te r is t ic
4 .2 E q P e r c 1 :5 0 E q u a l p e rc e n ta g e c h a r a c t e r is t ic 1 :5 0
4 .3 Q u ic k o p e n In v e r s e e q u a l p e r c e n t a g e c h a r a c t e r is t ic 1 :5 0 ( q u ic k o p e n in g )
4 .4 C u sto m e r C u sto m c h a ra c t e r is t ic ( c o n f ig u r a t io n v ia D T M )
5 L im it s/ a la r m s
5 .1 L o w e r lim it 0 % C lo s in g lim it is s e t t o in p u t v a lu e
5 .2 C u t o f f lo w 1 % 0 % - t ig h t s e a lin g p o in t is s e t t o in p u t v a lu e
5 .3 C u t o f f h ig h 1 0 0 % 1 0 0 % - t ig h t s e a lin g p o in t is s e t t o in p u t v a lu e
5 .4 U p p e r lim it 1 0 0 % O p e n in g lim it is s e t t o in p u t v a lu e
5 .5 S p lit r 0 % 4 m A S p lit r a n g e 0 % : in p u t v a lu e c o r r e s p o n d s t o 0 %
5 .6 S p lit r 1 0 0 % 2 0 m A S p lit r a n g e 1 0 0 % : in p u t v a lu e c o r r e s p o n d s t o 1 0 0 %
5 .7 L o w e r A la r m 1 0 % L o w e r p o s it io n a la r m o n o u t p u t 1 is s e t t o in p u t v a lu e
5 .8 U p p e r A la r m 1 1 0 % U p p e r p o s it io n a la r m o n o u t p u t 2 is s e t t o in p u t v a lu e
5 .9 V a lv e 0 % 4 m A C o n f ig u r a t io n o f r a t e d - s t r o k e o f 0 % a t 4 m A
5 .1 0 V a lv e 1 0 0 % 2 0 m A C o n f ig u r a t io n o f r a t e d - s t r o k e o f 1 0 0 % a t 2 0 m A
5 .1 1 S tro k e R a n g e x ° / 2 0 m m C o n f ig u r a t io n o f n o m in a l t r a v e l
5 .1 2 T e m p u n it °C C o n f ig u r a t io n o f t h e t e m p e r a t u r e u n it ° C o r ° F
6 P a ra m e te rs
6 .1 G a in c lo s in g 1 5 P : P ro p o r t io n a l g a in f o r c lo s e v a lv e
6 .2 G a in o p e n in g 2 p : P ro p o r t io n a l g a in f o r o p e n v a lv e
6 .3 R e s t im e c l 7 .5 I: In te
g r a t io n t im e f o r c lo s e v a lv e
6 .4 R e s t im e o p 2 .4 I: In te
g r a t io n t im e f o r o p e n v a lv e
6 .5 R a te lim c l 0 .3 5 T 6 3 : S e t t in g t im e f o r c lo s e v a lv e
6 .6 R a te lim o p 0 .3 5 T 6 3 : S e t t in g t im e f o r o p e n v a lv e
6 .7 C o n tro l g a p 0 .1 P e r m it t e d n e u tra l z o n e fo r c o n t r o l d if f e r e n c e
7 O u tp u t M a n u a l s e t t in g o f IP - M o d u le f o r t e s t in g o f p n e u m a t ic o u t p u t
8 S e tp o in t M a n u a l s e t t in g o f v a lv e p o s it io n :
8 .1 1 2 .5 % S t e p s S e tp o in t c h a n g e s o f 1 2 .5 % ste p s b y u s in g p u s h b u t t o n s U p o r D o w n
8 .2 1 % S te p s S e tp o in t c h a n g e s o f 1 % ste p s b y u s in g p u s h b u t t o n s U p o r D o w n
8 .3 D o P S T S t a rts th e P a r t ia l S tro k e T e st, w it h t h e g iv e n p a r a m e t e r s b y D T M
9 W o rk b e n c h
9 .1 R e s e t C o n f ig R e s e t t in g o f c o n f ig u r a t io n t o s e t t in g s e x f a c t o r y
9 .2 C a lib . 4 m A C a lib r a t e in p u t c u r r e n t t o 4 m A
9 .3 C a lib . 2 0 m A C a lib r a t e in p u t c u r r e n t t o 2 0 m A
9 .4 C a lib . - 4 5 ° C a lib r a t e p o s it io n m e a s u r in g v a lu e t o 4 5 °
9 .5 C a lib . + 4 5 ° C a lib r a t e p o s it io n m e a s u r in g v a lu e t o + 4 5 °
9 .6 R e s e t a ll 1 R e s e t t in g o f c o n f ig u r a t io n a n d C a lib r a t io n ( !) t o e x f a c t o r y s e t t in g s f o r s in g le - a c t in g o u t p u t
9 .7 R e s e t a ll 2 R e s e t t in g o f c o n f ig u r a t io n a n d C a lib r a t io n ( !) t o e x f a c t o r y s e t t in g s f o r d o u b le - a c t in g o u t p u t
9 .8 G o o n lin e S e r v ic e f u n c t io n : S t a r t o f c o n t r o lle r w it h o u t A u t o s t a r t . N o t r e c o m m e n d e d f o r r e g u la r u s e
9 .9 M e n u L a n g L a n g u a g e o n L C D :
9 .9 .1 E n g lis h S t a n d a r d E n g lis h
9 .9 .2 D e u t s c h S ta n d a rd G e rm a n
9 .9 .3 F r a n ç a is P r e s e le c t e d / f r e e ly d e f in a b le t h ir d la n g u a g e
9 .1 0 L C D o r ie n t O r ie n t a t io n o f L C D :
9 .1 0 .1 N o r m a l N o r m a l o r ie n t a t io n o f w r it in g o n L C D
9 .1 0 .2 F lip p e d R e v e r s e o r ie n t a t io n o f w r it in g o n L C D
9 .1 1 C a l. F e e d b k C a lib r a t io n o f o u t p u t c u r r e n t o f p o s it io n t r a n s m it t e r :
9 .1 1 .1 C a l 4 m A C a lib r a t io n o f t h e 0 % a t 4 m A
9 .1 1 .2 C a l. 2 0 m A C a lib r a t io n o f t h e 1 0 0 % a t 2 0 m A
1 0 n o t u se d
E00003-A-02
16 EP200 Master Instruction
Additional Parameters
The following parameters are accessible via communication only:
Parameter ex factory
Control difference limit value 5%
Control difference response time 1 min
Sealing hysteresis 0.5 %
Failsafe-Aktion OFF
Power-up action IN SERVICE
Parameter write protection OFF
Alarm limit for total strokes 90 Mio.
Alarm limit for total cycles 90 Mio.
Dead band for valve cycles 1%
Set value source: Model Code xFxx digital
Set value source: all others analog
Upper pre-alarm 100 %
Lower pre-alarm 0%
Hysteresis for position alarms 0.5 %
Complete parameter list see FDT/DTM Software.
E00003-A-02
EP200 Master Instruction 17
Configuration requested
Configuration of 0 and 100 %
Rotary actuators MENU 1: MENU 3:
"Mounting" "Valve Action"
Valid for single and double acting 1.1 1.2 1.3 1.4 3.1 3.2
ü ü
4 mA = 0%
S R D
20 mA = 100%
0 % 1 0 0 %
ü ü
4 mA = 100%
20 mA = 0%
ü ü
4 mA = 0%
S R D
20 mA = 100%
1 0 0 % 0 %
ü ü
4 mA = 100%
20 mA = 0%
ü ü
4 mA = 0%
S R D
20 mA = 100%
1 0 0 % 0 %
ü ü
4 mA = 100%
20 mA = 0%
ü ü
4 mA = 0%
S R D
20 mA = 100%
0 % 1 0 0 %
ü ü
4 mA = 100%
20 mA = 0%
E00003-A-02
18 EP200 Master Instruction
1 Mounting
1.1 Lin left For rotary actuators opening the valve during counter clockwise (left) rotation.
1.2 Lin right
1.3 Rot cclockw
1 Mounting
1.2 Lin right For rotary actuators opening the valve during clockwise (right) rotation.
1.3 Rot cclockw
1.4 Rot clockw
E00003-A-02
EP200 Master Instruction 19
Menu 2: Autostart Selection between different Autostart modes
(change with key UP or DOWN):
After selection and start (by pressing the UP+DOWN keys) the function
can be followed at LCD.
Duration on a valve position can take some time depending on actuator
volume, air supply, pressure, etc.
2 Autostart Moving direction, mechanical starting and ending positions are determined
SRD991 Vers.xx by one or several passages of valve position range.
Get end points
Ramps are entered and control system parameter is determined (ratio
position / valve size).
2 Autostart Jumps are entered for determination of control parameters.
SRD991 Vers.xx
Get motor gain Determination of positioning speeds.
2 Autostart
SRD991 Vers.xx
Get valve speed
E00003-A-02
20 EP200 Master Instruction
Menu 4: Characteristic of setpoint A relationship between the input signal and valve position is set.
2 0
0 % 2 0 4 0 6 0 8 0 w 1 0 0
4 0
2 0
0 % 2 0 4 0 6 0 8 0 w 1 0 0
4 0
2 0
0 % 2 0 4 0 6 0 8 0 w 1 0 0
E00003-A-02
EP200 Master Instruction 21
4 Valve Char. - - - - 1 LED 4 lights up
4.2 Eq Perc 1:50 “User defined characteristic”:
4.3 Quick open A characteristic line entered via
1 0 0
4 0
2 0
0 % 2 0 4 0 6 0 8 0 w 1 0 0
x x
0 .5 %
0 .5 %
0 % w 0 % w
Sealing tightly, linear charcteristic line Sealing tightly, inversely equal percentage
1 0 0 1 0 0
x x
x a 8 0 x a 8 0
6 0 6 0
4 0 4 0
2 0 2 0
x z x z
0 % 2 0 4 0 6 0 8 0 w 1 0 0 0 % 2 0 4 0 6 0 8 0 w 1 0 0
Opening limit xa, Closing limit xz, linear characteristic Opening limit xa, Closing limit xz,
inversely equal percentage characteristic
E00003-A-02
22 EP200 Master Instruction
Definitions
Stroke, stroke range of the membrane actuator is defined for rotary actuator as angle, angle range.
0 % position is the mechanical impact at actually closed valve (caution if using handwheel and mechanically adjust-
able stroke limitation!)
100 % position is the mechanical impact at actually open valve.
Closing limit is a lower limit set via software. In normal operation the valve will not close more than set here.
Attention: In the event of failure of the auxiliary energy no controlling is possible, therefore the springs in
the actuator will move the valve into safety position (for single-acting actuator).
Opening limit is a upper limit set via software. In normal operation the valve will not close more than set here.
Attention: In the event of failure of the auxiliary energy no controlling is possible, therefore the springs in
the actuator will move the valve into safety position (for single-acting actuator).
Normal operation (= IN SERVICE) means that the position is controlled to the 4–20 mA input signal.
E00003-A-02
EP200 Master Instruction 23
Split Range
Example: At low current, only the smaller valve positions; from approx. 40
% the large valve is added
5.6 Splitr 100 % Example: An input current of 10.4 mA has to correspond to a valve position
10.4 mA of 100 %.
E00003-A-02
24 EP200 Master Instruction
5.10 Valve 100 % By pressing of keys UP or DOWN, the value is adjusted and with keys UP+DOWN confirmed.
The keys have Autorepeat: By pressing and holding of a keyUP or DOWN, the value is counted
98.4 % upward, after some time in larger steps.
Confirm Example: The actual valve position 98.4 % is to be counted as 100 %.
E00003-A-02
EP200 Master Instruction 25
Menu 6: Parameter for Position controller
Along with the determination of the actuator geometry and control
parameters the suitable setting parameters for the position controller are
determined via function AUTO- START in Menu 2. Assessment of a
control behavior generally is very subjective. Partially a quick response is
requested without consideration of the overshoot width, partially a very
smooth swinging is requested with minor overshoot.
We basically recommend to first perform the execution of the automatic
setting via AUTOSTART in Menu 2 in order to achieve a stable control
behavior. Corrections may then be made from the determined values.
In rare cases AUTOSTART cannot find the optimal setting for the
respective application. See “Remarks for controller optimization” following
table 4.
A further optimization may follow by repeating AUTOSTART.
Integration time
constant
Tn Tn¯ sec
The dead band prevents (at the expense of accuracy) that the valve in the
controlled condition constantly moves around the setpoint. This reduces
harm to the mechanical parts of the actuator and, in particular, the valve
packing.
Selection of sub-menus:
6 Parameters Following selection of the sub-menu the codes for the parameter values
6.1 Gain closing (table 4) can be selected by pressing UP+DOWN:
6.2 Gain opening
6.3 Res time cl
etc.
6 Parameters
6.4 Res time op
6.5 Rate lim cl
6.6 Rate lim op
6 Parameters
6.5 Rate lim cl
6.6 Rate lim op
6.7 Control gap
E00003-A-02
26 EP200 Master Instruction
For the assessment of the control 12.5 % jumps in both directions may be
performed in Menu 8. The valve dynamics may be observed at LCD or the
mechanical indicator.
Prior to changing parameters for valve dynamics a number of items are to
be checked, see below. The pneumatic output can be operated directly
without controller via Menu 7 and the valve movement may be assessed.
E00003-A-02
EP200 Master Instruction 27
4. Was AUTOSTART performed in Menu 2 and did mes- When deciding a), “Tn” should become ineffective, table
sages 8 resp. 9 occur (messages, see table page 35)? value (15). Compensating “P(kp)” should be increased until
Remedy: “AUTOSTART” in Menu 2 resp. observe in- the setpoint jumps reach the setpoint within a short period
formation in table, page 35. of time and without significant over-response (adapt to both
5. Has the parameter for the positioning time been set at a movement directions).
value too high?
Remedy: decrease both parameters “T63" in Menu 6.5 When deciding b) start as in a) above. Thereafter “Tn” is
or 6.6 . reswitched and decreased until the setpoint deviation has
6. Is valve packing too tight resulting in a very high been re-controlled within a short period of time and without
friction? long after-response (adapt in both movement directions).
7. Is the supply air filter blocked? It is recommended to maintain the Tn’s for both directions
Remedy: Clean filter or exchange. about the same.
8. Has the supply air been contaminated by small oil If a post oscillation occurs after a setpoint jump, “Tn” is se-
drops, particulate or are pneumatic parts possibly lected too small, possibly “P(kp)“ was selected too large.
blocked?
Remedy: exchange pneumatic parts; possibly use a The positioning time “T63", also called valve damping, does
suitable air supply station. not have an effect during AUTOSTART in Menu 2, however,
setpoint jumps in Menu 8 reach the position controller in a
Behaviors B) and C) check: damped condition which then is not easily stimulated to
1. Is the air capacity possibly too high, e.g. through spool oscillation. This behavior is also true for the setpoint input.
valve or booster? This enables setting the controller to higher “P(kp)“ values
Remedy: Work, if necessary, without booster or without producing oscillations in the process. On one side
use version without spool valve. this helps the position control to level disturbances due to
2. Has the air supply pressure been set too high? friction, changes in load or air supply pressure changes
Remedy: reduce pressure install pressure reducer. faster. On the other hand it helps the superimposed valve
control circuit that neutral times in the valve control route do
Changing valve dynamics during behavior A): no have such a big effect (stability in valve control circuit).
If valve has a high friction (for example, often the case in
small rotary actuators due to low air supply pressure or due Changing valve dynamics during behavior B):
to a valve seat packing which is too tight) then the valve po- Increase “Tn” for both movement directions, possibly turn-
sition gets stuck after a setpoint jump and possibly is recon- off and proceed as described in behavior A) alternative b).
trolled via the resetting time Tn, possibly after quite some
time has elapsed.
Basically, the following is possible:
a) to accept a remaining deviation
b) to accept some response procedures (such as remain-
ing in over-response for a short time, and remaining
below setpoint and trailing).
E00003-A-02
28 EP200 Master Instruction
8.3 Do PST
8 Setpoint With this function, the Partial Stroke Test is started, with the given para-
8.3 Do PST meters by DTM. If the test is passed back to the menu.
8.1 12.5% Steps If the PST is not passed, the error message "PST error" appears on LCD.
8.2 1% Steps
E00003-A-02
EP200 Master Instruction 29
Menu 9: Calibration functions (for workshop)
Factory calibrations are carried out with sufficient accuracy and remain un-
SRD Main Menu changed during life time. However, an alignment may become necessary
7 Output in some cases after servicing hardware components.
8 Setpoint
9 Workbench
The following calibration functions The calibration of the input current or position sensor makes sense, if after
must only be performed by trained exchange of the electronics, the valve position is inaccurately displayed.
personnel.
Calibration of input current
Serves to equalize possible inaccuracies in the complete current loop.
E00003-A-02
30 EP200 Master Instruction
E00003-A-02
EP200 Master Instruction 31
8.5 Setting of the travel indicator 9 DECOMMISSIONING
The mechanical travel indicator is coupled to the feedback Before decommissioning the unit, disconnect the supply air
shaft of the positioner by a gear. The gear has two select- and the electrical input signal.
able ratios1) 1 : 2 and 1 : 6.
After disconnecting the electrical input signal the last con-
firmed configuration of the positioner is preserved in the
Selecting gear ratio:
memory.
For rotation angles of the feedback shaft less than 30° se-
lect a ratio 1 : 6. This gear selection amplifies the feedback
Exchange of device
shaft rotation angle six times and for example, a 20° angle
If a temporary decommissioning of the EP200 and a later
is shown as 120°.
mounting to another actuator has to be carried out, before
For rotation angles greater than 30 ° select a ratio of 1 : 2. disconnecting, we recommend to Reset Configuration in
This gear selection amplifies the shaft rotation angle by a Menu 9.1. So the default settings ”Ex-Factory” are re-
factor of two and for example, a 45° angle is shown as 90°. activated. This facilitates a later recommissioning.
For rotary actuators the rotation angle is equal to the ro-
tation angle of the actuator. Consequently, a 90° rotation
angle will result in a 180° display angle for the 1 : 2 gear
ratio.
>
1 : 2 1 : 6
Turn the travel indicator 12 to the desired position, put it on
the gear shaft against the stop and pinch the wire ring for
secure coupling.
E00003-A-02
32 EP200 Master Instruction
E00003-A-02
EP200 Master Instruction 33
11 TROUBLE-SHOOTING GUIDE
The components of the positioner are under constant sur-
veillance by the installed micro controller. Detected errors
are displayed in LCD.
Certain conditions (such as “Stroke limitation active”) are
displayed in LCD as message.
E00003-A-02
34 EP200 Master Instruction
11.3 Messages
Description of message / LCD text Remedy
Write protected
Message 1: Parameter and functions are write-protected Can be changed via Configurator, FDT/DTM Soft-
write protection ware
Calib invalid
Message 3: Incomplete calibration or entering value resp. Repeat calibrations in Menus 9.2 ... 9.5
Calibration calibration value outside of permissible tolerance
range
Pot problem
Message 5: Position sensor input recognizes error check 3-pole plug at electronic board
Position sensor check cable to sensor
check sensor (Potentiometer: 5k +20% –0%)
Positioner already ca- Position not within permissible rotation angle range. Check feedback lever mounting (flat area points to
librated, dismonted Lower deviation of the original 0% and exceeding arrow on housing)
and supply. If you of the original 100%, which have been determined
supply (4-20 mA or by Autostart.
with a fieldbus) a po-
During Autostart a change of the direction of mo- Acknowledge with UP+DOWN keys, then o.k.
sitioner not mounted
vement was found
and bring the poten-
tiometer out of range, Check further possible reasons:
the message will ape- valve seat worn-out; spindle lock out-of-line; carrier
ar and remain till the unit on spindle lock is damaged (for determination of
potentiometer goes valve position).
again in range and
the error is validate
with push button.
IP motor problem
Message 6: Connection I/P converter to electronic board faulty check 2-pole plug at electronic board
I/P-converter output check cable to the I/P converter
check I/P converter to detect short circuit or inter-
ruption
No supply press
Message 7: Detection: check air supply pressure
Air supply / spring closes: w > 2 %, but position < 1 % lead cable separated
pneumatic error spring opens: w < 98 %, but position > 99 % possibly poor control parameters are set
without spring: pneumatic parts blocked
no actuator change in direction of position signal
E00003-A-02
EP200 Master Instruction 35
Description of message / LCD text Remedy
Autostart err 1
Message 8: Air supply too low Check air supply
AUTOSTART Feedback lever (linear actuator) or Coupling (rotary Check mounting.
defective actuator) incorrectly linked. Potentiometer moves out Flat area points to arrow on housing
of operating range of ± 47 % of 0° position
Coupling (rotary actuator) incorrectly linked Check mounting
(R and L interchanged)
Pneumatic output to actuator closed or untight/ Check pneumatic connections
When direct mounting onto FlowTop or FlowPak,
the screw plug y1-d is not removed.
Mechanical stops not determinable Check spring movement of actuator /
check air supply / Check mounting
When using a booster or spool valve, no control Device version is not suitable for this actuator; se-
parameters can be determined, since air capacity lect version with smaller air capacity or remove
is too high. booster.
Control parameter too high since air capacity is too Use a booster or the version with spool valve. Re-
high (in general, oscillation in valve movement) duce control parameter prop.-gain (Menu 6.1 and
6.2) to Code 10 = value 26.6.
Possibly incomprehensible configuration data Reset configuration, see Menu 9.1
Autostart err 2
Message 9: Configuration to single-acting instead of Initialize factory calibration for double-acting in
AUTOSTART double-acting actuator Menu 9.7
defective
Optionboard err
Message 10: Configured status of the EP200 deviates from Check if correct option board has been connected
Disturbances at existing version (e.g. Option board has been Confirm message and thereby new instrument
Option board inserted subsequently. version.
Bad contact Connections to terminals interchanged
Check connections
Tighten electronics
Defective Exchange option board
E00003-A-02
36 EP200 Master Instruction
Maintainance
Message 14: Operating point of controller is outside of Pneumatic components have to be checked and if
Maintenance permissible tolerance necessary readjusted. Filters are possibly blocked
required and have to be replaced
Unforeseen
Message 15: Not defined
P o w e r-U p
IN IT
K e y m e n u
" R e s e t to fa c to r y s e ttin g "
O U T O F
F A IL IN S E R V IC E 2 )
1 ) K e y m e n u
S E R V IC E
" M a n u a l e n tr y o f v a lv e p o s itio n "
c o n c lu d e d
A u to s ta rt
D e v ic e c o n c lu d e d r e s p .
e rro r a b o rte d
K e y m e n u K e y m e n u
"A u to s ta rt" o r "A u to s ta rt" o r
"S h o rt A u to s ta rt" "S h o rt A u to s ta rt"
C A L IB R A T E
(A u to s ta rt)
1) Menu indication may be turned on resp. off. The respective oval shape indicates op-mode.
Messages can be constantly shown. Mode of operation changes in direction of arrow if described
2) Menu indication or message are constantly on conditions are met.
Key / menu “xxx” : Operation via local keys
Power-Up: Return of the supply voltage or RESET
E00003-A-02
EP200 Master Instruction 37
11.4 Diagnosis without LED or LCD inform
Fault Possible cause Solution
Positioner not operational using No input signal at 11, 12 Connect input signal
key pads Local operation blocked (write protection) Remove blockage via communication
No automatic power up (Reset) Reset device with keys
A key got jammed Release cover screws, check menu
functions, retighten cover
Failure in the positioner send device to manufacturer
Autostart not completed Actuator volume too large stop Autostart and carry out extended
(> 45 min) Autostart, see chapter 8.4, Menü 2
or apply booster
Failure in the positioner, otherwise carry out Autostart again, see chapter.
Message 8, 9 8.1 and 8.4, Menu 2
carry out Reset configuration
send device to manufacturer
Autostart remains stagnant for a longer Feedback lever (at stroke actuator)
time (>10 min) in step 1 or 2 (LED 1 or 2 incorrectly mounted. Verify installation
lights up), otherwise message 8 of feedback lever, see chapt. 4; flat part
points to arrow on housing
Coupling piece (at rotary actuator)
incorrectly turned (R and L mixed up):
Verify direction of rotation, see chapt. 4;
flat part points to arrow on housing
Autostart remains stagnant for a longer At large volume actuators the Autostart
time (>10 min) in step 3 can possibly remain stagnant for a
(LCD: shows”Control params“) longer time (>10 min) in step 3, prior to
continuing in step 4
Actuator does not react to a change in No Autostart performed. Perform Autostart
the input signal Positioner is not IN OPERATION Switch positioner IN OPERATION, see chap.
8.2 resp. Autostart or via Configurator
Setpoint source is configured wrong Correct configuration via configurator
Actuator does not attain the closed Autostart not carried out carry out Autostart
or opened position Supply pressure too low check supply air pressure
Travel limit is set check settings,
Message 12, 13 see chapter 8.4, Menu 5
Angle position linearization, positioner action check settings,
or characteristic curve is set incorrectly (e.g. see chapter 8.4,
‘Custom’, but values are missing) Menus 1, 3, 4
Unstable behavior, Autostart incomplete, therefore, control carry out complete Autostart,
position control circuit oscillates parameters not suitable see chapter 8.4, Menu 2
Small actuator volume but high air see chapter 8.4, Menu 6, reduce gain
capacity (P parameters)
Friction on valve packing too great loosen packing gland slightly or replace
IP module or Pneumatic amplifier defective change module, pneumatic amp
Actuator reacts too sluggishly air capacity insufficient attach booster
gain set too low see chapter 8.4, Menu 6
positioning time T63 set too high reduce positioning time, see chapter
8.4 Menu 6
No communication possible Input voltage too low Eliminate voltage drop
Faulty protocol, communicator and Check configuration of devices
device type do not match
Wrong electronics unit change device
E00003-A-02
38 EP200 Master Instruction
12 MAINTENANCE
12.1 General
The EP200 requires no periodical maintenance. Connect the plugs 41 and 42 to the new electronics unit 40
When replacing components during repair work, the safety and attach the new unit by using the 7 screws on the front
requirements must be observed! (attention with the cables).
E00003-A-02
EP200 Master Instruction 39
13 OPTIONS
Switch functions x = 1 0 0 %
Feedback lever, feedback shaft and the control vanes are x 0 % 1 0 0 %
1
By adjusting the screws, the control vanes can be adjusted
relatively to the angle rate, so that e.g. one vane dives into x = 0 %
and another dives out of the sensor (see illustration).
5 ,
*
Setting limit switch trigger points
First loosen screw S until disc D is no longer blocked by
bolt B . Then turn disc by 90°, until set screws 1 and 2 are
accessible.
Set trigger point switch GW1:
Turn screw 1 at mark (•), until desired switch behavior
is reached.
Set trigger point switch GW2:
Turn screw 2 at mark (• •), until desired switch behavior
is reached.
To fix switch points turn disc again by 90°, until the bolt
catches, then fasten tight the center screw S .
E00003-A-02
40 EP200 Master Instruction
E00003-A-02
EP200 Master Instruction 41
14 DIMENSIONS
M 8 x 1 0 tie f
2 x
M 8 x .3 9 d e e p
1 .1 8
3 0
1 .1 8
3 0
.5 9
1 5
1 .1 8
3 0
.3 9
1 0
.5 9
1 5
3 0 ,6
1 .2
4 .3 3
1 1 0
m m 1 7 6
in 6 .9 4
1 1 7
4 .6 1
M 6 x 1 0 tie f
4 x
M 6 x .3 9 d e e p
1 .9 7
5 0
.5 1
1 3
5 ,3 9
1 3 9
2 .8 7
7 3
.3 1
8
8 ,4 1 4
2 x
.3 3 .5 5
1 9 6 2
.7 5 2 .4 4
E00003-A-02
42 EP200 Master Instruction
ORDER CODES
Digital Positioner EP200-
Version
Single Acting E
Double Acting D
Analog Position Feedback
without 0
Signal Output 4…20 mA F
Built-In Limit Switch
without S-
Inductive Limit Switch - Intrinsic Safe (Standard Version) T-
Inductive Limit Switch - Intrinsic Safe (Security Version) U-
Inductive Limit Switch - Three Wire Version R-
Electrical Classification
without ZZZ
Subject to alterations - reprinting, copying and translation prohibited. Products and publications are normally quoted
here without reference to existing patents, registered utility models or trademarks. The lack of any such reference
does not justify the assumption that a product or symbol is free.
Version 10.2012
E00003-A-02