Electropneumatic Converters
for Direct Current Signals
i/p Converter Type 6127
Mounting and
Operating Instructions
EB 6127 EN
Edition September 2006
Contents
Contents Page
1 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Pneumatic connection . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1 Checking zero and span . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2 Adjusting the air output capacity . . . . . . . . . . . . . . . . . . . . 8
4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Dimensions in mm . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 EB 6127 EN
Description
Article code
Type 6127- x x x x x x x x x x
Explosion protection Without 0
Rack-mounting Single (Type 6109) 1
unit Double (Type 6109) 2
Single (Type 6112) 3
Double (Type 6112) 4
i/p module Type 6109 1
Type 6112 2
Input 4 to 20 mA 1
Output 0.2 to 1.0 bar 1
3 to 15 psi 2
Operating direction Increasing/increasing 1
Increasing/decreasing 0
Temperature range Tmin ≥ –10 °C 0
Special version Without 0 0 0
1 Description
1.1 Application 1.2 Versions
The devices are used to convert a direct cur-
Type 6127- 0 x
rent input signal into a pneumatic signal for
measuring and control. They are especially Rack-mounting unit with:
suitable as intermediate elements between one i/p converter 6109 1
electrical measuring devices and pneumatic two i/p converters 6109 2
controllers or between electrical control de- one i/p converter 6112 3
vices and pneumatic control valves. two i/p converters 6112 4
The input is a load-dependent direct current
from 4 to 20 mA. The output is a pneumatic
signal from 0.2 to 1 bar (3 to 15 psi).
EB 6127 EN 3
Description
1)
Measured with 2 m hose 4 x 1
2)
According to IEC 770
4 EB 6127 EN
Description
EB 6127 EN 5
Installation
6 EB 6127 EN
Operation
Span
4. Set the input signal to the lower range
value (e.g. to 4 mA for a range from 4
to 20 mA = 0.2 to 1 bar) using a suit-
able current source.
The output signal at the test pressure
gauge should indicate a lower range
value of 0.2 bar.
Should another value be indicated, read-
just the zero point accordingly with the
ZERO potentiometer.
EB 6127 EN 7
Maintenance
8 EB 6127 EN
Dimensions in mm
5 Dimensions in mm
2.5
162.5
pA1
128.5
100
pA2
EB 6127 EN 9
SAMSON AG · MESS- UND REGELTECHNIK
2006-09