Professional Documents
Culture Documents
https://doi.org/10.1007/s42835-020-00447-0
ORIGINAL ARTICLE
Abstract
Protective relays have been designed with different technologies resulting in electromechanical, solid-state, and numerical
devices. Speed and reliability are the two most important characteristics of a protective relay. Other capabilities such as
monitoring and recording are supposed to be of secondary priority. The new technology using combination of field-program-
mable analog arrays (FPAAs) and digital technologies seems to be a breakthrough and has the potential to provide better
performance than the present-day numerical relays. The use of FPAAs for designing and implementing overcurrent relay is
investigated. The modeling and simulation of a protected system using Matlab are described. Hardware implementation using
FPAAs is described. The practical test for different types of fault conditions is presented. The practical results show the ability
of the new protection to response to the steady-state fault condition fastly and also can obtain different types of Time–Cur-
rent characteristics with high accuracy. Also two types of characteristics Inverse Definite Minimum Time type IDMT type
and very-inverse type are implemented, the protection system is tested in a fault of line-to-line type and the results show the
ability to discriminate the fault condition and isolate the faulted section only, the remaining network can operate normally.
Keywords Overcurrent relay · IDMT · TMS · TC · Peak value detector · Pickup current · Input/output port · FPAA
13
Vol.:(0123456789)
Journal of Electrical Engineering & Technology
2 Peak Detector For the system in which the fault is specified practically
by the fault position, that being substantially not affected
To detect the fault current, the maximum value of the sinu- by the changes in the impedance of power source, in this
soidal waveform current should be measured, which taken case, the favorite is to use Inverse Definite Minimum Time
from current transformers the derivation in Appendix A [8]. type (IDMT) [11]. Where gives fast tripping, even the fault
The instantaneous equation of the sinusoidal waveform cur- close to the source, that severe faults generality can happen
rent is [9]: [12]. When the impedance between protection relay and the
source (ZS) is small value when compared with the imped-
i(t) = Im sin(𝜔t) (1) ance of protected zone (ZL), there is a significant difference
between the current magnitude for a fault at the near end of
the zone ( VS/ZS, VS: source voltage) and the current mag-
where Im is the maximum value. The conventional methods
nitude for a fault at the far end ( VS/ (ZS + ZL)) [13]. The
for measuring the peak value needs more than one cycle
operating time of relay is proportional inversely with the
(20 ms) [10]. In this paper for fast measure the maximum
line current so that the overcurrent operates for a fault at the
value the instantaneous power theory or p-q theory was
end of the zone faster than the nearer to the source, and the
used. In this theory the αβ0 transformation or the Clarke
ratio of operating time for a fault current is ( ZS/ (ZS + ZL))
transformation transforms the three-phase instantaneous cur-
[14]. Figure 2 shows the characteristics of the time-distance
rent from the abc phases, ia(t), ib(t) and ic(t) to the αβ0-axes
resultant for radial transmission with individual sections
which are denoted as i α, iβ and i 0. The Clarke transformation
[15–17]. By using a selective Time Coordination margin
of the three phase currents can be given:
(TC) which is the sum of the breaker, over-travel, and factor-
of-safety times, the relay operating time can be controlled
� � � ⎡ 1 −1 −1 ⎤⎡ i ⎤
i𝛼 2⎢ 2 2 ⎥⎢ a ⎥ (increase or decrease) by using very inverse characteristic
(2)
3 ⎢⎢ √3 √3 ⎥⎢ ib ⎥ [16, 18].
=
i𝛽 ⎥⎣ ic ⎦
⎣0 2 − 2 ⎦ To calculate the operating time of overcurrent relay [19]:
13
Journal of Electrical Engineering & Technology
NB 1 NB NB NB NS Z
NS − 1/2 NB NS NS Z PS
Z 0 NB NS Z PS PB
PS 1/2 NS Z PS PS PB
PB 1 PB PS PB PB PB
13
Journal of Electrical Engineering & Technology
15
10
Line current in PU
5
-5
-10
-15
-20
Fig. 5 FLC validation test 0.26 0.28 0.3 0.32 0.34 0.36 0.38 0.4 0.42
Time in seconds
10
8
6
Currents in PU
4
2
0
-2
-4
-6
-8
Fig. 6 FLC validation surface -10
0.2 0.22 0.24 0.26 0.28 0.3 0.32 0.34 0.36 0.38 0.4
Time in seconds
structure type with 50% overlapping. Fig. 4 shows the FLC
structure. From Fig. 5 the error between training and testing Fig. 9 Iα and Iβ and peak amplitude at single phase fault
stage is very small and all the values are reached the target
the error was (2.1 × 1 0−6). Figure 6 shows the validation 6 Simulation and Results
surface, from the figure it’s clear that the change in the con-
troller in both directions (positive to negative) was smooth. To check the protective system design first simulated by
using Matlab/Simulink, the model shown in Fig. 7. Three
types of faults conditions tested the designed protective
system: the single-phase, two-phase and three-phase to a
ground fault. The simulation test done by applying the faults
13
Journal of Electrical Engineering & Technology
25
1
0.8 20
0.6
Line current in PU
15
Line voltages in PU
0.4
10
0.2
0 5
-0.2 0
-0.4
-5
-0.6
-0.8 -10
-1 -15
0.26 0.28 0.3 0.32 0.34 0.36 0.38 0.4 0.42 -20
0.2 0.25 0.3 0.35 0.4 0.45
Time in seconds
Time in seconds
15
10 20 Ia
Ib
Peak Detector
15
Line current PU
Line current in PU
10
0 5
0
-5
-5
-10 -10
-15
-15
0.2 0.25 0.3 0.35 0.4 -20
0.2 0.25 0.3 0.35 0.4 0.45
Time in seconds
Time in seconds
15
Ia suddenly after normal operation and record the protection
Ib
10
Peak Detector
response to fault conditions. Figure 8 shows a single line to
a ground fault where the fault happens at t = 0.33 s the relay
5
action was at t = 0.37 s.
0 The time taken from detection to tripping was about
-5 (40 ms) this time included the detection and the delay time
depending on the multiple of pickup current. Figure 9 shows
-10
the quadrature components Iα and Iβ and the peak value eval-
-15
0.2 0.25 0.3 0.35 0.4 0.45
uated using Eq. 2. It can be noticed that fast measuring the
Time in seconds peak value of the current with good precision. Figure 10
shows the line voltage before and after the fault occurs. Fig-
Fig. 12 Iα and Iβ and peak amplitude at two phase fault ures: 11, 12, and 13 show the second type of fault test the
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
-1
Time in Seconds
13
Journal of Electrical Engineering & Technology
PI
1 FLC
0.8 1.35
Line voltage in PU
0.6
Fig. 16 The line voltage at three phase fault Fig. 20 The Step change in line current
25
two phase fault condition. Figures: 14, 15, and 16 show
Trip signal and measuring signal
Ia
Ib
20 Measuring signal
Trip signal the third type of fault test the three phase fault condition.
15
Figure 17 shows the quadrature components with peak value
10
and trip signal. Figure 18 shows the trip signal with delay
5
time depending on the value of fault current (multiple of
0
pickup current) as in Eq. 5. Figure 19 shows time current
-5
characteristic for two TMS. To validate the FLC Figure 20
-10
shows the results of the control system response to step
-15
0.26 0.28 0.3 0.32 0.34 0.36 0.38 0.4 0.42 0.44 change in the active power. From the results, it is clear that
Time in seconds the Fuzzy controller has a smoother in response and reaches
the steady state faster than the conventional PI controller.
Fig. 17 Iα and Iβ, peak value and trip signal
7 Practical System
Trip signal verses Detecting signal
2
To validate, the protection designs a Field Programmable
Ia
Ib
1.5 Ic
1
10
ates several source files that can be used in an application
managing the FPAA. It can also download the configuration
10
0
directly to the FPAA. The configuration data are stored in an
internal SRAM memory, that is divided into two areas: the
configuration memory (CM) and the shadow configuration
10-1
0 5 10 15 memory (SM) [23]. FPAA Implementation of overcurrent
Multiple of Pickup current
protection circuit is shown in Fig. 21, the three input cur-
rents are filtered and then the peak value is calculated by
Fig. 19 Time–Current characteristic
13
Journal of Electrical Engineering & Technology
13
Journal of Electrical Engineering & Technology
Time in Seconds
0
10
-1
10
2 4 6 8 10 12 14 16
8 Discussion of The Results Multiple of Pickup current
To validate the instantaneous power theory to measure the Fig. 26 Time current characteristic for normal inverse
peak amplitude Figs. 24 and 25 show the peak level and the
quadrature components calculated using FPAA. The param-
eters of the overcurrent relay shown in Table 2. The experi-
mental results for the overcurrent relay consist of two types 10
1
TMS=1
Multiple of Pickup current
0
10
-1
10
2 4 6 8 10 12 14 16 18 20
Time in seconds
13
Journal of Electrical Engineering & Technology
Appendix A
Where:
R: resistance.
one cycle and also more accurate and less peripheral design
needs.
9 Conclusion
Appendix B
In this paper the technique of overcurrent protection relay
based on FPAA was presented, the use of FPAA shows the The rules of Fuzzy logic control system like a PI controller
simple design with high efficiency and fast process com- shown below. The controller inputs were split into 5 trian-
pared with the previous works in [4–7]. The peak amplitude gular membership functions MFs (− 1, − 0.5, 0, 0.5, 1) with
detector of phase current using instantaneous power theory 50% overlapping, as shown below:
gives fast-tracking response to any change in the current
amplitude where the measuring time less than one cycle with
high accuracy of error less than 2%, the use of Fuzzy logic
control gives more smooth in response also different type of
characteristics were obtained practically only by changing
the constants of Eq. 5 in the algorithm program with wide
range of TMS, compared with the traditional protection in
reference [1], also the protection design has a response time
of less than one cycle after the fault occurs to isolate the
faulted area.
The rules were 25-control rules as shown:
13
Journal of Electrical Engineering & Technology
13
Journal of Electrical Engineering & Technology
22. Gyorok G (2009)The FPAA realization of analog robust electronic Northern Technical University. currently, he is head of Technical power
circuit. ICCC2009, IEEE 7th Inter. Conf. on Comp. Cybernetics, engg. dept. His research interests include protection, power electronics,
Spain pp.179–183 FACTS, Renewable energy.
23. Koziol S et al (2010) Hardware and software infrastructure for a
family of floating- gate based FPAA. Proceedings of 2010 IEEE Mohammed Ghazal obtained his M.Sc. degree from Computer Engi-
international symposium on circuits and systems, France. pp. neering Technology, Northern Technical University, Mosul, Iraq in
2794–2797 2016. His M.Sc. thesis entitled: “Wheelchair Robot Control Using
EOG signals” and his current research focuses on the development of
Publisher’s Note Springer Nature remains neutral with regard to face recognition algorithm.
jurisdictional claims in published maps and institutional affiliations.
13