65 Figure 4-7. Cooling tower. TR is tower range (95°F - 85°F), CR is condenser rise (85°F to 95°F). 66 HVAC Fundamentals
Figure 4-8. Forced Air Cooling Tower
Metering Devices (flow control)
Thermal Expansion Valve (TXV) (TEV) Automatic Expansion Valve (AXV) (AEV) Float Valve (High Side or Low Side, Flooded Systems) Capillary Tube Hand Valve
EVAPORATORS
HVAC evaporator temperatures are usually between 34 and
45 degrees Fahrenheit. This is true whether the air conditioning unit’s cooling coil is a direct expansion refrigerant coil supplying cold air to the conditioned space or a water cooler supplying chilled water to the cooling coils. Operating at less than 34°F in- creases the likelihood of frosting up the direct expansion refriger- ant coil or freezing the water in the water cooler and water coil. However, operating at higher evaporator temperatures reduces the horsepower-per-ton ratio of the compressor (Table 4-1).
Air Standard Cycles - Otto, Diesel, Dual, Brayton Cycle With Intercooling, Reheating and Regeneration-Calculation of Airstandard Efficiency and Mean Effective Pressure