Professional Documents
Culture Documents
C.C.N. : 80443617
2
MAXIMUM PRESSURE ALARM SETTINGS .................. 34 TOTAL UNIT RESET AND DEFAULT VALUES ............ 50
STOP CONTROL SETTINGS..................................... 35 SECTION 10 — DIAGNOSTIC FUNCTIONS IN THE X04
CONTROLLER ....................................................................... 54
TOLERANCE SETTINGS........................................... 35
IR-PCB (INGERSOLL RAND COMPRESSOR INTERFACE PCB)..... 54
DAMPING SETTINGS .............................................. 36
CONNECTIVITY TO X4I AND DIAGNOSTIC LED
PRESSURE CHANGE SETTINGS ................................ 36 INDICATORS ............................................................ 54
AUXILIARY INPUT SETTINGS................................... 36 ‘IR-PCB’ PRESSURE REGULATION CONTROL INPUTS .. 55
AUXILIARY OUTPUT SETTINGS ............................... 37 VFD INPUT CONTROL DIAGNOSTIC INDICATOR ..... 55
ERROR LOG RESET................................................. 38 SEQ (REMOTE PRESSURE REGULATION CONTROL)
USER CONFIGURATION: TAB S03 .............................. 38 INPUT DIAGNOSTIC INDICATOR ............................ 55
PRESSURE SENSOR – RANGE SETTINGS ................... 39 ‘IR-PCB’ STATUS MONITORING OUTPUTS .............. 55
COMPRESSOR CONNECTION METHOD ................... 41 READY AND RUN STATUS SIGNALS ........................ 56
3
SECTION 2 — INTRODUCTION
The X4I is a specialized controller designed to provide safe, may have electro-pneumatic or microprocessor based
reliable, and energy-efficient control of your compressed controls. The X4I is completely customizable to meet the
air system. The X4I is capable of controlling up to four specific needs of your compressed air system.
positive displacement air compressors. The compressors
4
SECTION 3 — SAFETY
OPERATION
W A R N IN G : R is k o f D an g e r
!
• The X4I must only be operated by
competent personnel under qualified
W A R N IN G : R is k o f E le ctric S h o c k supervision.
5
i. Isolate the X4I from the main • The accuracy of sensor devices must be
electrical power supply. Lock the checked on a regular basis. They must be
isolator in the “OFF” position and calibrated when acceptable tolerances are
remove the fuses. exceeded. Always ensure any pressure
within the compressed air system is safely
ii. Attach labels to the isolator vented to atmosphere before attempting to
switch and to the unit stating remove or install a sensor device.
“WORK IN PROGRESS - DO NOT
APPLY VOLTAGE”. Do not switch • The X4I must only be cleaned with a damp
on electrical power or attempt to cloth, using mild detergents if necessary.
start the X4I if such a warning Avoid the use of any substances containing
label is attached. corrosive acids or alkalis.
• Make sure that all instructions concerning • Do not paint the control faceplate or
operation and maintenance are strictly obscure any indicators, controls,
followed and that the complete unit, with instructions or warnings.
all accessories and safety devices, is kept
in good working order.
6
SECTION 4 — COMPRESSOR CONNECTION AND CONTROL
7
X4I MAIN DISPLAY
User Interface
The User Interface display functiuonality is
depicted below:
a b User Interface DisplayUser Interface
Display Functionality
102
PSI
c a) System Pressure Value
b) System pressure Units
d 1 10:35 e c) Unit Status
d) Unit Active Functions
f 1 2 3 4 e) Time
g f) Compressor Number
A B C D g) Compressor Sequence Assignment
h) Compressor Status
h
ON – Active, Running
8
SECTION 5 — INSTALLATION
It is recommended that installation and commissioning be UNIT LOCATION
carried out by an authorized and trained product supplier.
Compressor IR-PCB
#3
RECEIVER
Compressor #3 Control Cable
X4I X03 CONNECTOR IR-PCB CONNECTOR
V3 V1
13 1
14 2
15 3
Compressor IR-PCB
16 4
17 5 #4
18 6
DRIP LEG Compressor #4 Control Cable
X4I X04 CONNECTOR IR-PCB CONNECTOR
V4 V1
19 1
20 2
21 3
22 4
23 5
24 6
9
POWER SUPPLY
DEMAND (DRY) SIDE PRESSURE CONTROL
X PM -T AC 2 4 2
1 2 3 4 1 2 3 4
X04
Pressure Sensor Located After Shared Cleanup
L N E E VO L TAG E S E L E C T Equipment
X01 230Vac
1 2 3 4
L N E X04
P P
VO L TAG E S E L E C T
115Vac
1
P
Power Supply Terminals
SUPPLY (WET) SIDE PRESSURE CONTROL Regular routine monitoring of pressure differential
across air treatment equipment is recommended.
P
P
1
10
PRESSURE SENSOR CONNECTION
run through grounded conduit no greater than 330 feet 3 GND C03
NO
(100 meters) in length. 4 D11
OUT
5 D12 C
NC
Each compressor in the system must be assigned a unique 6 +20V C02
NO
identification number from 1 up to the number of LED 5 V C
IN
compressors in the system. The identification number LED 2 LOAD
NC
LED 1 SEQ
should be clearly indicated on each compressor for
operational reference.
READY
LED 4
ALARM
RUN
LED 3
11
The voltage to this input must de-energize when the
Consult the air compressor manual or your air compressor is stopped and unavailable to produce air upon
compressor supplier/specialist for details before installing a load signal, or the emergency stop button is pressed, or
the X4I. when the compressor experiences a fault that prevents the
compressor from running.
Each air compressor must be equipped with an online/
offline pressure regulation system capable of accepting a When the compressor ready lamp or other control circuit is
remote load/unload signal through a volt free switching energized, the IR-PCB will detect the voltage and signal the
contact or a single electro-mechanical pressure switch. X4I that the compressor is ready and available to load and
produce air when a load request signal is given.
The IR-PCB accepts a 12V to 250V input voltage detection
system and utilizes universal relay contact control outputs
(250V “CE” / 115V “UL” @ 5A maximum) integrated directly The IR-PCB common input terminal must always be
into the circuits of an air compressor. The IR-PCB avoids the connected to the neutral, common or 0V line of the applied
need for additional relays or remote inputs. The IR-PCB also input voltage.
acts as an electrical barrier between the compressor and the
X4I providing protection and voltage isolation.
READY INPUT, ALTERNATIVE CONNECTION METHOD
Consult the X4I Interconnect and Application Guide In instances where a convenient voltage signal for a
prior to the installation of the X4I and the IR-PCB to the air compressor ready condition is not available, the “ready”
compressor. input can be connected directly to a constant compressor
control voltage (12V to 250Vac or dc). This will signal the
X4I that the compressor is ready and available at all times
INPUT FUNCTIONS when power is applied to the compressor. The X4I has a
built-in function to determine when a compressor is not
responding, or is in a shutdown condition, even if the
The IR-PCB is fitted with a six-pin terminal, C04, for “ready” signal says otherwise. If the X4I requests a
compressor monitoring. The IR-PCB uses two inputs, Ready compressor to run/load, but fails to detect a RUN signal
and Run, to determine compressor status. An alarm input within 60 seconds, the X4I will regard the compressor as
can be used if compressor warning indication is available “not ready” and indicate the compressor as not available. If
and required. The alarm input is optional and is not a RUN signal is reacquired at any time, the X4I will
necessary for system operation. automatically reset the compressor “not ready” condition
and re-establish control.
READY INPUT
+Vac
The ‘Ready’ connection is intended to indicate that the
compressor is in a “started” state, has no alarm condition F1
that has shut down the compressor, and is ready to respond
to X4I regulation without manual intervention.
R EAD Y LAM P 0V
0Vac
+V
READY
12
RUN INPUT
The IR-PCB input common terminal must always be
M A IN (LIN E ) C O N T A C T O R connected to the neutral, common or 0V line of the applied
0V input voltage.
+V
WARNING INPUT (OPTIONAL)
The IR-PCB is equipped with a warning input that can be
used to detect warning conditions.
ALAR M RUN READY The IR-PCB input common terminal must always be
C04 connected to the neutral, common or 0V line of the applied
input voltage.
Run Signal Circuit with Auxiliary Switch
In instances where a motor starter contactor is not available
or accessible, any part of a compressor control circuit that
is energized when the compressor is running can be
monitored. For example: fan contactor or voltage signal to a
remote starter.
13
OUTPUT FUNCTIONS
0V
+V
The X4I will control the IR-PCB load/unload relay outputs
based on the active system load and unload pressure LO A D
setpoints. The IR-PCB load/unload relay contacts can be S O LE N O ID
used for compressor controllers that have electro-
mechanical pressure switch load/unload regulation.
NC
NO
C
NC
NO
OUT IN
C 02
LO AD
S O L E N O ID
0V
+V
R U N -O N
T IM E R
NC
NO
C
NC
NO
The C01 and C02 terminals of the IR-PCB are intended to OUT IN
14
The IR-PCB connection examples shown in this manual are
Compressors that use electronic pressure detection intended to provide a guide for the majority of compressor
but are not equipped with a remote pressure control enable control systems in use. Some compressors have variations
feature will not automatically revert to local control if the in operation and/or function; consult your compressor
X4I is stopped or experiences a fault or loss of power. supplier/specialist for advice.
ir-P C B
C 02
AUXILIARY INPUT (OPTION)
NO L oca l/R em ote
The X4I is equipped with an auxiliary input at terminals 31
OUT C co m m o n and 32 (X07).
NC
NO
R e m o te Lo a d The function of the input is menu selectable and can be
co m m o n adapted for differing application requirements.
IN C
NC
X07
32
Alternate Logic 31
15
AUXILIARY OUTPUT (OPTION) potential can result in intermittent malfunction or anomaly
that is difficult to diagnose. To avoid this possibility, always
The X4I is equipped with a remote relay contact output at use shielded cables, securely bonded to a known ground at
terminals 33 and 34 (X08). one end. In addition, give careful consideration to cable
The function of the output is menu selectable and can be routing during installation.
adapted for differing application requirements. • Never route an RS485 data
communications or low voltage signal
X08 cable alongside a high voltage or 3-phase
34 power supply cable. If it is necessary to
R6 cross the path of a power supply cable(s),
33
always cross at a right angle.
16
SECTION 6 — CONTROL FEATURES AND FUNCTIONS
STANDARD CONTROL FEATURES AND When a compressed air system includes one or more
variable speed compressors, each variable speed
FUNCTIONALITY compressor must have its target pressure (on its local
controller) set to the system target pressure.
PRESSURE CONTROL The variable speed compressors in the system will run on
their target pressure and smooth out the variations in system
Pressure control is achieved by maintaining the system pressure. This assumes that system demand does not vary
pressure within an acceptable range, or pressure band, more than the capacity of the variable speed compressor.
which is defined and programmed by the user. Pressure will A variable speed compressor will be included in the load/
rise in the band when system demand is less than the unload sequence and be controlled exactly as a fixed speed
loaded compressor’s output. Pressure will fall in the band machine with the exception of speed control to maintain
when system demand is greater than the loaded target pressure.
compressor’s output.
Simply stated, pressure control is achieved by unloading
ANTI-CYCLING CONTROL
and loading compressors to closely match compressor
output with system demand within a specified pressure The most efficient way to utilize most air compressors is
band defined by PL and PH. See Figure 1. either fully loaded or off, with the exception of variable
speed compressors which can operate efficiently at reduced
Variable speed compressors also operate within the
loading. Compressor cycling (start-load-unload-stop, etc.)
pressure band and actively match compressor output with
is essential to maintain pressure control. Excessive cycling,
system demand by speeding up and slowing down around a
however, can result in poor compressor efficiency as well as
target pressure defined by the exact midpoint of the
increased maintenance.
pressure band defined by PT. See Figure 2.
Anti-cycling control is incorporated to help ensure that only
the compressors that are actually required are started and
operating while all others are kept off. Anti-cycling control
a
PH includes a pressure tolerance range or band, defined by the
user, which is outside of the primary pressure band. Inside
PT
the tolerance band, an active control algorithm continually
b
PL analyzes pressure dynamics to determine the last possible
second to add or cycle another compressor into the system.
This control is further enhanced by the ability to fine tune
the tolerance band settings and algorithm processing time
(Damping).
PH PT
PT PL
TO
PL - TO
PL
17
When system pressure is in the tolerance band, the X4I will system. Tolerance (TO) and damping (DA) can be used
continuously calculate the moment at which compressors for minor tuning of the system.
will be loaded or unloaded based on the rate of change of
system pressure. When the system pressure strays outside
SYSTEM VOLUME
of the tolerance band, the X4I will abandon energy
efficiency and begin to protect the system air pressure by
loading or unloading the compressors. Loading will be
delay controlled.
When the compressed air system storage is relatively small
compared to the system demand, and fluctuations are large
and quick, the tolerance band setting should be increased
to maintain energy efficient operation and avoid a situation
in which multiple compressors are loaded just to be
unloaded moments later.
- +
When the compressed air system is relatively large
compared to system demand and fluctuations are smaller Assorted Receiver Tanks
and slower, the tolerance band can be reduced to improve
System volume defines how fast system pressure will rise or
pressure control and maintain energy efficient operation.
fall in reaction to either increased/decreased demand or
The factory default setting for tolerance is 3.0 PSI (0.2Bar). increased/decreased supply. The larger the system volume,
This setting is user adjustable. the slower the pressure changes in relation to increased/
decreased demand or supply. Adequate system volume
enables effective pressure control and avoids system over-
DAMPING pressurization in response to abrupt pressure fluctuations.
Any time the pressure is within the Tolerance band the Adequate system volume is created by correctly sizing and
Anti-Cycling algorithm is active, sampling the rate of utilizing air receivers.
pressure change and calculating when to load or unload the The most accurate way to determine the size of air receivers
next compressor. The damping (DA) setting is a user or the additional volume required would be to measure the
adjustable setpoint that determines how quickly the size and duration of the largest demand event that occurs
controller samples and recalculates, effectively speeding up in the system, then size the volume large enough to ride
or slowing down the reaction time. through the event with an acceptable decrease in system
The X4I’s factory default DA setting of “1” is adequate for pressure. Sizing the volume for the worst event will ensure
the majority of compressed air systems but may need to be system stability and effective control over all other normal
adjusted in the following circumstances involving operating conditions.
aggressive and disproportionate system pressure changes: If measurement is not available, then estimating the largest
• Inadequate air storage event is a reasonable alternative. For example, assume that
• High pressure differential across the air the largest demand event could be equal to the loss of the
treatment equipment largest operating air compressor. System volume would be
sized to allow time for a back-up compressor to be started
• Incorrectly sized piping and loaded with an acceptable decrease in pressure.
• Slow or delayed compressor response
The following formula determines the recommended
In these circumstances, the X4I may overreact and attempt minimum storage volume for a compressed air system:
to load additional compressors that may not be necessary if
the system was given time to allow the system pressure to
stabilize after the initial compressor is given time to load. If
the tolerance has already been increased and the X4I is still
overreacting, then increasing the damping factor is the next
step.
V — “Volume of Required Storage” (Gal, Ft3, m3, L)
Damping is adjustable and is scaled from 0.1 to 10 with a
factory default of 1. A factor of 0.1 is a reaction time 10 T — “Time to Start Back-up Compressor” (Minutes)
times faster than the default and a factor of 10 is a reaction
C — “Lost Capacity of Compressed Air” (CFM, m3/min)
time 10 times slower than the default.
Pa — “Atmospheric pressure” (PSIa, BAR)
NOTE: There are many variables that go into
determining the stability and control of the system P — “Allowable Pressure Drop” (PSI, BAR)
pressure, only some of which are able to be controlled
by the X4I. System storage, air compressor capacity, and
air demand all need to be analyzed by experienced
professionals to determine the best installation for your
18
Example 1: Find Required Storage Volume in Ft3 and US Gal. based on a set interval, a set time of day each day, or a set
time of day once a week.
(4) - 25 Hp Compressors at 92 CFM (2.6 m3) each / 15
seconds to start and load a compressor. 5PSIG is the
The compressor load control strategy defines when
maximum allowable pressure drop.
compressors load and unload based on system pressure
T=15 Seconds (.25 minute) variations and whether they run in fixed or variable speed
modes.
C=92 ft3
Each compressor in a system will be assigned a permanent
Pa = 14.5 PSI number based on where they are wired into the terminal
Delta P = 5 PSI PCB. Compressor 1 will always be wired into terminal X01;
compressor 2 will always be wired into terminal X02, etc.
V = [.25 x (92 x 14.5)]/5
Each compressor will also be assigned a letter from A to D
V = (.25 x 1334)/5 based on its location in the sequence:
V = 333.5/5 • A = the base load compressor (the first
compressor to be used).
V = 67 Ft3
• B = the first trim compressor (the second
1 ft3 = 7.48 Gal compressor to be used).
• C = the second trim compressor (the third
Gal= 67 Ft3 x 7.48 compressor to be used).
Gal = 498.9 • D = the third trim compressor (the last
compressor to be used).
Example 2: Find Required Storage Volume in m3 and L.
Compressor sequence assignments are reviewed and
(4) - 25 Hp Compressors at 92 CFM (2.6 m3) each / 15 dynamically changed at a rotation event based on the
seconds to start and load a compressor. 0.34 BAR is the sequencing strategy that is selected.
maximum allowable pressure drop.
T=15 Seconds (.25 minute)
FIRST IN LAST OUT CONTROL MODE (FILO)
3
C=2.6 m
Compressor load sequence will be A, B, C, D and
Pa = 1BAR
Unload sequence D, C, B, A
Delta P = .34 BAR
V = [.25 x (2.6 x 1)]/.34 FIRST IN LAST OUT ROTATION MODE (FILO)
V = (.25 x 2.6)/.34 The default configuration of the X4I provides FILO (First In/
Last Out) sequence control strategy.
V = .65/.34
19
SEQUENCE ROTATION EVENTS Compressor A will always be the first to be loaded and last
to be unloaded.
A sequence rotation event can be triggered in the
following ways: a periodic interval, a pre-determined time PRIORITY SETTINGS
each day, or a pre-determined time day and time each
week. The sequence assignment pattern can be modified by using
the priority settings.
Please refer to the Quick Setup Manual to determine how to
configure the rotation events. Priority settings can be used to modify the rotation
sequence assignments. Compressors can be assigned a
ADVANCED CONTROL FEATURES AND priority of 1 to 4, where 1 is the highest priority. Any
compressor can be assigned any priority and any number of
FUNCTIONALITY compressors can share the same priority.
Priorities allow you to set up rotation groups. All
ADVANCED SEQUENCE CONTROL STRATEGIES compressors that have the same priority number will rotate
inside their own group. The group with the highest priority
The advanced configuration of the X4I provides VEC
will always be in the front of the sequence.
(Variable Energy Control) sequence control strategy, Priority
Settings, Table Selection, and Pre-fill operation. For example, in a four compressor system including one
variable speed compressor in the compressor 1 position
you may want the variable speed compressor to always be
VARIABLE ENERGY CONTROL MODE (VEC)
in the Lead position. By assigning compressor 1 a priority of
1 and the other three compressors a priority of 2, the
The primary function of VEC mode is to accommodate variable speed compressor will always remain at the front of
a variable speed compressor connected to the X4I using an the sequence:
IRV-PCB interface.
1 2 3 4
VEC mode utilizes the FILO sequencing and rotation
strategy with the additional control philosophy needed to
efficiently control variable speed compressors. 1 2 2 2
20
In a third example, there is a four compressor system that Each table consists of the following parameters which can
includes a variable speed compressor designated be set independently in each table:
compressor 1 and a fixed speed compressor that is an • PH – High Pressure Setpoint
emergency backup assigned as compressor 4. To ensure
• PL – Low Pressure Setpoint
that compressor 1 is always at the front of the sequence
and compressor 4 is always at the end of the sequence, set • Pm – Minimum pressure warning level
the priority as shown below: • SQ – Sequence Rotation Strategy
• 01 – Compressor 1 Priority
1 2 3 4
• 02 – Compressor 2 Priority
1 2 2 3 • 03 – Compressor 3 Priority
#1 A B C D • 04 – Compressor 4 Priority
#2 A C B D
The “maximum” pressure fault level and the rotation
#3 A B C D interval, or rotation time, are set independently in a
configuration menu and are unchanging regardless of the
#4 A C B D table selected.
When the X4I is instructed to change between tables, it will
Compressor 1 has priority 1, compressor 4 has priority
not abruptly change the system operating parameters. The
3 and all other compressors have priority 2
X4I will adjust the system target pressure upward or
A last example involves another four compressor system downward to the next table’s settings. This transition will
that will be assigned into two independently rotation occur gradually to preserve energy efficiency and safe,
groups. Compressors 1 and 2 are given priority 1 and reliable control:
compressors 3 and 4 are given priority 2. This results in the
rotation sequence shown below: 1 2
1 2 3 4
1 1 2 2
#1 A B C D PC
#2 B A D C Changing Target Pressures
#3 A B C D The time the system is allotted to change the target
pressure is known as the Pressure Change Time (PC). This is
#4 B A D C
a value that is adjustable in the system settings screen. See
the Quick Setup Manual.
Two independently rotating compressor groups
If the X4I is able to complete the transition in less time than
is allotted without threatening energy efficiency then PC will
be automatically shortened.
T01
PH ----
PL
Pm
----
---- An aggressively short time setting will compromise
SQ ----
TABLES AND THE PRESSURE SCHEDULE energy efficiency.
21
The pressure schedule has the capability of changing tables ALTERNATE CONTROL FEATURES AND
based on the time of day, once each day, or once each day FUNCTIONALITY
except weekends. Please see the Quick Setup Manual for
detailed information on how to configure the pressure
schedule. The alternate control strategies of the X4I provides EHR
(Equal Hours Run) and FIFO (First In/First Out) sequence
control strategy.
PRE-FILL
The pre-fill feature provides an energy efficient method of EQUAL HOURS RUN MODE
increasing pressure to normal operating levels upon system
start. This feature avoids the inefficient potential for all The primary function of EHR mode is to keep the
compressors to start and load in an attempt to quickly get running hours of all compressors in the system as close as
the system pressure up to normal levels: possible. This provides the opportunity to service all of the
compressors at the same time, given that the expected
service interval for the compressors is similar.
22
If system pressure continues to decrease, compressor 2 (B)
The running hours meter display on most compressors will be loaded and be reassigned to (A) while compressor 1
are intended for approximate service interval indication is reassigned as (D). If this causes system pressure to rise
only and may deviate in accuracy over a period of time. above the high pressure setpoint, then compressor 1 (D)
Compressors will be utilized following the FILO strategy. will be unloaded to allow compressor 2 (A) to maximize its
run time. If system pressure decreases further, compressor
3 will be loaded and reassigned to (A) while Compressor 2
FIRST IN FIRST OUT MODE (FIFO) is reassigned to (D) and so on.
The most recently loaded compressor will always be
The primary function of FIFO mode is to minimize the assigned (A) and the longest running compressor will
utilization on any one compressor. This control strategy is always be assigned (D).
commonly used with air cooled reciprocating compressors.
1
23
SECTION 7 — DISPLAY AND MENU OPERATION
The Main Display and the keypad and navigation buttons on
the X4I are depicted below and provide the following
functionality:
User Interface
The User Interface display functiuonality is
depicted below:
a b User Interface DisplayUser Interface
Display Functionality
102
PSI
c a) System Pressure Value
b) System pressure Units
d 1 10:35 e c) Unit Status
d) Unit Active Functions
f 1 2 3 4 e) Time
g f) Compressor Number
A B C D g) Compressor Sequence Assignment
h) Compressor Status
h
ON – Active, Running
24
Unit Functions:
The following Icons are used by the X4I to
display the Controller Active Functions.
Operating Mode:
Power Failure Auto-Restart Below the active lower, or load, pressure set point
Prefill Function
Pressure Schedule
Unit Status:
The following Icons are used by the X4I to
display the Controller Status.
Stopped
Standby
Compressor Status:
The following Icons are used by the X4I to display the Compressor/s Status.
25
DISPLAY ITEM STRUCTURE INFORMATION DISPLAYS
Operational system status and values are accessible from To view detailed information applicable to the selected User
the normal user display. To view status or values that are
not normally visible on the default screen, press UP or menu display item press the ENTER button:
DOWN. All standard user display items are viewable only
and cannot be adjusted. The standard user display items
are regarded as “Menu Page 00” items. STATUS DISPLAY
All adjustable value, parameter or option item displays are
grouped into “menu mode” lists. Items are assigned to a list P00
according to type and classification. Item lists are identified
by page number (or menu number). All adjustable
parameters and options are assigned to menu mode pages
#1 18:00 T02
“P01” or higher.
102 psi
NORMAL OPERATIONAL DISPLAY (MENU 1 98 psi
PAGE P00) 80 psi
At controller initialization, all display elements and LED Status Display Screen
indicators are switched on for three seconds and then the
normal operating display is shown. In normal operational
display mode, the main display will continuously show the If the ‘Pressure Schedule’ feature is active; shows the
detected system pressure and the Item display will show the day of the week (#1: Monday), the time of day (18:00) and
first item of the “Page 00” menu. User menu “items” can be the table to be used (T02) of the next scheduled instruction
selected using the UP or DOWN buttons at any time. to be executed.
Pressing the ENTER button will lock any selected item
display and inhibit return to the default display. When an
item display is locked, the “lock key” symbol will be shown. The current active ‘Table’ (T01)
To unlock an item display, press UP or DOWN to view an 1
alternative item display or press RESET or ESCAPE. No item Upper, or unload, pressure setpoint
values, options or parameters can be adjusted in “Page
P00”. If a fault condition occurs, the fault code becomes the Lower, or load, pressure setpoint
first list item and the display will automatically jump to Minimum pressure Alarm (Warning)
display the fault code. More than one active fault code item
can exist at any one time and can be viewed by pressing UP
or DOWN. The most recent “active” fault will be at the top of
the list.
SEQUENCE ROTATION
P00
#4 18:00
Main Status Screen
18 / 05 / 2006
ABCD
26
START
Press the ESCAPE button to return to the normal To start the X4I, press START. If the pre-fill function is
enabled, and system pressure is below the set pre-fill
operational display screen. pressure, the system will enter pre-fill mode for the set
pre-fill time.
NOTE: The sequence assignment can be manually rotated
at any time. When viewing the “Sequence Rotation” infor- See the section on pre-fill for more information.
the ESCAPE button to abandon the manual rota- Each compressor in the system must be started
tion. (running or in a standby or auto restart condition) before
X4I control of the compressor can be established. The X4I
Automated sequence rotation is not disrupted by a man- will not start a compressor that is in a stopped condition.
ual rotation; the next scheduled automated sequence
rotation event will still occur.
27
SECTION 8 — COMMISSIONING
When commissioning the X4I, carry out the following 3. Switch on the power supply to the X4I.
procedures before attempting to start.
4. The control program identification will be displayed
for a short period followed by the normal
It is recommended that an authorized and trained operational user display.
service technician perform the commissioning.
PRESSURE DISPLAY
PHYSICAL CHECKS
Check the displayed system pressure. If the pressure is
1. Before applying power to the X4I, ensure the power incorrect, or inaccurate, check the type and range of the
supply connections are correct and secure and the sensor and carry out the pressure sensor commissioning
operating voltage selector is set correctly for the and calibration procedure. If the display shows an error,
power supply voltage in use (115Vac or 230Vac (+- this will need to be corrected before continuing. See the
10%), 50/60Hz). Operator’s Manual for troubleshooting and correcting the
fault/error condition.
2. Open the front panel of the X4I and check the
location of the link wire(s) connected to the
“Voltage Selection” terminals of the power supply X4I QUICK SET-UP CONFIGURATION
PCB. If necessary, change the link wire locations to
those illustrated for the voltage in use.
Before successful basic operation can be established
specific parameters must be entered prior to startup.
See the section on Installation for more Please refer to the X4I Quick Setup Manual for instruction to
information. accomplish this.
28
SECTION 9 — SYSTEM CONFIGURATION
29
REAL TIME CLOCK SETTINGS the Month for the Real Time Clock. The values for
this parameter are “1” to “12”.
30
5. You should be returned to the S01 home screen ROTATION INTERVAL SETTINGS
and values just entered should appear next to the
PS parameter.
1. From the S01 home screen scroll up (+) or
AUTO RESTART SETTINGS
scroll down (-) to move the cursor to
highlight 04- RP (Rotation Interval). New Picture
1. From the S01 home screen scroll up (+) or Below
31
TABLE SELECT SETTINGS
7. Scroll up (+) or scroll down (-)
until the value is set for the Rotation Interval
1. From the S01 home screen scroll up (+) or
required for your air system. Press the ENTER
button to accept this parameter. scroll down (-) to move the cursor to
highlight 05- TS (Table Select).
8. The flashing cursor should be displayed
highlighting the Minutes dash. This sets the
Minutes for the Rotation Interval. The values for
this parameter are:
• “0” to “59”
• “–“ represents the Rotation Interval is
disabled.
32
BACKLIGHT ADJUST SETTINGS USER CONFIGURATION: TAB S02
1. From the S01 home screen scroll up (+) or 1. After you have returned to the page selection
scroll down (-) to move the cursor to screen, scroll up (+) or scroll down (-)
highlight 06- BL (Backlight Adjust).
until the S02 page is highlighted.
Backlight Settings
2. The default setting for this parameter is 5. The 5 S02 Tab Screen
indicates the current level the backlight is set for.
The default display Backlight Setting level has been
set to enable a ‘continuous use service life’ in 2. Press the ENTER button to confirm your
excess of 90000 hours while providing good selection. The cursor should be flashing on 01 P>.
readability in all ambient light conditions. The
display will temporarily increase brightness by 2
levels when a button is pressed and return to
normal setting after a period of no keypad activity.
required for visibility. Press the ENTER button 1. From the S02 home screen scroll up (+) or
to confirm this selection. You should be returned to
the S01 home screen and values just entered
should appear next to the BL parameter. scroll down (-) to move the cursor to
highlight 01- P> (Units Settings).
6. After you have completed adjusting the settings on
Units Settings
2. The default setting for this parameter is PSI. The PSI
indicates the pressure units selected for X4I. This
parameter determines the X4I display and
operating units.
33
4. The flashing cursor should be displayed MAXIMUM PRESSURE ALARM SETTINGS
highlighting the Units parameter. The values for
this parameter are:
1. From the S02 home screen scroll up (+) or
• “PSI”
• “BAR” scroll down (-) to move the cursor to
• “kPA” highlight 03- PM (Maximum Pressure Alarm).
34
STOP CONTROL SETTINGS TOLERANCE SETTINGS
35
6. You should be returned to the S02 home screen
and values just entered should appear next to the
5. Scroll up (+) or scroll down (-)
TO parameter.
until the number is set to the value required to
maintain control of for your air system. Press the
DAMPING SETTINGS
ENTER button to confirm your selection.
6. You should be returned to the S02 home screen
1. From the S02 home screen scroll up (+) or and values just entered should appear next to the
DA parameter.
scroll down (-) to move the cursor to
highlight 06- DA (Damping Settings).
PRESSURE CHANGE SETTINGS
S01 S02 S03
1. From the S02 home screen scroll up (+) or
05 TO 3.0 PSI
06 DA 1.0 scroll down (-) to move the cursor to
07 PC 4 Min highlight 07- PC (Pressure Change Settings).
08 AI 05:SS NO
09 AO 07:ON NO S01 S03
S02
06 DA 1.0
Damping Settings 07 PC 4 Min
08 AI 05:SS NO
2. The default setting for this parameter is 1.0. The
09 AO 07:ON NO
parameter adjusts the time before an additional 10 ER X
compressor is loaded in accordance with the
urgency of the situation to increase air system
capacity further. The rate of pressure change may
be aggressive and disproportionate. In such
instances the X4I may over-react and attempt to Pressure Change Settings
load an additional compressor that may not be 2. The default setting for this parameter is 4 Min. The
necessary once the initial compressor is running, 4 minutes is the time the X4I will use implement a
loaded, and able to contribute adequate additional smooth and controlled change from one ‘target’
generation capacity. The X4I has a dynamic pressure level to another when a Table change is
reaction algorithm that is pre-set by default to made.
accommodate for the majority of installation
characteristics. If an increase or decrease in the
Tolerance band is insufficient, the reaction 3. Press the ENTER button to display the Pressure
response can be influenced by increasing or Change Settings configuration screen.
decreasing the ‘Damping’ factor.
4. The flashing cursor should be displayed
• If air system storage is generous and the highlighting the 4. The values for this parameter
rate of the pressure change is slow to rise, are “1” for 1 minute between Table target pressure
then the ‘Damping’ can be increased to setpoint changes through “120” for 120 minutes
improve pressure control without between Table target pressure setpoint changes.
compromise to optimum energy efficiency.
As the Dampening value is increased, the
Loading of additional compressors is less 5. Scroll up (+) or scroll down (-)
rapid. until the number is set to the value required
• If air system storage is inadequate and the maintain control of for your air system. Press the
rate of the pressure change is fast to fall,
then the ‘Damping’ can be decreased to ENTER button to confirm your selection.
improve pressure control without 6. You should be returned to the S02 home screen
compromise to optimum energy efficiency. and values just entered should appear next to the
As the Damping value is decreased, the PC parameter.
Loading of additional compressors is more
rapid.
AUXILIARY INPUT SETTINGS
3. Press the ENTER button to display the
Dampening Settings configuration screen. 1. From the S02 home screen scroll up (+) or
4. The flashing cursor should be displayed
highlighting the 1.0. The values for this parameter scroll down (-) to move the cursor to
are “.1” for the fastest Damping reaction time (10 highlight 08- AI (Auxiliary Input Settings).
times faster than the default of 1.0) through “10.0”
for the slowest Damping reaction time (10 times
slower than the default of 1.0).
36
8. You should be returned to the S02 home screen
S01 S02 S03 and values just entered should appear next to the
AI parameter.
07 PC 4 Min
08 AI 05:SS NO AUXILIARY OUTPUT SETTINGS
09 AO 07:ON NO
10 ER X
01 P> PSI
1. From the S02 home screen scroll up (+) or
2. The default setting for this parameter is 05:SS NO. S01 S03
S02
With this setting, the function for the Auxiliary
Input for X4I is set to Remote Start/Stop. The
function of the Auxiliary Input as well as the state 08 AI 05:SS NO
of the contacts controlling the Auxiliary Input can 09 AO 07:ON NO
be changed. 10 ER X
01 P> PSI
02 NC 3
3. Press the ENTER button to display the
Auxiliary Input Settings configuration screen.
4. The flashing cursor should be displayed
highlighting the 05:SS parameter. The values for Auxiliary Output Settings
this parameter are:
2. The default setting for this parameter is 07:ON NO.
• “01:T1”Override > Use Table 1 With this setting, the function for the Auxiliary
Output for X4I is set to the X4I is Active. The
• “02:T2”Override > Use Table 2 function of the Auxiliary Output as well as the state
• “03:T3”Override > Use Table 3 of the contacts controlling the Auxiliary Output can
be changed. If it is determined this value requires a
• “04:TS”Override > Place the X4I in Standby change, then this will need to be modified.
• “05:SS”Remote Start/Stop (Default)
• “06:AA”Remote Alarm (always active) 3. Press the ENTER button to display the
Auxiliary Output Settings configuration screen.
• “07:AR”Remote Alarm (active when X4I is
running, inhibited when the X4I is stopped 4. The flashing cursor should be displayed
or in Standby highlighting the 05:SS parameter. The values for
this parameter are:
• “08:TA”Remote Trip (always active)
• “01:AFAny Fault”Any Alarm (Warning),
• “09:TR”Remote Trip (active when X4I is Shutdown (Trip) or Compressor Not
running, inhibited when the X4I is stopped Available.
or in Standby
• “02:ATAny Trip”Any Shutdown (Trip) or
Compressor Not Available.
5. Scroll up (+) or scroll down (-) • “03:CFCompressor Fault”Any compressor
until you have selected the input function desired. Alarm (Warning), Shutdown (Trip) or Not
Available
Press the ENTER button to confirm your
selection. • “04:CACompressor Alarm”Any compressor
Alarm (Warning)
37
• 11:POPressure Control OverrideNormal, or 4. The flashing cursor should be displayed
Pressure Schedule operation is being
manually overridden highlighting the . The values for this parameter
are:
5. Scroll up (+) or scroll down (-) • “ ” for not resetting the Error log
until you have selected the output function desired.
• “ “ for resetting the Error log
Press the ENTER button to confirm your
selection.
6. The flashing cursor should be displayed 5. Scroll up (+) or scroll down (-) to
highlighting the NO. The values for this parameter select the function you want to perform. Note: If
are:
you select the to reset the Error Log, the .will
• “NO” for the auxiliary output relay contacts
are normally open and will close when the revert back to the after selecting the ENTER
set function is active or true
• “NC“ for the auxiliary output relay contacts button. Press the ENTER button to confirm
are normally closed and will open when the your selection.
set function is active or true; or in the 6. You should be returned to the S02 home screen
event of a X4I shutdown or loss of power
and the should appear next to the ER parameter.
7. Scroll up (+) or scroll down (-) to 7. After you have completed adjusting the settings on
select the appropriate setting for your output
ERROR LOG RESET 1. After you have returned to the page selection
09 AO 07:ON NO
10 ER X
01 P> PSI
02 NC 3
03 PM 145 PSI
38
PRESSURE SENSOR – OFFSET PRESSURE SENSOR – RANGE SETTINGS
1. From the S03 home screen scroll up (+) or 1. From the S03 home screen scroll up (+) or
scroll down (-) to move the cursor to scroll down (-) to move the cursor to
highlight 01- 1O (Pressure Sensor 1 Offset highlight 02- 1R (Pressure Sensor Range Settings).
Settings).
S02 S03 C01
S02 S03 C01
02 1R 232 PSI
01 1O 0 PSI 01 1O 0 PSI
02 1R 232 PSI
39
COMPRESSOR CONFIGURATION: TAB C01
3. Press the ENTER button to display the
Compressor Run Hours setup screen for
1. After you have returned to the page selection compressor #1
4. The flashing cursor should be displayed
screen, scroll up (+) or scroll down (-) highlighting the 0. The values for this parameter
are “0 to x” where x = the actual run hours for the
until the C01 page is highlighted. compressor connected to the #1 control channel.
2. Press the ENTER button to confirm your down (-) to move the cursor to highlight
selection. The cursor should be flashing on line 01 the remaining compressors and set the run hours
01. to match each of the other compressors.
8. You should be returned to the C01 home screen
S03 C01 C02 and values just entered should appear next to the
01 parameter. Once all run hours have been
entered for all compressors, you should be
01 01 0 hrs returned to the C01 home screen and all values
entered should appear next each compressor
02 02 0 hrs
parameter.
03 03 0 hrs
04 04 0 hrs 9. After you have completed adjusting the settings on
C01 Home Screen the C01 screen press the ESCAPE button to
return to the page selection screen.
COMPRESSOR RUN HOURS
COMPRESSOR CONFIGURATION: TAB C02
1. From the C01 home screen scroll up (+) or
1. After you have returned to the page selection
01 01 0 hrs
02 02 0 hrs
03 03 0 hrs
04 04 0 hrs
40
6. The flashing cursor should be displayed
highlighting the Compressor Start Sequence Time.
The Default setting for this parameter is 10 Sec.
This is the time required to start the motor and
then load the compressor. The values for this
parameter are “0” to “60” seconds.
Compressor Connection Settings 10. You should be returned to the C02 home screen
and ‘ir-PCB’ should appear next to the 01-01
2. The default setting for this parameter is I-PCB. parameter.
This setting is used for the type, method of
connection, and the control functionality, of each
compressor connected to the X4I. Each air 11. IRV-PCB Setup: Scroll up (+) or scroll
compressor in the system is integrated with the X4I
using an interface module.
down (-) to change the value to IRV-PCB.
3. Press the ENTER button to display the Press the ENTER button to confirm your
Compressor Connection setup screen for selection.
compressor #1
12. The flashing cursor should be displayed
4. The flashing cursor should be displayed highlighting the Compressor Start Sequence Time.
highlighting the I-PCB. The values for this The Default setting for this parameter is 10 Sec.
parameter are: This is the time required to start the motor and
then load the compressor. The values for this
• “IR-PCB” for Fixed speed, load/unload; parameter are “0” to “60” seconds.
connected to X4I using ‘ir-PCB’ module
using 6-wire method.
• “IRV-PCB” for Variable Speed; connected to 13. Scroll up (+) or scroll down (-)
X4I using ‘ir-PCB’ module employing the to change the value to the time required. Press the
7-wire ‘V’ terminal method
ENTER button to confirm your selection.
• “I-485” for Fixed speed, load/unload;
connected to X4I on Multi485 network. 14. The flashing cursor should be displayed
highlighting the ‘i-PCB’ Alarm (Warning) Input. The
• “V-485” for Variable Capacity/Speed;
Default setting for this parameter is +V=!. If the ‘i-
connected to X4I on Multi485 network
PCB’ Alarm input detects a voltage between 12-
250VAC/DC, an alarm (Warning) condition is
generated. The values for this parameter are:
5. IR-PCB Setup: Scroll up (+) or scroll
• +V=! for an Alarm (Warning) condition is
generated if the ‘ir-PCB’ Alarm input
down (-) to change the value to IR-PCB.
detects a voltage between 12-250Vac/dc
(default)
Press the ENTER button to confirm your
selection.
41
• 0V=! for an Alarm (Warning) condition is 24. The flashing cursor should be displayed
generated if the ‘ir-PCB’ Alarm input highlighting the Compressor Start Sequence Time.
detects no voltage. The Default setting for this parameter is 10 Sec.
This is the time required to start the motor and
then load the compressor. The values for this
15. Scroll up (+) or scroll down (-) parameter are “0” to “60” seconds.
to change the value for the Alarm condition
required for your application. Press the ENTER 25. Scroll up (+) or scroll down (-)
button to confirm your selection. to change the value to the time required. Press the
16. The flashing cursor should be displayed ENTER button to confirm your selection.
highlighting the Compressor Run-On Stop Time.
The Default setting for this parameter is 0 Sec. 26. You should be returned to the C02 home screen
This is the time that the compressor main motor and ‘v-485’ should appear next to the 01-01
will continue to run when the compressor is parameter.
unloaded. The time is from the moment the
compressor unloads until the main motor stops
and the compressor enters a ‘Standby’ or ‘Auto 27. Repeat this by scrolling up (+) or scrolling
Restart’ condition. This setting is only applicable
to ‘IRV-PCB’ connectivity and is not displayed for
down (-) to move the cursor to highlight
other connectivity options. The values for this
the remaining compressors and set the
parameter are “0” to “999” seconds.
Compressor Connection type and the Compressor
Connection parameters for each of the other
compressors.
17. Scroll up (+) or scroll down (-)
to change the value to the time required. Press the 28. You should be returned to the C02 home screen
and values just entered should appear next to the
enter button to confirm your selection. 01 parameter Once all values have been entered for
all compressors, you should be returned to the C01
18. You should be returned to the C02 home screen home screen and all ‘i-PCB’ values entered should
and ‘irv-PCB’ should appear next to the 01-01 appear next each compressor parameter.
parameter.
29. After you have completed adjusting the settings on
21. Scroll up (+) or scroll down (-) until the T01 page is highlighted.
to change the value to the time required. Press the
42
2. Press the ENTER button to confirm your 5. Scroll up (+) or scroll down (-)
selection. The cursor should be flashing on line 01 until the number is set to the value required to
PH. maintain control of for your air system. Press the
08 04 1
01 PH 102 PSI Low Pressure Setpoint Setting
02 PL 98 PSI
2. The default setting for this parameter is 98 PSI.
03 Pm 0 PSI The 98 PSI indicates the Low Pressure Setpoint that
04 SQ FILO ( ) used to load the compressor when the Table is
active.
High Pressure Setpoint Setting 3. Press the ENTER button to display the Low
2. The default setting for this parameter is 102 PSI. Pressure Setpoint setup screen.
The 102 PSI indicates the High Pressure Setpoint 4. The flashing cursor should be displayed
that is used to unload the compressor when the highlighting the 98 PSI. The values for this
Table is active. parameter are:
• The highest value for the Low Pressure
3. Press the ENTER button to display the High setpoint = PH “High Pressure” setpoint
Pressure Setpoint setup screen. minus TO “Tolerance”.
4. The flashing cursor should be displayed i. If PH is set for 102 PSI and TO is
highlighting the 102 PSI. The values for this set for 3.0 PSI, then the highest
parameter are: value for the Low Pressure
setpoint would be 99 PSI.
• The highest value for the High Pressure
setpoint = PM “Maximum Pressure Alarm” • The lowest value for the Low Pressure
minus 2 times TO “Tolerance”. setpoint = Pm “Minimum Pressure Alarm”
setpoint plus 2 times TO “Tolerance”
i. If PM is set for 145 PSI and TO is
set for 3.0 PSI, then the highest ii. If Pm is set for 80 PSI and TO is
value for the High Pressure set for 3.0 PSI, then the lowest
setpoint would be 139 PSI. value for the Low Pressure
setpoint would be 86 PSI...
• The lowest value for the High Pressure
setpoint = PL “Low Pressure” setpoint plus
TO “Tolerance”
5. Scroll up (+) or scroll down (-)
ii. If PL is set for 98 PSI and TO is set until the number is set to the value required to
for 3.0 PSI, then the lowest value maintain control of for your air system. Press the
for the High Pressure setpoint
would be 101 PSI. ENTER button to confirm your selection.
43
6. You should be returned to the T01 home screen
and values just entered should appear next to the P00 T01 T02
PL parameter.
03 Pm 80 PSI
MINIMUM PRESSURE ALARM SETTINGS 04 SQ FILO ( )
05 01 1
06 02 1
1. From the T01 home screen scroll up (+) or 07 03 1
• The lowest Minimum Pressure Alarm • FIFO – First In First Out. The Rotation and
setpoint = “The minimum range of the Control functionality of the FIFO mode is
pressure transducer used.“ the first compressor loaded is the first
compressor to be unloaded
• The highest Minimum Pressure Alarm
setpoint = “The value from the Table PL – • VEC – Variable Energy Control. This uses
Low Pressure Setpoint” minus 2 times TO the same Rotation and Control
“Tolerance”” functionality of the FILO mode with the
additional control required for variable
i. If PL in Table 1 (T01) is set for speed compressor installations
100 PSI and TO is set for 3.0 PSI,
then the highest Minimum • EHR – Equal Hours Mode. The Rotation and
Pressure setpoint would be 94 Control functionality of the EHR mode is to
PSI. equalize the Run Hours on all compressors
5. Scroll up (+) or scroll down (-) 5. Scroll up (+) or scroll down (-)
until the number is set to the value required to until the control mode is set to the value required
maintain control of for your air system. Press the to maintain control of for your air system. Press
ENTER button to confirm your selection. the ENTER button to confirm your selection.
6. You should be returned to the T01 home screen 6. You should be returned to the T01 home screen
and values just entered should appear next to the and values just entered should appear next to the
Pm parameter. SQ parameter
1. From the S01 home screen scroll up (+) or 1. From the T01 home screen scroll up (+) or
scroll down (-) to move the cursor to scroll down (-) to move the cursor to
highlight 04- SQ (Sequence Strategy). highlight 05- 01 (Compressor Priority).
44
COMPRESSOR #2 THROUGH 4 PRIORITY SETTINGS
P00 T01 T02
1. Repeat Steps above for Compressor #2, #3, and #4
04 SQ FILO ( )
Priority settings. When complete, the ENTER
05 01 1
button to confirm your selection. You should be
06 02 1 returned to the T01 home screen
07 03 1
08 04 1 2. After you have completed adjusting the settings on
Compressor #1 Priority Setting the T01 screen, press the ESCAPE button to
return to the page selection screen.
2. The default setting for this parameter is 1. The 1
indicates the Compressor Priority setting for 3. Repeat the T02 and T03 Tabs Screen if you will be
compressor number #1 Any compressor can be using more than one Table in your application.
assigned any priority or remove it from Sequence
Rotation and Control and any number of 4. After you have completed adjusting the settings on
compressors can have the same priority. By
changing the priority setting, it can be used to
modify the ‘Rotation’ sequence assignment. For
example: The air system configuration is a single the other T0x screens, press the ESCAPE
variable speed compressor that should be always button to return to the page selection screen.
loaded first and act a trim compressor and 3 fixed
speed compressors that should be rotated on an PRESSURE SCHEDULE CONFIGURATION P01
equal basis. You would assign the variable speed
compressor a Priority of 1 and the 3 fixed speed TAB SCREEN
compressors a Priority of 2. The variable speed
compressor is always loaded first and the 3 fixed
1. After you have returned to the page selection
speed compressors would load and rotate based on
the Sequence and Rotation setup.
screen, such as in figure 3, scroll up (+) or
1 2 3 4
#2 A C D B
#3 A D B C
#4 A B C D
Priority Example
45
PRESSURE SCHEDULE SETTINGS this parameter are “0” to “59”. The value “–“
indicates the Pressure Schedule is disabled.
• “8” for every working day of the week 14. You should be returned to the P01 home screen
(every day, Monday through Friday, 15. After you have completed adjusting the settings on
excluding Saturday and Sunday)
• “9’” for every day of the week
(every day, Monday through Sunday)
the P01 screen, press the ESCAPE button to
• “–“ for disabling the Pressure Schedule return to the page selection screen.
5. Scroll up (+) or scroll down (-) PRE-FILL CONFIGURATION P02 TAB SCREEN
until the value is set for the Pressure Schedule
1. After you have returned to the page selection
required for your air system. Press the ENTER
button to accept this parameter. screen, such as in figure 3, scroll up (+) or
6. The flashing cursor should be displayed
highlighting the Hours dash (Military Time). This scroll down (-) until the P02 page is
sets the Hour for the Pressure Schedule. The values highlighted.
for this parameter are “00” to “23”. The value “–“
indicates the Pressure Schedule is disabled.
46
2. Press ENTER to confirm your selection. The • “ ! X ” for Pre-fill, Standard Mode
cursor should be flashing on line 01 PF. ii. If one or more of the pre-defined
pre-fill compressors experiences
P01 P02 S01 a shutdown, or is stopped, the
pre-fill function is cancelled and
normal operation begins.
06 03 X
01 PF X
02 PT - MIN 5. Scroll up (+) or scroll down (-)
03 PP 0 PSI until the value is set for the Pre-fill Function
04 01 X
required for your air system. Press the ENTER
button to accept this parameter.
Home Screen 6. You should be returned to the P02 home screen
and values just entered should appear next to the
PF parameter.
PRE-FILL FUNCTION SETTINGS
2. The default setting for this parameter is . The Pre-fill Time Setpoint Setting
2. The default setting for this parameter is – MIN .
indicates the pre-fill function is turned off. The
The – MIN indicates the Pre-fill Time is turned off.
pre-fill function provides a controlled and energy
The Pre-fill Time Setpoint (in minutes) determines
efficient method of increasing pressure to normal
the time the Pre-fill Function has to start and load
operating levels at system start. This feature avoids
the designated Compressor/s to increase system
the inefficient potential for all available system
pressure to normal operational levels
compressors to start and load before pressure
reaches the normal operating level.
3. Press the ENTER button to display the Pre-fill
Time Setpoint screen.
3. Press the ENTER button to display the pre-fill
function setpoint screen. 4. The flashing cursor should be displayed
4. The flashing cursor should be displayed highlighting the . The values for this parameter
are:
highlighting the . The values for this parameter
are: • “–” for the Pre-fill Time is Off
• “1 to 120” for the number of minutes for
• “ ” for the Pre-fill Function is Off the Pre-fill Time Setpoint
47
PRE-FILL PRESSURE SETTINGS
P01 P02 S02
1. From the P02 home screen scroll up (+) or ENTER button to confirm your selection.
2. You should be returned to the P02 home screen
scroll down (-) to move the cursor to 3. After you have been returned to the page selection
highlight 04- 01 (Pressure Schedule).
48
DIAGNOSTICS D01 TAB SCREEN X4I CONTROLLER DIAGNOSTICS
D1Digital Input 1
1. After you have returned to the page selection D2Digital Input 2
D3Digital Input 3
screen, scroll up (+) or scroll down (-)
D4Digital Input 4
until the D01 page is highlighted. D5Digital Input 5
D6Digital Input 6
D7Digital Input 7
D8Digital Input 8
D2 Tab Screen
R1Relay Output 1
49
DIGITAL INPUTS
OFF (open circuit)
ON (closed circuit)
Pulsing
The pulse signal from an “ir-PCB” is 0V to 24VDC at 50/
60Hz. A typical DC voltage meter, or multimeter, will detect
this as 12VDC +-4V.
ANALOG OUTPUT
The analog output can be manually adjusted. Use UP (plus)
and DOWN (Minus) to adjust and ENTER. The output will
return to normal operational value upon menu exit.
After you have completed adjusting the settings on the D01
50
The Default Parameters for all X4I settings are shown in the following lists.
ON
TABLE #1
OFF TABLE #3
T01
Pulsing T03
PHHigh Pressure Setpoint
Default Setting is: 102 PSI PHHigh Pressure Setpoint
PLLow Pressure Setpoint Default Setting is: 102 PSI
Default Setting is: 98 PSI PLLow Pressure Setpoint
PmMinimum Pressure Alarm Default Setting is: 98 PSI
Default Setting is: 0 PSI PmMinimum Pressure Alarm
SQSequence Rotation Mode Default Setting is: 0 PSI
Default Setting is: FILO SQSequence Rotation Mode
01Compressor #1 Priority Default Setting is: FILO
Default Setting is: 1 01Compressor #1 Priority
02Compressor #2 Priority Default Setting is: 1
OFF
Default Setting is: 1 02Compressor #2 Priority
03Compressor #3 Priority ON Default Setting is: 1
Default Setting is: 1 03Compressor #3 Priority
04Compressor #4 Priority Default Setting is: 1
Default Setting is: 1 04Compressor #4 Priority
Default Setting is: 1
TABLE #2
Pressure Schedule
T02
P01
PHHigh Pressure Setpoint
Default Setting is: 102 PSI 01Schedule Setting #1
PLLow Pressure Setpoint Default Setting is: -. - - : - - - - -
Default Setting is: 98 PSI to
PmMinimum Pressure Alarm 28Schedule Setting #28
Default Setting is: 0 PSI Default Setting is: -. - - : - - - - -
SQSequence Rotation Mode
Default Setting is: FILO
01Compressor #1 Priority
Default Setting is: 1
02Compressor #2 Priority
Default Setting is: 1
03Compressor #3 Priority
Default Setting is: 1
04Compressor #4 Priority
Default Setting is: 1
51
Pre-fill Configuration
P02 S02
PFPre-fill Function P>Pressure Units
Default Setting is: X Default Setting is: PSI
PTPre-fill Time NCNumber Of Compressors
Default Setting is: - MIN Default Setting is: 4
PPPre-fill Pressure PMMaximum Pressure Alarm
Default Setting is: 0 PSI Default Setting is: 145 PSI
01Compressor #1 CFStop Control Function
Default Setting is: X Default Setting is: X
02Compressor #2 TOTolerance
Default Setting is: X Default Setting is: 3.0 PSI
03Compressor #3 DADamping
Default Setting is: X Default Setting is: 1.0
04Compressor #4 PCPressure Change Time
Default Setting is: X Default Setting is: 4 MIN
AIAuxiliary Input Function
Default Setting is: 05:SS NO
User Configuration
AOAuxiliary Output Function
S01 Default Setting is: 07 ON NO
ERError Log Reset
CtReal Time Clock Set
Default Setting is: X
Default Setting is: -. - - : - -
PSPressure Schedule Enable
Default Setting is: X
ARAuto Restart Enable Sensor Calibration
52
Compressor Running Hours
C01
Compressor Configuration
C02
01Compressor #1 Configuration
Default Setting is: IR-PCB
02Compressor #2 Configuration
Default Setting is: IR-PCB
03Compressor #3 Configuration
Default Setting is: IR-PCB
04Compressor #4 Configuration
Default Setting is: IR-PCB
53
SECTION 10 — DIAGNOSTIC FUNCTIONS IN THE X04
CONTROLLER
In order to understand and utilize the functionality provided on the D01 the signals can then be used to understand the information displayed o
diagnostics tab, you must first know how to troubleshoot the control the D01 diagnostic screen in the X4I.
signals between the X4I and the ir-PCB interface. The troubleshooting of
ir-PCB ir-PCB
C03 C03
V 1 2 3 4 5 6 C05 V 1 2 3 4 5 6 C05
V1 1 2 3 4 5 6 V1 1 2 3 4 5 6
Wire Connections for IR-PCB Mode Wire Connections for IRV-PCB Mode
6core, earth shielded, cable (330 ft max) 7core, earth shielded, cable (330 ft max)
C01
ir-PCB
LED 5
RUN
C03
LED 4
READY
V 1 2 3 4 5 6
LED 2
X03-3 (GND) is 0Vac and 0VDC common. GND is also The ‘ir-PCB’ provides 3kV opto-coupled isolation between
connected to ‘earth’ on the X4I Terminal PCB (this is not a compressor circuit pressure regulation and monitoring
‘Safety Earth’ connection and is used for “control” only). inputs (X01, X02 and X04) and the low voltage connections
to the X4I (X03).
54
‘IR-PCB’ PRESSURE REGULATION CONTROL INPUTS
LOAD INPUT DIAGNOSTIC INDICATOR
On connector C03, the following connections provide the
control to the compressor from the X4I to the ir-PCB.
V 1 2 3 C 03 + 24Vac
L O AD
0Vac
V 1 2 3 0Vac
LED 2
GND
LO A D
24Vac
0Vac
GND
C 03
V S E Q LO A D
24Vac When the X4I initiates a Load command to the compressor,
the controller will send a signal to the Load input (2) on the
ir-PCB. Its associated diagnostic LED 2 will be on indicating
VFD INPUT CONTROL DIAGNOSTIC INDICATOR the presence of 24Vac.
LED 5
On connector C03, the following connections provide the
0Vac
GND
status of the compressor from the ir-PCB to the X4I.
VFD
24Vac
3 4 5 6
When the X4I is set up for in VFD mode (IRV-PCB), the
controller will send a signal to the VFD input (V) on the ir-
PCB. Its associated diagnostic LED 5 will be on indicating C 03 0V D C +24 V D C
GND
12-250Vac
V 1 2 3 C 03 + 24Vac or D C
SEQ +V
0Vac R E AD Y
C 04 0V
LED 1
0Vac
LED 4
GND
SEQ A LA R M RUN READY
(W arning)
24Vac
When the X4I places a compressor into Sequence control, When the compressor is “on” and “ready” to be sequenced,
the controller will send a signal to the SEQ input (1) on the there will be voltage present on the Ready connection on
ir-PCB. Its associated diagnostic LED 1 will be on indicating C04. Its associated diagnostic LED 4 will be on indicating
the presence of 24Vac. the presence of the signal.
12-250Vac
+V
C 04 RUN
0V
LED 3
A LA R M RUN READY
(W arning)
55
STATUS SIGNALS
12-250 V ac
12-250V ac or DC
Po la r ity is n o t Po la r ity is n o t
im p o r ta n t im p o r ta n t
+V 12-250Vac
12-250Vac or D C
READY
0V
Load Enable
Load/Unload
VFD /Fixed
+ VDC
NO C NC NO C NC A larm R un R eady
OU T IN +Vac
C02 C04 RUN
C01 0V ac C 04
+V D C
ir-PC B +24 V D C +V R un R ead y
P u lse 5 0 /6 0 H z
C03
+24V D C
X 01
R ead y/R un
V 1 2 3 4 5 6 D2 D2 D i2 D2
0V D C X 03
0V D C 0V D C
C 05 GND GND
X 4I ir-P C B
0V DC
D2
When the Ready and Run signals are present on C04, they Note: RUN input 12-250V’ac’ only. The ‘ac’ frequency is
can be monitored on connection C03 terminal 5 (D2). used to create the pulsing on the ‘D2’ (C03-3) output.
Referring to the above graph, the signal (wave form) seen Note: If measured with a ‘typical’ DC voltage meter the
on D2 is shown. ‘pulsing’ will appear as 10VDC (+-3V)
12-250V ac
or DC
Po la r ity is n o t
im p o r ta n t
12 - 250Vac
or D C
+V
ALARM
0V
VFD /Fixed
Load Enable
Load/U nlo ad
+VD C
N O C N C N OC N C A larm R un R eady
O UT IN
C02 C04
S ervice +24 V D C C 04
M ain ten an ce
C01
A larm
ir-PC B 10k A larm /S erv. D1
D i6
C03 P u lse 5 0 /6 0 H z
V 1 2 3 4 5 6 +24V D C X 01 X 03
D1 D2 0V D C 0V D C
0VD C GND GND
C0 5
X 4I ir-P C B
0V DC Se rv ic e
D1 M a int e na nc e
When the Alarm or Service Maintenance signals are present In addition, if the ‘D1’ wire connection from the X4I to the
on C04 or C05, they can be monitored on connection C03 ‘ir-PCB’ is not connected the ‘D2’ output on the ‘ir-PCB’ pin
terminal 5 (D1). Referring to the above graph, the signal will always measure 0VDC (no pull-up resistor connected).
(wave form) seen on D1 is shown.
A Service/Maintenance signal (pulsing) will mask any Alarm
Pulses are generated by the ‘ir-PCB’ itself for the Service/ (Warning) signal. This is not an issue because the X4I will
Maintenance ‘D1’ (C03-5) Signal. ignore any compressor Alarm (Warning) or Trip (Shutdown)
conditions in Service/Maintenance mode.
Notice that the 10k pull-up resistor on the X4I Terminal PCB
will hold the ‘D1’ signal at +24VDC. The Signal will go to Note: If measured with a ‘typical’ DC voltage meter the
0VDC when there is an Alarm (Warning) input on the ‘ir- ‘pulsing’ will appear as 10VDC (+-3V)
PCB’. This functions in reverse to the way the ‘D2’ Ready/
Run signal, from the ‘ir-PCB’ to the X4I functions.
56
DETERMINING TERMINAL PCB TO CONTROLLER I/O CONNECTIONS FROM THE X4I WIRING
DIAGRAM FOR USE WITH THE CONTROLLER DIAGNOSTIC TEST FUNCTIONS
C015
C+ C019 C016
1 C020 C017
X01 C03
Di2 2 C021 C018
ir- PCB X04 3 C022
C019 10k 6 + +20VDC 6
Ready/Run 4 C023
C020 C021 5 Di2 Ready/Run 5
5 C024
C025 4 Di6 Alarm/Serv 4 ir-PCB 1
C021
6 C025
C022
3 - .GND 3
7 C026
C015 2 R2 LOAD 2
C023
8 C027
1 1
C024 R1 SEQ
V1 V
C025 V1 VFD
X04-3
(C2)
Di2
ir- PCB 1
Ready/Run
Terminal PCB
COMPRESSOR #1 DIAGNOSTICS
• To view ‘ir-PCB’ #1 Ready/Run input in the controller’s Diagnostic menu select digital input ‘D2’ (Di2)
• To view ‘ir-PCB’ #1 Alarm/Serv input in the controller’s Diagnostic menu select digital input ‘D6’ (Di6)
COMPRESSOR #2 DIAGNOSTICS
• To view ‘ir-PCB’ #2 Ready/Run input in the controller’s Diagnostic menu select digital input ‘D3’ (Di3)
• To view ‘ir-PCB’ #2 Alarm/Serv input in the controller’s Diagnostic menu select digital input ‘D7’ (Di7)
COMPRESSOR #3 DIAGNOSTICS
• To view ‘ir-PCB’ #3 Ready/Run input in the controller’s Diagnostic menu select digital input ‘D4’ (Di4)
• To view ‘ir-PCB’ #3 Alarm/Serv input in the controller’s Diagnostic menu select digital input ‘D8’ (Di8)
COMPRESSOR #4 DIAGNOSTICS
• To view ‘ir-PCB’ #4 Ready/Run input in the controller’s Diagnostic menu select digital input ‘D5’ (Di5)
• To view ‘ir-PCB’ #4 Alarm/Serv input in the controller’s Diagnostic menu select digital input ‘A2’ (Ai2)
57
DIGITAL (SWITCHING) INPUT EXCEPTIONS
• ‘ir-PCB’ #4: The ‘Alarm/Service Note: A digital (switching) conditioning circuit is not
Maintenance’ digital input (X04-22) is employed on analog input 2 (‘ir-PCB’ #4 Alarm/Service
monitored by a DC voltage ‘Analogue’ Maintenance) because this input has a ‘pulsing’ state that
input (A2) on the unit’s controller. The the digital (switching) conditioning circuit is unable to
Terminal PCB has a 2x150k resistor and detect correctly; hence the DC voltage level detection to
capacitor circuit to condition the signal pick-up the ‘pulsing’ state.
from the ‘ir-PCB’. View analogue input ‘A2’
in the controller’s Diagnostic menu.
• Auxiliary Digital Input 1 (X07) is monitored
by ‘Analog’ input (A3) on the unit’s
controller. The analogue input has been
fitted with a digital (switching) conditioning
circuit and has the same characteristics as
a normal ‘Digital’ input. View analogue
input ‘A3’ in the controller’s Diagnostic
menu.
58
SECTION 11 — FAULT CODES
In the event of a unit or system “fault” the X4I will display a The alarm (warning) symbol will alternate with the normal
fault code. The fault code becomes an item in the user compressor status symbol every two seconds.
operational display menu. If more than one “active” fault
occurs, each will be displayed as a separate item in the
operational user menu. Press UP or DOWN to view all active
fault codes or to view the normal status display. NOT AVAILABLE
The compressor is reporting a general or group trip
Alarm (Warning) (shutdown) condition. The compressor has been stopped
and taken out of service, power to the compressor has been
isolated/lost or the compressor is not communicating.
Shutdown (Trip)
• The ready input of the “ir-PCB” is no longer
Fault codes are separated into unit faults (ERR) and system active.
alarms (warning) (SYS).
• The run input of the “ir-PCB” is no longer
Each fault type has a unique numeric code. active while the compressor is being
requested to run loaded.
ERR.01 Pressure Sensor • The run input of the “ir-PCB” did not
activate within 60 seconds of a load
request.
ERR.04 Internal 24V Fault
• The compressor is reporting a general or
group shutdown or stopped condition
ERR.05 Emergency Stop (RS485 network connectivity only).
• The remote compressor interface unit is in
ERR.06 Real Time Clock Error a shutdown condition (RS485 network
connectivity only).
SYS.01 Excess Pressure (PM) The X4I fault LED will “fast flash”.
The “not available” symbol will “slow flash”.
SYS.02 Min Pressure (Pm)
#
SYS.04 Insufficient Capacity COMPRESSOR INHIBITED, REMOVED FROM
SERVICE
Compressor fault states are displayed as part of the Set in the X4I active “table” (# = table number 1, 2 or 3) as
normal operational status display and do not generate fault inhibited from use.
codes. Examine the applicable compressor unit to establish
In this condition, the status of the compressor is still
the nature or description of the detected fault condition.
monitored. The X4I fault LED will not illuminate or flash
unless an actual alarm (warning) or trip (shutdown, not
X4I COMPRESSOR FAULT INDICATIONS, available) condition occurs.
TYPES, AND CODES: The two symbols will alternate every two seconds.
ALARM (WARNING)
• The Alarm input on the “ir-PCB” has been COMMUNICATIONS DISRUPTION
activated.
Network communications with the compressor have been
• The compressor, or remote compressor
interface unit, is reporting a general or disrupted/lost.
group alarm condition on the RS485
network (RS485 network connectivity only). Note: only applicable where the compressor is integrated
The X4I fault LED will “slow flash”. with the X4I using the RS485 communications network.
59
SPECIAL CONTROLLER FAULT CODES To view the second error information screen, press the
• E0836 PLL Unlock Internal failure or
excessively high external electrical ENTER button. To return to the main error log menu
interference
• E0866 Controller internal
power supply fault screen, press the ESCAPE button.
• E5000 Internal memory
map error E01 01.01
• E5001 Internal memory
failure 1 2 3 4
E01 01.01
E: ERR.01
16/05/2006 14:25
1
60
PARTS LIST
Item Part No. Description
- 39265889 X4I
2
- 80443617 Manual, User CD
1 39265897 Unit, Controller
2 39265913 Unit, XPM-TAC24
3 39265905 PCB, Terminal
4 38036703 Gland, Set - Pg11 3
5 39265921 Module, ir-PCB
6 39265939 Sensor, Pressure 1
4-20mA, 232psi (16bar) 4
5 i-PCB 6
20mm
IEC 5mm
61
TECHNICAL DATA Mounting Dimensions:
62
DIAGRAMS
Wiring Diagram
T 1-5 6-32 1 -R 6 -C G T erm in al P C B
33 34 35 36
C01
X08
C03
4-20m A
X 06
4
+VDC C03 C04
A i1 C04 C05
3
X 05
31 32
+VDC C05 C06
X07
C 031 A -G N D SEQ C08
2
A i2 C06 C07
GND C07
C 032 Ao
1
+VDC C07 C08
A i3 C08
27 28 29 30
C 010
C09
X06
C09
X 09
C 010
C+ C 019
SEQ
C 020 C 011
X 08
2 C 021
25 26
C 012 C04
X05
3 C 022
C 013
X 04
C03
L2 L1
4 C 023
C 014 C 019
5 C 024
+
-
V4 19 20 21 22 23 24
C 015 R -S E Q 10k
6 C 025
C 016 C 024
24 V ac
XPM 485
R S 485#2
GND
7 C 026
C 017
C 034 150k
C06
X04
8 C 027
C 018 150k
C 019 C 012
2 4V ac
C 020
C 011
SEQ
R5 C 021
X 02
C 012 C 022
C 023
C 0 1 /3
L2 L1 R S 485#1
C 024
R6
V3 13 14 15 16 17 18
1 0k
M ulti485
C 0 1 /4 C 025
X 07
C 023
GND
C 026 C 027
X03
C 013 C 027
C09 R1
C 014 C 028 C 018
C 010
R2 C 029
C 015
X 03
C 030
R3
C 016 C 033
9 10 11 12
1 0k
C 017 C 034
24V ac
C 022
R4
X 01
C 026
X02
C 018
2
1
C 031
8
-
C 016
0VDC
C 032 4 -20 m A
7
+
V2
C 029
C 028
R -V 4
6
R -V 3 1 0k
24 V ac
0V ac
C 021
5
R -V 2
C 025
X01
3 4
X 02
X P M -T A C 24
R -V 1
X03
2
C 015
2
1
1 2
2 4V ac
1
N
E
E
L
0 V a c - e a rth ed
V1
X 01
L N E
230V ac 1 0%
115V ac 1 0%
63
Connection Diagram
Terminal PCB
36
115V 'UL ' @ 5A maximum.
35 X08
34
33 Auxiliary Output #1
32 X07
31 Auxiliary Input #1
330ft (100m) max
30 L1
29 X06 L1
28 L2 Multi485 L2
27 L1
L2 330ft (100m) max
26 -
X05 - System
25
+ Ai1Pressure
+ +
24
+ +20VDC 6 4- 20mA
19
R5 LOAD 2
V4
R1 SEQ 1
4
V4 VFD V
IR- PCB 6- core
V
IRV- PCB 7-core
18
+ +20VDC 6 ir-PCB3
17
16 Di4 Ready/Run 5
X03
15 Di8 Alarm/Serv. 4
14
- GND 3 330ft (100m) max
13 R4 LOAD 2
R1 SEQ 1 3
V3
V V
V3 VFD IR- PCB 6- core
IRV- PCB 7-core
12
+ +20VDC 6
11 ir-PCB2
10
Di3 Ready/Run 5
X02
Di7 Alarm/Serv. 4
9 - GND 3 330ft (100m) max
8
R3 LOAD 2
7
V2
R1 SEQ 1
2
V2 VFD V IR- PCB 6- core
V
IRV- PCB 7-core
6 + +20VDC 6
5
Di2 Ready/Run 5 ir-PCB1
4 X01
3
Di6 Alarm/Serv. 4
2
- GND 3 330ft (100m)max
1
R2 LOAD 2
V1
R1 SEQ 1
1
V1 VFD V IR- PCB 6- core V
IRV- PCB 7-core
64
XPM-TAC24
Power Supply Module
83
89
6 12 mm
6
4 x 4.5mm
BLUE BLACK
BROWN ORANGE
RED WHITE
GREEN VIOLET
10 32
1 2 3 4
X04 1 2 3 4
230V
T3.15A
T1.6A
T1.6A
T1.0A
115V
115V +-10%
IEC T1.0A FH1
5x20mm
1 2 3 4
X03 X02
2 1 2
X01 12 mm
141 L N E E
147
24Vac/2 24Vac/1
earthed isolated L N E
65
X4I Commissioning Form
Customer Contact Customer Ref:
Comp #1 Manufacturer
Comp #1 Model/Type
psi cfm
Comp #1 Working Pressure psi/bar
#1 kW VA Hz
Comp #1 Full Load Capacity cfm
Comp #2 Manufacturer
cfm
Comp #2 Model/Type
psi
#2 kW VA Hz
Comp #2 Working Pressure psi/bar
Comp #2 Full Load Capacity cfm
Comp #3 Manufacturer
psi cfm Comp #3 Model/Type
#3 kW VA Hz Comp #3 Working Pressure psi/bar
Comp #3 Full Load Capacity cfm
Comp #4 Manufacturer
psi cfm Comp #4 Model/Type
#4 kW VA Hz Comp #4 Working Pressure psi/bar
Comp #4 Full Load Capacity cfm
66
S01 Ct Real Time Clock Set
S01 PS Pressure Schedule Enable
S01 AR Auto Restart Enable
S01 RP Rotation Interval or Time
S01 TS Default Table T01 T02 T03
67
Machine models represented in this manual may be used in various locations world-wide. Machines sold and
shipped into European Union Territories require that the machine display the EC Mark and conform to various
directives. In such cases, the design specification of this machine has been certified as complying with EC
directives. Any modification to any part is absolutely prohibited and would result in the CE Certification and marking
being rendered invalid. A declaration of that conformity follows:
we,
Represented in EC by:
declare that, under our sole responsibility for manufacture and supply,
the product(s)
X4I
to which this directive relates, is (are) in conformity with the provisions of the above directives using the following
principal standards.
H. Seddon