Professional Documents
Culture Documents
Price Quotation of Laboratory Building - Fire Detection, Protection, PA, Door 11.08.20
Price Quotation of Laboratory Building - Fire Detection, Protection, PA, Door 11.08.20
In Words:
INSTALLATION, TESTING, COMMISSIONING OF
N & PROTECTION SYSTEM FOR LABORATORY BUILDING
3,404,270.25 502,820.00
- -
10,901,666.50 6,199,794.00
- -
14,305,936.75 6,702,614.00
Total Amount in BDT
3,907,090.25
-
17,101,460.50
-
-
21,008,550.75
SUPPLY, INSTALLATION, TESTING, COMMISSIONING OF FIRE DETECTION & PROTECTION SYSTEM FOR LABO
Supply & Installation of Addressable type Fire Alarm Control Panel complete with
following basic options. Master Controller Assembly / CPU shall be suitable with port
to add Voice alarm system / Fire Fighter Telephone system / Printer / Remote
Annunciator etc. FACP must be comply with internationally accepted standard.
Control units for Fire -Protective Signaling Systems. Product shall be UL listed or FM
Approved with Graphic Software Computer-4G. FACP for per loop up to 225
Addressable Devices and 3 loops..
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply & Installation of Repeater Panel / Remote LCD Annunciator with the same
"look and feel" as the FACP operator interface. The Remote LCD Annunciator shall
use the same Primary Acknowledge, Silence, and Reset Keys, Status LEDs and LCD
Display as the FACP. Product shall be UL listed or FM Approved.
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply and installation of Addressable type Manual Call Station of red LEXAN, with
molded, raised-letter operating instructions of contrasting color. Station will
mechanically latch upon operation with a key common with the control units.
Product shall be UL listed or FM Approved.
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply & Installation of Addressable type Isolator / Fault Isolator Module shall be
used in the field wiring between the devices (contractor shall propose the quantity
and location in the system required) to detect & isolate the devices at the time short
cirtuit in SLC. The device shall be suitable to temperature range 0º to 50°C. Product
shall be UL listed or FM Approved.
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Brand: Cooper/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply & Installation of Addressable Relay/Control Module shall be used in the field
wiring to connect the conventional initiating devices with the Addressable FACP
interfaces to control/operate dampers, motors or similer appliances on receiving
signal from the FACP as when as required . Temperature range 0°C to 50°C. Product
shall be UL listed or FM Approved.
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply & Installation of Addressable Input Module shall be used in the field wiring to
connect the conventional initiating devices with the Addressable FACP interfaces to
control/operate dampers, motors or similer appliances on receiving signal from the
FACP as when as required . Temperature range 0°C to 50°C. Product shall be UL
listed or FM Approved.
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
This new version is designed to comply with SS 546:2009 Code of Practice for
Emergency Voice Communication System in Buildings. The following features
required by SS546:2009:
- audible alert signal at remote handsets for incoming calls
- facility for visual indicator on remote handsets mounted in noisy environment
- ability to initiate calls from the master handset to remote handsets
- signal to activate recording system when master handset is lifted.
Brand: Simplex/Honeywell/Siemens/NOHMI/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Fireman telephone outlet shall be concealed type mounted on wall suitable to adopt
mail socket of the fireman telephone jack. Front cover shall be S.S. plate.
Brand: Simplex/Honeywell/Siemens/NOHMI/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply & Installation of Evacuation light shall be used during fire or emergency at
power interruption to facilitate the occupants to evacuate the building safety. Light
shall be double fittings type, with reflector, battery operated, 100watt, 24V DC
power supply. Set shall be with auto charger, battery shall be good to provide power
for 30 minutes at least. installation of Evacuation/Exit Sign with light shall be at
located shown in the drawing and shall be as per recommendation of the
manufacturer.
Country of Origin: china or Eqv.
Supply & Installation of Fire proof two core multi standard PVC insulted, 2 hours fire
rated (FR) PVC sheathed cable of copper conductor of required size as per drawing &
design. Cable shall be complete with supply and return loop. The work shall be
complete with water grade PVC conduits, conduit bends, tees etc. complete as per
direction and standard. Cutting of wall, floor, roof etc. mending good the damage
shall be as per direction. All verticle cable work through conduit shall be runin duct,
necessary cutting(if any) shall be done as required in walls & all horizontal cable
work through PVC conduits shall be surface. Cable work shall be done as per
drawing and direction. The Authority shall supply required power up to panel, the
cable shall be able to with stand fire temperature 400°C for at least two hours.
Installation of Fire proof cable shall be as per recommendation of the manufacturer.
Approved type of PVC conduit shall be used.
Total Taka
CTION SYSTEM FOR LABORATORY BUILDING
MATERIAL SERVICE
TOTAL Breakdown Structure
Rate (BDT) Total Amount (BDT) Rate (BDT) Total Amount (BDT)
1656 19,872.00 -
7245 57,960.00 -
0 0 -
0 - -
0 - -
0 -
20.7 258,750.00 -
31.05 165,651.75 -
0 - -
0 - -
0 - -
0 - -
0 - -
0 - -
0 - 50,000.00 50,000.00
329940 329,940.00
22860 22,860.00
2700 148,500.00
3060 397,800.00
2880 1,088,640.00
3150 78,750.00
2880 72,000.00
2610 78,300.00
2070 51,750.00
2880 115,200.00
2610 15,660.00
124110 124,110.00
1440 17,280.00
6300 50,400.00
-
-
18 225,000.00
27 144,045.00
-
-
-
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
The PVA-20CSE is a call station extension for the PAVIRO system. The call
station has 20 customizable slection buttons. A maximum of five call station
extensions can be installed on one call station. Other
Properties: *
Two indicator lights (green/red) per button.
* Label with transparent covering.- the
label can be changed at anytime. * Can be used as a standing or desk/rack
flush mounted device. * Internal monitoring with error logging-
complying with all relevant national & international standards.
* Easy configuration - Use of the Configuration Wizard
or IRIS-Net software.
Brand: TOA/Bosch/Eqv
Origin: Japan/ Germany or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Features: #
MP3 playback from SD card and USB inputs. #
FM tuner with RDS, presets and digital control. #
Simultaneous operation of SD/USB-player and FM tuner. #
Seperate outputs foor digital source and FM tuner. #
Mains Power supply #
Voltage: 115-230/VAC, ±10%, 50/60 Hz #
Power Supply fuses: 230 VAC 0.63 AT/250 V
# 120 VAC 1.25 AT/250 V
# Power Consumption typical: 10W
# Max Power Consumption: 50 VA Tuner Frequency Range.
# Distortion: < 1%
# Channel Seperation (1 kHz): >40 dB
# Intermediate rejection: >70 dB
# Weight: Approx 3.6 kg
# Mounting Standalone: 19" rack.
# Color: Charcoal
# Operating temperature: -25°C +45°C to
# Storage temperature: -40°C to + 70°C
# Relative humidity: <90%
Brand: TOA/Bosch/Eqv
Origin: Japan/ Germany or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply & Installation of Addressable Input Module shall be used in the field
wiring to connect the conventional initiating devices with the Addressable
FACP interfaces to control/operate dampers, motors or similer appliances on
receiving signal from the FACP as when as required . Temperature range 0°C
to 50°C. Product shall be UL listed or FM Approved.
Brand: Simplex/Honeywell/Siemens/Bosch/Eqv.
Origin: UK/USA/Germany/EU/Japan/Italy or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Total T
OTECTION SYSTEM FOR LABORATORY BUILDING
MATERIAL SERVICE
TOTAL Breakdown Structure
Rate (BDT) Total Amount (BDT) Rate (BDT) Total Amount (BDT)
Total Taka 0 Total Taka 0
COSTING/SCHEDULE PRICE
Rate Total Amount
(BDT) (BDT)
SUPPLY, INSTALLATION, TESTING, COMMISSIONING OF FIRE DETECTION & PROTECTION SYSTEM FOR
LABORATORY BUILDING
MATERIAL SERVICE
Item No. Description of Item Qty. Unit Rate (BDT) Total Amount (BDT) Rate (BDT) Total Amount (BDT)
1.0 Fire Water Pump (Engine Driven): 1 Set 2,636,352.00 2,636,352.00 35,000.00 35,000.00
Supply & Installation of Diesel Engine Driven Fire Pump complete with all related &
essential accessories. The pump shall be designed & installed in accordance with
globally accepted international standard. Pumps shall be of the non-overloading,
volute type, centrifugal type end suction and vertical discharge connections in the
lower half of the casing, allowing removal of the rotating element without disturbing
the pipe connections and operating at not over 300 rpm. Pumps shall be selected foa
atotal efficiency of not less than 65% . Pump performance curves shall be submitted
for approval together with the pump technical data. The pump shall have a capacity
of handle 750 USGPM of water against a head of 90 Meter of water.
Each unit shall be tested and NFPA approved.
Product shall be UL listed or FM Approved.
Brand: AC Fire/Petterso/Aurora/Aturia/Lifeco/Eqv.
Origin: USA/UK/EU/JAPAN/Ireland/Canada/UAE or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
2.0 Fire Water Pump (Motor Driven): 1 Set 993,393.00 993,393.00 25,000.00 25,000.00
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
3.0 Jocky Pump (Pressure Maintenance Pump): 1 Set 131,445.00 131,445.00 5,000.00 5,000.00
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
4.1 Butterfly Valve, Gate Valve & Ball Valve: 13000 13,000.00
It shall be anti corrosive cast iron body flanged end type complete with companion
flanges, nut-bolt gasket etc above 80mm dia and below 80mm dia threaded.
Flexible joint shall be suitable to absorb shock and system hammering and to reduce
vibration transmission. Flexible joint shall be ss construction, flanged end type.
Supply, Installation & testing of Pressure Release valve of 100mm dia of cast
iron/brass body with adjustable knob to adjust set pressure for release excess
pressure from the system to safe the fire fighting system network to drain. The valve -
shall be installed at pump house in discharge header. The valve shall be suitable to
withstand pressure of 12kg/cm². Inlet/outlet shall be flanged/threaded end type.
-
4.7 Pressure Gauge 22 Nos. 2,645.00 58,190.00 1,500.00 33,000.00
Supply and installation of 100mm dia type -
Following to be Mentioned: -
a) Brand: -
b) Origin: -
c) Country of Manufacturing/Fabricating/Assembling: -
d) Port of Shipment: -
-
4.8 Pressure Switch 3 Nos. 10,350.00 31,050.00 500.00 1,500.00
Supply, installation and testing of pressure switch complete with sensing element,
enclosure material, 15 mm NPT pressure connection, direct mounting electrical -
connection, other material etc. accepted / approved by the consultant
-
4.9 Auto Air-Vent Valve 10 Nos. 11,500.00 115,000.00 750.00 7,500.00
Supply & installation of auto air vent valve of 1 inch (25mm) dia of 1" dia inlet BSP,
bronze made with rubber ball and seat. The valve shall be suitable to release air from
the fire hydrant pipes. Shall be suitable to withstand pressure upto 10kg/cm².
Zone control valves are designed to operate utilizing electrical service for actuation.
A sprinkler system must be capable of shut down after the fire has been controlled,
and for periodic maintenance and modification. Control valves can provide this
function. in the simplest system a single shut off valve may be located at the point
where the water supply enters the building. Set should complete with: Butterfly
Valve, Test & drain Valve and Water Flow Indicator and related all accessories.
Supply & installation of pressure reducing valve of 40mm and 65 mm dia, brass
body, screwed end type, shall be used with 40mm dia internal hydrant unit (where to
reduce high pressure is necessary). Valve body shall be made with hot pressed brass, -
seat of stainless steel ANSI304 shall be suitable for 80°C. Initial pressure shall be 15
bar, adjustable final pressure shall be 0.5bar (min), 7bar (max)
Supply and installation of cast Iron body double deaded pillar hydrant complete with
2 (two) nos. cast brass made controllable outlet of 65mm dia with female
instanteneous outlet, Inlet shall be 100mm dia flanged end. The hydrant shall be
suitable to withstand test pressure of 300 psi (minimum). Color of the unit shall be
red / approved by the manufacturer or as per code.
Country of Origin: Australia/USA/EU/Japan/Malaysia/ or their licensed
manufacturing units located globally.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
7.0 Fire Brigade Connection: 4 -way 1 Set 29,900.00 29,900.00 2,000.00 2,000.00
Supply and installation of 4 - way fire brigade connection complete in all respect
with all accessories. The unit shall have two Inlet connections of 2½" (63mm) male
instanteneous with non-return valve and having 6" dia (150mm) flanged type outlet
directly connected with stand pipe. It will have also one 25mm dia drain valve for
drainage of water, rubber blank cap and chain for protection. Outlet 150mm dia shall
be as per ANSI-B-16B-16.5B. Shall be suitable to withstand pressure of 20kg/cm².
Shall be manufactured according to BS standard & suitable for using with fire service
& civil defence department of Bangladesh.
Country of Origin: Australia/USA/EU/Japan/Malaysia/ or their licensed
manufacturing units located globally.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
9.0 Automatic Alarm Check Valve 1 Set 103,500.00 103,500.00 2,000.00 2,000.00
Supply, installation, testing & commissioning of 100mm dia alarm check valve
complete with retarded chamber, trim assemble, alarm gong, control, drain & test
valve as per manufacturer's specification. The valve shall be UL listed / FM approved
Origin: UK/USA/Equivalent.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
Supply & fixing the following capacities multi purpose ABC dry chemical powder
stored pressure type with manometer system fire extinguisher suitable for repeated
use complete with wall bracket, CO2 cartridge, easy refilling system etc. as per
sample accepted & approved by the consultant. Origin: China or Equivalent.
Wet chemical fire suppression system shall be complete with wer chemical storage
cylinder with discharge valve, wall bracket, mechanical control head, discharge
nozzle, remote control box, reset level assembly, SPDP micro switch, vent plug,
fusable link detector, EMT conduit, cable etc. complete in all respect.
Brand: Kiddle/SRI/Hygood/SFFECO/Unique/Equivalent
Country of origin: USA/Singapore/UAE/Malaysia/Equivalent
14.0 ABC Dry Powder (5 kg) for Lift Machine Room 3 Nos. - - -
a) 200 mm (8 inch) dia, wall thickness: 8.2mm 80 Rft. 2,185.00 174,800.00 721.60 57,728.00
b) 150 mm (6 inch) dia, wall thickness: 7.1mm 530 Rft. 1,403.00 743,590.00 656.00 347,680.00
c) 100 mm (4 inch) dia, wall thickness: 6.0mm 10 Rft. 828.00 8,280.00 590.00 5,900.00
d) 75mm (3 inch) dia, wall thickness: 5.5mm 667 Rft. 667.00 444,889.00 550.00 366,850.00
e) 65 mm (2½ inch) dia, wall thickness: 5.2mm 1715 Rft. 483.00 828,345.00 524.80 900,032.00
f) 50 mm (2 inch) dia, wall thickness: 3.9mm 900 Rft. 304.75 274,275.00 426.40 383,760.00
g) 40 mm (1½ inch) dia, wall thickness: 3.7mm 1000 Rft. 230.00 230,000.00 393.60 393,600.00
h) 32 mm (1.25 inch) dia, wall thickness: 3.6mm 1170 Rft. 218.50 255,645.00 360.80 422,136.00
i) 25 mm (1inch) dia, wall thickness: 3.4mm 7200 Rft. 138.00 993,600.00 295.20 2,125,440.00
j) 20 mm (3/4 inch) dia, wall thickness: 2.9mm 50 Rft. 97.75 4,887.50
k) 50 mm dia drain MS pipe (Origin: Bangladesh) 120 Rft. 304.75 36,570.00 426.40 51,168.00
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
16.0 Pump Controller Panels: 3 Set -
Supply, installation of fire & jockey pump control panel complete with MCCB / MCB /
magnetic contactor / on-off push switch / indication lamp for phase indication, run,
trip mode / ampere meter / volt meter / overload selector switch / phase failure
protection device / dry operation protection device / volt guard / connector block /
bus-bar / CT of rated capacity / ventilation fan / buzzer / cable lugs / and all other
accessories. The panel shall be well dressed in side for safety purpose and for looking
good. Products shall be UL/FM Listed
Origin: UK/USA//EU/Japan or Eqv.
Following to be Mentioned:
a) Brand:
b) Origin:
c) Country of Manufacturing/Fabricating/Assembling:
d) Port of Shipment:
After complete proper installation the system shall be tested, commissioned and
balanced of the system shall be done as per direction and recommendation of the
manufacturer and NFPA. Pipe work system shall be tested at 250 psi/15 bar pressure
for 24 hours without any leakage. All the individual items shall be tested seperately
upto the satisfaction of the Consultant/PD. After proper testing, commissioning and
balancing the system shall run for seven days upto the satisfaction of the owner.
Supply & Installation of Fire rated door complete with UL Listed/ FM approved panic bar. The
door shall be made with 1.5 mm thick sheet steel painted with approved red color over a coat of
primer. Thickness of leaf shall be 40mm and filled with fire proof/ resisting materials of minimum
two hours rated. Door size shall be 900mm (wide) X 2100mm (height).
MATERIAL SERVICE
TOTAL
Unit Rate (BDT) Total Amount (BDT) Rate (BDT) Total Amount (BDT)
Sqft
Breakdown Structure
Rate (BDT) Total Amount (BDT)
TIME & COST SCH
DESCRIPTION DURATION
PHASE-1
PHASE-2
PHASE-3
HANDOVER
TIME & COST SCHEDULE
MATERIAL SERVICE
PENSE
TOTAL