Electrical data Multi-turn actuators for open-close duty with

DC motors SA 07.1 – SA 16.1


Short-time duty S2 - 15 min, 220 V DC
Multi-turn actuator Motor
Type Speed Torque Nominal Current2) Starting Protective
Type Power Speed current1) approx. Imax. current Field current resistor
rpm max. Nm PN (kW) rpm IN (A) (A) IA (A) IF (A) RV (Ω)3)
4 FN00063-4-0.02 0.02 1,400 0.2 0.4 3.0 0.3 –
5.6 FN00063-4-0.02 0.02 1,400 0.2 0.4 3.0 0.3 –
8 FN00063-4-0.04 0.045 1,400 0.4 0.7 3.0 0.3 –
11 FN00063-4-0.04 0.045 1,400 0.4 0.7 3.0 0.3 –
16 FN00063-2-0.09 0.09 2,800 0.8 1.3 9.0 0.3 –
22 FN00063-2-0.09 0.09 2,800 0.8 1.4 9.0 0.3 –
SA 07.1 32 30 FN00071-4-0.18 0.18 1,400 1.2 1.8 7.0 0.3 –
45 FN00071-4-0.18 0.18 1,400 1.2 2.1 7.0 0.3 –
63 FN00071-2-0.37 0.37 2,800 2.2 2.8 19 0.4 –
90 FN00071-2-0.37 0.37 2,800 2.2 3.3 19 0.4 –
125 FN00071-2-0.37 0.37 2,800 2.2 4.2 19 0.4 –
180 FN00071-2-0.37 0.37 2,800 2.2 4.6 19 0.4 –
4 FN00063-4-0.04 0.045 1,400 0.4 0.6 3.0 0.3 –
5.6 FN00063-4-0.04 0.045 1,400 0.4 0.6 3.0 0.3 –
8 FN00063-4-0.12 0.12 1,400 0.8 1.1 3.0 0.3 –
11 FN00063-4-0.12 0.12 1,400 0.8 1.2 3.0 0.3 –
16 FN00063-2-0.25 0.25 2,800 1.6 2.1 9.0 0.3 –
22 60 FN00063-2-0.25 0.25 2,800 1.6 2.4 9.0 0.3 –
SA 07.5 32 FN00080-4-0.37 0.37 1,400 2.5 3.1 16 0.4 –
45 FN00080-4-0.37 0.37 1,400 2.5 3.8 16 0.4 –
63 FN00080-2-0.75 0.75 2,800 5.1 5.5 26 0.4 –
90 FN00080-2-0.75 0.75 2,800 5.1 6.8 26 0.4 –
125 FN00080-2-0.75 0.75 2,800 5.1 8.7 26 0.4 –
180 50 FN00080-2-0.75 0.75 2,800 5.1 9.8 26 0.4 –
4 FN00063-4-0.12 0.12 1,400 0.8 0.9 3.0 0.3 –
5.6 FN00063-4-0.12 0.12 1,400 0.8 1.2 3.0 0.3 –
8 FN00071-4-0.18 0.18 1,400 1.2 1.8 7.0 0.3 –
11 FN00071-4-0.18 0.18 1,400 1.2 2.2 7.0 0.3 –
16 FN00071-2-0.37 0.37 2,800 2.2 3.1 19 0.4 –
22 120 FN00071-2-0.37 0.37 2,800 2.2 4.2 19 0.4 –
SA 10.1 32 FN00090-4-0.55 0.55 1,400 4.2 6.0 23 0.3 9.8
45 FN00090-4-0.55 0.55 1,400 4.2 7.6 23 0.3 9.8
63 FN00090-2-1.10 1.1 2,800 7.6 10 27 0.3 6.5
90 FN00090-2-1.10 1.1 2,800 7.6 12 27 0.3 6.5
125 FN00090-2-1.10 1.1 2,800 7.6 15 27 0.3 6.5
180 100 FN00090-2-1.10 1.1 2,800 7.6 16 27 0.3 6.5
4 FN00080-8-0.18 0.18 700 1.9 3.4 6.0 0.4 –
5.6 FN00080-8-0.18 0.18 700 1.9 3.8 6.0 0.4 –
8 FN00080-4-0.37 0.37 1,400 2.5 4.4 16 0.4 –
11 FN00080-4-0.37 0.37 1,400 2.5 5.2 16 0.4 –
16 FN00080-2-0.75 0.75 2,800 5.1 7.6 26 0.4 –
22 250 FN00080-2-0.75 0.75 2,800 5.1 8.4 26 0.4 –
SA 14.1 32 FN00100-4-1.50 1.5 1,400 9.3 12 22 1.4 5.9
45 FN00100-4-1.50 1.5 1,400 9.3 14 22 1.4 5.9
63 FN00100-2-3.00 3.0 2,800 19 22 49 1.4 4.1
90 FN00100-2-3.00 3.0 2,800 19 26 49 1.4 4.1
125 FN00100-2-3.00 3.0 2,800 19 34 49 1.4 4.1
180 200 FN00100-2-3.00 3.0 2,800 19 34 49 1.4 4.1
4 FN00090-8-0.37 0.37 700 2.6 4.4 10 0.5 14.4
5.6 FN00090-8-0.37 0.37 700 2.6 4.8 10 0.5 14.4
8 FN00090-4-0.75 0.75 1,400 5.1 7.9 23 0.5 9.8
11 FN00090-4-0.75 0.75 1,400 5.1 8.8 23 0.5 9.8
SA 14.5 16 500 FN00090-2-1.50 1.5 2,800 9.3 13 27 0.5 6.5
22 FN00090-2-1.50 1.5 2,800 9.3 15 27 0.5 6.5
32 FN00112-4-3.00 3.0 1,400 19 21 29 1.1 2.7
45 FN00112-4-3.00 3.0 1,400 19 25 29 1.1 2.7
4 FN00100-8-0.75 0.75 700 4.9 8.0 13 1.3 7.9
5.6 FN00100-8-0.75 0.75 700 4.9 8.6 13 1.3 7.9
8 FN00100-4-1.50 1.5 1,400 9.3 14 22 1.3 5.9
SA 16.1 11 1,000 FN00100-4-1.50 1.5 1,400 9.3 15 22 1.3 5.9
16 FN00100-2-3.00 3.0 2,800 19 25 49 1.4 4.1
22 FN00100-2-3.00 3.0 2,800 19 29 49 1.4 4.1
All DC motors for 110 V DC and 220 V DC are designed as shunt motors.
DC motors are generally designed without motor protection since the motor heats up within the rotor and not within the field
windings.
Motor data are approximate. Due to usual manufacturing tolerances, there may be deviations from the values given.
For notes on the threads of the cable entries as well as other information, refer to “Technical data Multi-turn actuators for
open-close duty with DC motors”.
1) Current at running torque according to “Technical data SA 07.1 – SA 16.1".
2) Current at max. torque. We recommend to select switching devices accoding to these values.
3) The recommended protective resistors are not included in the scope of supply of the DC motors.
We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.
Page 1 of 1

Issue 1.07
Y000.530/002/en