Title: Ethics Year & 3rd-C Date: October 13, 2020 Section:
Presidential Decree No. 1096
National Building Code of the Philippines Summary of Chapters XI-XIII
Chapters XI deals with protection of pedestrians during construction or demotion,
Chapter XII provides detailed elaboration on general design and construction requirements and Chapter XIII states electrical and mechanical regulations in relation to construction. These chapters under the National Building Code of the Philippines noticeably imposes standards and requirements on building design and construction to protect the welfare of persons involved like pedestrians and human habitants. Stated under general provisions of Chapter XI of the NBCP, first is that no person is permitted to use or occupy a street, alley or public sidewalk for the performance of work covered by a building permit. To further protect pedestrians, no person is also allowed to perform any work on any building or structure adjacent to a public way that is in general use for travelling pedestrians. Adequate lighting between sunset and sunrise is also required to any material or structure temporarily occupying public property like fence, canopies and walkways. In storage in public property, materials and equipment necessary for work when placed on public property must not obstruct free and convenient approach as well as not interfere with any drainage of any street or alley gutter. Mixing of mortar, concrete or similar materials is not allowed in public streets. All public and private utilities above or below ground is required to be protected from damage by any work being done. A temporary walkway of minimum 1.20 meters wide must be provided in case there is no sidewalk in front of the building site during construction or demolition. Walkways also need to be capable of supporting a uniform live load of 650 kilograms per square meter. With regards to protection required, pedestrian traffic is necessitated to be protected by a railing on the street side when walkway extends into the roadway and when adjacent to excavation. Protective devices should also be properly maintained in place and kept in good order for the entire length of time when pedestrians may be endangered. As for removal of protective devices, every protective fence or canopy should be removed within 30 days after protection is no longer required. Demolishing any building should also not be started unless all necessary pedestrian protective structures are in place. To state in general the lengthy yet in depth provisions of Chapter XII entitled General Design and Construction Requirements, buildings to be constructed is required to comply with all the regulations and specification mandated in the provisions under this chapter with consideration on quality, characteristics and properties of materials, methods of design and construction, type of occupation and lastly, is the classification. Matters regarding structural design of all buildings and other structures should conform to the provisions of the National Structural Code of Buildings in pursuant to the amended Republic Act No. 544 or the Civil Engineering Law. As per the provisions of the NBCP regarding the construction of footings and foundations, these structural components is necessitated to be of the appropriate type, adequate size and capacity to safely sustain the superimposed loads under seismic or any condition of external forces that may affect the safety or stability of the structure. The architect and engineer’s responsibility here is to adopt the type and design of the same in accordance with the standards imposed by the Secretary. On the other hand, provisions on retaining walls state that this structural component must be provided with adequate design and type of construction whenever or wherever there exist in the site of the construction an abrupt change in the ground levels of level of the foundation such that instability of the soil could result. NBCP provided many requirements on excavation works. Some of the key requirements is that before undertaking excavation works, drilling or disturbing the ground, the people causing such work to be done is needed to contact all public utilities or services to determine possible location of underground facilities to avoid hazard to public safety, health and welfare. Any person making an excavation below existing grade should also protect the excavation in order for the soil of adjoining property will not result to cave-in or settle and thereby defraying the cost of underpinning or extending the foundation of buildings on adjoining properties. Still under the section for general design and construction requirements, standard automatic fire-extinguishing systems should be installed in the following: (1) in every storey, basement or cellar with a minimum area of 200 sq. meters which is used for habitation, recreation, dining, study, or work which has an occupant load of more than 20; (2) in all dressing rooms, rehearsal rooms, workshops or factories, and other rooms with an occupant load of more than 10, assembly halls under Groups H and I Occupancies with occupant load of more than 500, and if next doors of given rooms are more than 30 meters from the nearest safe fire dispersal area of building or opening to an exit court or street, and; (3) in all rooms used for storage or handling of photographic x-ray nitrocellulose films and other inflammable articles. Minimum requirements for chimneys, fireplaces and barbecues are also discussed in chapter XII. Chimneys in wood-framed buildings should be anchored laterally at the ceiling line and at each floor line which is more than 1.80 meters above grade. Masonry chimneys for residential type appliances must be constructed of masonry units or reinforced concrete with walls with minimum thickness of 100 millimeters or of rubble stone masonry with minimum thickness of 300 millimeters. Masonry chimneys for low, medium and high-heat appliances should be addressed with construction of masonry units, solid masonry units and double walls of solid masonry units of reinforced concrete with minimum thickness of 200 mm except that for high-heat appliances with a minimum air space of 50 mm between walls. Every masonry chimney is required to extend at least 600 mm above the part of the roof through which it passes and at least 600 mm above the highest elevation of any part of a building within 3 meters to the chimney. Fireplace walls should set to be in minimum thickness of 200 mm, walls of fireboxes with minimum thickness of 250 mm, firebox with minimum depth of 500 mm, and maximum thickness of joints in firebrick should be 10 mm. Metal hoods used as part of a fireplace or barbecue shall be in a minimum of No. 18 gauge copper, galvanized iron, or other equivalent corrosion-resistant ferrous metal. For smoke chamber, front and side wall must be in a minimum thickness of 200 mm and smoke chamber back walls with minimum 150 mm. Walls of chimneys without flue lining must be in a minimum thickness of 100 mm, combustible materials must be placed not within 50 mm of fireplace, smoke chamber or chimney walls. To discuss the minimum requirements for penthouses and roof structures, no penthouse or other projection above the roof in structures of other than Type V construction should exceed 8.40 meters above the roof when used as an enclosure for tanks or for elevators which run to the and in all other cases should not extent beyond 3.60 meters in height with the roof. The aggregate area of all penthouses and other roof structures should only have a maximum thickness of 1/3 of the area of the supporting roof. On Types III and IV constructions, the exterior walls and roofs of penthouses which are 1.50 m or more from an adjacent property line may be of one-hour fire-resistive incombustible construction. Walls with minimum 1.50 m from an exterior wall of a Type IV construction may be of one-hour fire-resistive incombustible construction. Lastly, Chapter XIII deals with electrical and mechanical regulations. All electrical and mechanical systems, equipment and installations is mandated to conform to the provisions of the Philippine Electrical and Mechanical Engineering Codes. With regards to the provision of the NBCP on clearance of service drops as electrical regulations, service drop conductors should not be readily accessible. When not in excess of 600 volts, conductors must have a minimum clearance of 2.50 meters from the highest point of roofs over which they pass. Conductors are also necessitated to have a minimum clearance of 3 m from the ground or from any platform or projection from which they might be reached. Conductors should also have a horizontal minimum clearance of 1 m from windows, doors, porches, fire escapes, or similar locations and should be run less than 1 m above the top level of a window or opening. Also, service drop of conductors, when crossing a street, is needed to have a minimum clearance of 5.50 m from the crown of the street or sidewalk over which it passes, and should have a minimum clearance of 3.00 m above ground at its point of attachment to the building or pedestal.