You are on page 1of 8

PT.

PRIMA TUNGGAL JAVALAND


KOMPLEK RUKO MUTIARA BLOK A6 No 23-25 Jl KAMAL RAYA
OUTER RING ROAD CENGKARENG JAKARTA 11730 INDONESIA

HYDRAULIC CALCULATIONS

FOR

PT. MEINDO ELANG INDAH


IPP JAWA1 PROJECT PROJECT
SPRINKLER SYSTEM

DATE: DEC 14, 2020

-DESIGN DATA-

OCCUPANCY CLASSIFICATION: ORDINARY HAZARD


NFPA-13

DESIGN DENSITY: 6.1 lpm/sq.m (0.15 gpm/ft2)

SPRINKLER K-FACTOR: 80.6 lpm/bar-1/2

MINIMUM SPRINKLER PRESSURE: 1.4 bar

NUMBER OF SPRINKLER CALCULATED: 6 Sprinklers

TOTAL WATER FLOW REQUIRED: 624.9 lpm

TOTAL WATER REQUIRED: 625.0 lpm

FLOW AND PRESSURE (@ BAR): 624.9 lpm @ 2.53 bar

SPRINKLER ORIFICE SIZE: 15 mm

NAME OF CONTRACTOR: PT. PRIMA TUNGGAL JAVALAND

DESIGN/LAYOUT BY:
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 12/14/2020 E:\NS\MEI\CABLE AREA_4 INCH_01.SDF
JOB TITLE:

WATER SUPPLY DATA

SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D


NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (BAR) (BAR) (LPM) (BAR) (LPM) (BAR)

31 (N/A) 0.00 (N/A) 0.000 625.0 2.527

AGGREGATE FLOW ANALYSIS:

TOTAL FLOW AT SOURCE 625.0 LPM


TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 LPM
OTHER HOSE STREAM ALLOWANCES 0.0 LPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 625.0 LPM

NODE ANALYSIS DATA


NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(M) (BAR) (L/MIN)

1 2.48 K=80.60 1.400 95.4


2 2.58 - - - - 1.464 - - -
3 2.58 - - - - 1.640 - - -
4 2.58 - - - - 1.658 - - -
5 2.48 K=80.60 1.514 99.2
6 2.58 - - - - 1.724 - - -
7 2.50 - - - - 1.759 - - -
8 2.50 - - - - 1.791 - - -
9 2.50 - - - - 1.805 - - -
10 2.58 K=80.60 1.797 108.0
11 2.58 - - - - 1.784 - - -
12 2.48 - - - - 1.794 - - -
13 2.58 K=80.60 1.745 106.5
14 2.58 - - - - 1.745 - - -
15 2.48 - - - - 1.755 - - -
16 2.50 - - - - 1.926 - - -
17 2.50 - - - - 1.896 - - -
18 2.50 K=80.60 1.888 110.8
19 2.58 - - - - 1.872 - - -
20 2.58 - - - - 1.859 - - -
21 2.48 K=80.60 1.698 105.0
22 2.58 - - - - 1.859 - - -
23 2.58 - - - - 1.859 - - -
24 2.48 - - - - 1.869 - - -
25 2.50 - - - - 2.217 - - -
26 2.30 - - - - 2.329 - - -
27 1.97 - - - - 2.362 - - -
28 1.65 - - - - 2.394 - - -
29 1.15 - - - - 2.457 - - -
30 0.60 - - - - 2.519 - - -
31 0.60 SOURCE 2.527 625.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 12/14/2020 E:\NS\MEI\CABLE AREA_4 INCH_01.SDF
JOB TITLE:

PIPE DATA

PIPE TAG Q(LPM) DIA(MM) LENGTH PRESS.


END ELEV. NOZ. PT DISC. VEL(MPS) HW(C) (M) SUM.
NODES (M) (K) (BAR) (LPM) FL/M (BAR)

Pipe: 1 -95.4 15.00 PL 0.10 PF 0.074


1 2.48 80.6 1.400 95.4 8.99 120 FTG ---- PE-0.010
2 2.58 0.0 1.464 0.0 0.7404 TL 0.10 PV

Pipe: 2 -95.4 15.00 PL 0.20 PF 0.176


2 2.58 0.0 1.464 0.0 8.99 120 FTG E PE 0.000
3 2.58 0.0 1.640 0.0 0.7404 TL 0.24 PV

Pipe: 3 -95.4 40.89 PL 3.20 PF 0.018


3 2.58 0.0 1.640 0.0 1.21 120 FTG ---- PE 0.000
4 2.58 0.0 1.658 0.0 0.0056 TL 3.20 PV

Pipe: 4 99.2 15.00 PL 0.10 PF 0.153


4 2.58 0.0 1.658 0.0 9.35 120 FTG N PE 0.010
5 2.48 80.6 1.514 99.2 0.7961 TL 0.19 PV

Pipe: 5 -194.6 40.89 PL 0.70 PF 0.066


4 2.58 0.0 1.658 0.0 2.47 120 FTG N PE 0.000
6 2.58 0.0 1.724 0.0 0.0209 TL 3.14 PV

Pipe: 6 -194.6 40.89 PL 0.08 PF 0.027


6 2.58 0.0 1.724 0.0 2.47 120 FTG E PE 0.008
7 2.50 0.0 1.759 0.0 0.0209 TL 1.30 PV

Pipe: 7 -194.6 40.89 PL 0.30 PF 0.032


7 2.50 0.0 1.759 0.0 2.47 120 FTG E PE 0.000
8 2.50 0.0 1.791 0.0 0.0209 TL 1.52 PV

Pipe: 8 -194.6 52.50 PL 2.40 PF 0.015


8 2.50 0.0 1.791 0.0 1.50 120 FTG ---- PE 0.000
9 2.50 0.0 1.805 0.0 0.0062 TL 2.40 PV

Pipe: 9 214.5 52.50 PL 0.08 PF 0.001


9 2.50 0.0 1.805 0.0 1.65 120 FTG N PE-0.008
10 2.58 80.6 1.797 108.0 0.0074 TL 0.08 PV

Pipe: 10 106.5 40.89 PL 0.70 PF 0.013


10 2.58 80.6 1.797 108.0 1.35 120 FTG E PE 0.000
11 2.58 0.0 1.784 0.0 0.0069 TL 1.92 PV

Pipe: 11 0.0 15.00 PL 0.10 PF 0.000


11 2.58 0.0 1.784 0.0 0.00 120 FTG N PE 0.010
12 2.48 0.0 1.794 0.0 0.0000 TL 0.19 PV

Pipe: 12 106.5 40.89 PL 3.20 PF 0.039


11 2.58 0.0 1.784 0.0 1.35 120 FTG N PE 0.000
13 2.58 80.6 1.745 106.5 0.0069 TL 5.64 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 12/14/2020 E:\NS\MEI\CABLE AREA_4 INCH_01.SDF
JOB TITLE:

PIPE TAG Q(LPM) DIA(MM) LENGTH PRESS.


END ELEV. NOZ. PT DISC. VEL(MPS) HW(C) (M) SUM.
NODES (M) (K) (BAR) (LPM) FL/M (BAR)

Pipe: 13 0.0 15.00 PL 0.20 PF 0.000


13 2.58 80.6 1.745 106.5 0.00 120 FTG ---- PE 0.000
14 2.58 0.0 1.745 0.0 0.0000 TL 0.20 PV

Pipe: 14 0.0 15.00 PL 0.10 PF 0.000


14 2.58 0.0 1.745 0.0 0.00 120 FTG E PE 0.010
15 2.48 0.0 1.755 0.0 0.0000 TL 0.14 PV

Pipe: 15 -409.1 52.50 PL 1.85 PF 0.120


9 2.50 0.0 1.805 0.0 3.15 120 FTG N PE 0.000
16 2.50 0.0 1.926 0.0 0.0245 TL 4.90 PV

Pipe: 16 215.8 52.50 PL 0.90 PF 0.030


16 2.50 0.0 1.926 0.0 1.66 120 FTG T PE 0.000
17 2.50 0.0 1.896 0.0 0.0075 TL 3.95 PV

Pipe: 17 215.8 40.89 PL 0.30 PF 0.008


17 2.50 0.0 1.896 0.0 2.74 120 FTG ---- PE 0.000
18 2.50 80.6 1.888 110.8 0.0254 TL 0.30 PV

Pipe: 18 105.0 40.89 PL 0.08 PF 0.009


18 2.50 80.6 1.888 110.8 1.33 120 FTG E PE-0.008
19 2.58 0.0 1.872 0.0 0.0067 TL 1.30 PV

Pipe: 19 105.0 40.89 PL 0.70 PF 0.013


19 2.58 0.0 1.872 0.0 1.33 120 FTG E PE 0.000
20 2.58 0.0 1.859 0.0 0.0067 TL 1.92 PV

Pipe: 20 105.0 15.00 PL 0.10 PF 0.171


20 2.58 0.0 1.859 0.0 9.91 120 FTG N PE 0.010
21 2.48 80.6 1.698 105.0 0.8851 TL 0.19 PV

Pipe: 21 0.0 40.89 PL 3.20 PF 0.000


20 2.58 0.0 1.859 0.0 0.00 120 FTG N PE 0.000
22 2.58 0.0 1.859 0.0 0.0000 TL 5.64 PV

Pipe: 22 0.0 15.00 PL 0.20 PF 0.000


22 2.58 0.0 1.859 0.0 0.00 120 FTG ---- PE 0.000
23 2.58 0.0 1.859 0.0 0.0000 TL 0.20 PV

Pipe: 23 0.0 15.00 PL 0.10 PF 0.000


23 2.58 0.0 1.859 0.0 0.00 120 FTG E PE 0.010
24 2.48 0.0 1.869 0.0 0.0000 TL 0.14 PV

Pipe: 24 -624.9 52.50 PL 2.37 PF 0.291


16 2.50 0.0 1.926 0.0 4.81 120 FTG T PE 0.000
25 2.50 0.0 2.217 0.0 0.0537 TL 5.42 PV

Pipe: 25 -624.9 52.50 PL 0.20 PF 0.092


25 2.50 0.0 2.217 0.0 4.81 120 FTG E PE 0.020
26 2.30 0.0 2.329 0.0 0.0537 TL 1.72 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 12/14/2020 E:\NS\MEI\CABLE AREA_4 INCH_01.SDF
JOB TITLE:

PIPE TAG Q(LPM) DIA(MM) LENGTH PRESS.


END ELEV. NOZ. PT DISC. VEL(MPS) HW(C) (M) SUM.
NODES (M) (K) (BAR) (LPM) FL/M (BAR)

Pipe: 26 -624.9 102.26 PL 0.33 PF 0.001


26 2.30 0.0 2.329 0.0 1.27 120 FTG ---- PE 0.032
27 1.97 0.0 2.362 0.0 0.0021 TL 0.33 PV

Pipe: 27 -624.9 102.26 PL 0.32 PF 0.001


27 1.97 0.0 2.362 0.0 1.27 120 FTG ---- PE 0.031
28 1.65 0.0 2.394 0.0 0.0021 TL 0.32 PV

Pipe: 28 -624.9 102.26 PL 0.50 PF 0.014


28 1.65 0.0 2.394 0.0 1.27 120 FTG A PE 0.049
29 1.15 0.0 2.457 0.0 0.0021 TL 6.60 PV

Pipe: 29 -624.9 102.26 PL 0.55 PF 0.009


29 1.15 0.0 2.457 0.0 1.27 120 FTG B PE 0.054
30 0.60 0.0 2.519 0.0 0.0021 TL 4.21 PV

Pipe: 30 -625.0 102.26 PL 0.66 PF 0.008


30 0.60 0.0 2.519 0.0 1.27 120 FTG E PE 0.000
31 0.60 SRCE 2.527 (N/A) 0.0021 TL 3.71 PV

NOTES (HASS):

(1) Calculations were performed by the HASS 8.6 computer program


in accordance with NFPA13 (2016)
under license no. 38051640 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760

(2) The system has been calculated to provide an average


imbalance at each node of 0.0212 lpm and a maximum
imbalance at any node of 0.6364 lpm.

(3) Total pressure at each node is used in balancing the system.


Maximum water velocity is 9.91 m/sec at pipe 20.

(4) Items listed in bold print on the cover sheet

are automatically transferred from the calculation report.

(5) Available pressure at source node 31 under full flow conditions is


0.00 bar compared to the minimum required pressure of 0.00 bar.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 12/14/2020 E:\NS\MEI\CABLE AREA_4 INCH_01.SDF
JOB TITLE:

(6) PIPE FITTINGS TABLE

Pipe Table Name: STANDARD.PIP

PAGE: * MATERIAL: S40 HWC: 120


Diameter Equivalent Fitting Lengths in Meters
(mm) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
15.00 0.04 0.09 0.04 0.09 0.11 0.02 0.19 0.19 0.09

PAGE: A MATERIAL: S40 HWC: 120


Diameter Equivalent Fitting Lengths in Meters
(mm) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
40.89 1.22 2.44 0.61 2.74 1.83 0.30 3.05 3.05 2.44
52.50 1.52 3.05 0.91 3.35 1.83 0.30 3.05 3.05 3.05
102.26 3.05 6.10 1.83 6.71 3.66 0.61 6.10 6.10 6.10
WATER SUPPLY ANALYSIS
Fixed Source Pressure: 0.00 bar
6.0
LEGEND
JOB TITLE:

1 Available pressure
0.00 bar @ 625.0 l/min
DATE: 12/14/2020

2 Required pressure
5.0
2.53 bar @ 625.0 l/min

G
A
U
G 4.0
E

P
R A. Source Supply Curve
B. System Demand Curve
E
S 3.0
S
U 2
R
E
2.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS

(
b
a
r
) 1.0

B
E:\NS\MEI\CABLE AREA_4 INCH_01.SDF
Page 7

1
0.0 A

-1.0
160 240 320 400 480 560 640 720 800
FLOW (LPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
(2) On Site pressures are based on hose stream deduction at the source
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 12/14/2020 E:\NS\MEI\CABLE AREA_4 INCH_01.SDF
JOB TITLE:

WATER SUPPLY CURVE

3.6+
|
|
|
3.3+
|
|
|
3.0+
|
|
|
2.7+
|
| X
|
P2.4+
R |
E |
S |
S2.1+
U |
R |
E |
1.8+
( |
B |
A |
R1.5+
) |
|
|
1.2+
|
|
|
0.9+
|
|
|==============================
0.6+ LEGEND "
| "
| X = Required Water Supply "
| 2.53 bar @ 625 l/min "
0.3+ "
| "
| "
| "
0.0*\\\\\\\\\\\\\\\\\\\\\\\\\\-\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\+
200 300 400 500 600 700 800 900 1000
FLOW (LPM)