Schedule of Rates - KPTCL PDF
Schedule of Rates - KPTCL PDF
Sl.
Particulars Page No.
No.
1 Corporate Order v
PART - I :
3 1 - 62
Material Portion
PART - II :
4 63 - 110
Labour Charges
PART - III :
5 111 - 130
Transformer Repairs
PART - IV :
Sl.
Symbol Abbreviation
No.
1 Ltr Litre
2 kL Kilo litre
3 km Kilo metre
4 m Metre
5 mm Milli metre
7 MT Metric Tonne
9 Sq m Metre square
13 L/s Lumpsum
14 kN Kilo Newton
15 nm Nano metre
16 mA Milli Ampere
c) Tree Schedule: Containing the details like name of the tree, girth
size of tree distance from central line of the alignment, approximate
height of the tree etc., complete.
4. EXCAVATION
i) Normal Dry Soil: Soil removed by means of ordinary pick axe and
shovel.
ii) Partially Submerged Soil : Where water rises in the pit upto 0.75 m
below ground level. Ref. IS: 5613 (Part II/Sec.2)1976.
iii) In Fully Submerged Soil : Where sub soil water rises in the pit
within 0.75 m below ground level.
iv) Soft rock/wet black cotton soil Laterite soil / B.C. Soil.
vi) Hard Rock with blasting. Requiring extensive blasting and /or
quarrying methods such as chiselling, wedging or using pneumatic
breakers etc.,
a) Back filling with the excavated earth available near the tower /
station structure / new earth with initial lead of 50 m including
watering and compacting layer by layer of 150 mm depth.
Labour charges for fabrication of ODS (as per approved drawing) made
out or rolled steel section, equipment mounting structures, inclusive of
one coat of good quality red oxide primer. All steel rolled sections shall
be free from any imperfections, mill scales, slag intrusions,
laminations, fillings rust etc., that may impair the strength, durability
and appearance and all members shall be of approved quality.
Galvanizing of structure / tower members shall conform to IS 4759 –
1968 and spring washers shall be galvanized in accordance with IS
1573 – 1970.
Bolts and nuts shall be of GKW make or similar quality shall be used.
All bolts & nuts and washers shall be galvanized in accordance with
ISS: 5358-1969. The depth of the bolt shall be such that the thread
portion will not be extending upto the plane of contact of the member.
The member connected shall bear upon the shank of the bolt and not
on the threaded portion of the bolt. The length of the bolt shall extend
at least 6 mm beyond the nuts when fully tightened.
8. ERECTION OF TOWERS
The ODS shall be erected on foundation not less than 14 days after
concreting or till such time concrete acquiring strength, either by build
up method or section method, positioning, levelling, aligning, plumbing
or column/ masks shall be done as approved by KPTCL., site Engineer,
i) Upright
i) Upright
Hoisting, erection, assembling the fuse units at the desired level on the
designated structures, levelling, aligning and checking for smooth
operation.
a) Main bus (all the three phases) using falcon / drake / lynx / coyote
/ double conductors with fixing of insulators having required height
above equipment, including providing jumps to inter connect
different segment of the main bus.
c) Rigid bus: Cutting the tubular bus bars of required size as per
drawing installation of main bus, aligning bus post insulator stacks
with clamps making V-taps, straight line taps, expansion joints,
bus inserts. Welding aluminium tubes by using pure argon gas with
shielding from wind and dust. The welding process to be carried out
at the rate of 15-20cm/minute washing with hot water after welding
and radiographic testing of joints including cost of gas and all
equipments required The weld shall have average strength from
120-155 kg/Sq cm.
1) Excavation for laying earthmat & back filling after laying the
earthmat.
10) Providing 450 mm dia Hume pipe collar for all electrodes in the
earthmat area and labelling.
I. Quantity
1. Density=1
4. Resistivity ≤ 10 ohm-metre.
Sl. Requirement of
Type of Electrode
No. dry Bentonite
1 Cast Iron Pipe electrode of
100 mm Id. 13 mm thick,
275 m long as per IS- 45 kg per
3040-1987 for a treatment electrode.
of 150 mm all-round the
electrode.
2 M.S.Flat conductor of
earthmat in sub-station for 9 Kg per running
a treatment of 150mm metre.
alround the MS Flat
conductor.
II Application:
a) Preparation of slurry:
The slurry shall be prepared in the following proportion.
To obtain good contact between soil and the electrode, the slurry
must be allowed to swell around the electrode/earthmat
conductor. This can be achieved only when the slurry is poured
around the electrode immediately after the slurry is prepared.
The annular space between cylindrical former and the earth pit
shall be back filled with normal soil up to the height of the
cylindrical former.
7. After laying the flats in the trench and interleaving all the
perpendicular crossings of flats shall be welded and applied a
thick coat of ACB paint as above.
12. The transformer plinth, Control room and outdoor switch shall
be surrounded by MS Flat of designed cross section at the
designed depth and the earthmat conductor shall be terminated
at the surrounding MS Flat by welding.
13. The earthmat shall be run below the concrete cable duct,
wherever the mat encounters cable duct path.
D) EARTH CONNECTIONS:
3) LIGHTNING ARRESTERS:
Each phase of the lightning arrester base plate shall be
connected to the cast iron pipe electrode provided for that
individual phase by running Galvanised Iron Flat from the base
plate. The cast iron pipe in turn shall be connected to the
earthmat by welding using Galvanised Iron Flat.
4) LIGHTNING MAST:
The earth conductor from the top of the Mast shall be run up to
the earthmat & welded.
5) SWITCHGEAR:
A minimum of two cast iron pipe electrodes are to be provided at
both ends of the switch gear. A separate earth bus of Galvanised
Iron Flat shall be run along the switch gear on the power cable
entry side & cable sheath earths shall be connected to this bus,
6) CONTROL ROOM
A Minimum of two cast iron pipe electrodes are to be provided
around the control room. The control panel earth bus shall be
connected to earthmat through the CI Pipe electrodes provided
as above.
The control panel body & earth points shall be connected to the
control panel earth bus.
G) SUBSTATION FENCING:
e) The fence earth and station earthmat shall not have any electrical
tie and should be physically separate.
b) The distance between any two CI pipe electrodes should not be less
than twice the length of the CI pipe electrode.
c) The lightning arrester earth connection should not be run over the
ground surface. They should be directly run vertically down up to
the mat depth and connected to the earthmat at the nearest point
at that depth.
The pipe shall be buried such that, only 150 mm length of the CI
pipe is above the ground level.
The annular space shall be filled with Sodium bentonite slurry till
the entire bore length of required depth is covered. The slurry level
sinks after few hours. This is again to be filled with slurry and the
process continued until the entire length is filled with bentonite and
no further sinking takes place.
1) Metal piping should not be used for water supply within the
substation yard.
24. PAINTING
a) Supplying and painting of two coats of good quality Red oxide primer
after cleaning and scrapping the surface.
Installing and assembling, filling of acid and wiring, test charging and
discharging.
Supplying and spreading of 100 mm thick with 20/25 mm jelly with all
lead and lifts.
a) Excavation
b) Burnt brick/size stone/RCC revetment including form box back
filling besides Removing the excess excavated soil, duct covering
with RCC slabs.
Formation of Faraday cage using 7/10 SWG or 7/9 SWG rig including
fixing of hardware at tension points and grounding the cage using the
same size of wire as for the cage.
Provisions made in MWSR 2016 viz. 15% over the basic labour rates to
take care of contractor’s overheads, ‘Special Locality Allowance’,
Scattered Area Mobilisation Allowance (at 5% over the basic labour
rates for both Station and Line work for the areas which are not
covered under ‘Special Locality Allowance’), Area allowance for
Transmission Line works etc., are retained in MWSR 2019.
11 kV NCTs - 2000-1200/1-1-1 A
1.3.11 No. 0.26
(for 31.5 kA SWG)
11 kV NCTs - 1200-800/1-1-1 A
1.3.12 No. 0.28
(for 500 MVA SWG)
11 kV NCTs - 800-600-400/1-1-1 A
1.3.13 No. 0.42
(for 350 MVA SWG )
11 kV NCTs - 600-300/1-1-1 A
1.3.14 No. 0.41
(for PCVCBs upto 10 MVA Transformer)
11 kV CTs - 2000-1200/1-1-1 A
1.3.15.1 No. 0.34
(for Incomer/Bus coupler for 31.5 kA SWG)
11 kV CTs - 1200-800/1-1-1 A
1.3.15.2 No. 0.20
(for Incomer/Bus coupler for 500 MVA SWG)
11 kV CTs - 800-400/1-1-1 A
1.3.15.3 No. 0.21
(for Incomer/Bus coupler for 350 MVA SWG )
11 kV CTs - 600-400/1-1-1 A
1.3.15.4 No. 0.27
(for for feeders of 31.5 kA SWG)
11 kV CTs - 400-200/1-1-1 A
1.3.15.5 No. 0.24
(for for feeders of 500 MVA SWG)
11 kV CTs - 200-100/1-1-1 A
1.3.15.6 No. 0.24
(for feeders of 350 MVA SWG)
1.5.2 110 kV/√3 / 110 V/√3 - 110 V/√3 - 110 V/√3 No. 0.93
1.5.3 66 kV/√3 / 110 V/√3 - 110 V/√3 - 110 V/√3 No. 0.57
1.11.6 12.1 kV, 2.9 MVAr star connected Capacitor Bank Set 3.72
1.11.7 12.1 kV, 5.8 MVAr star connected Capacitor Bank Set 7.71
2.2.5 220 kV Bus Bar Protection panel - Type 2BBA No. 26.31
3 TOWERS : 7308
Amount
5 ACCESSORIES : 7308
in Rs.
6.3 9.5 metre Long 300 kg working load for ODS No. 9753.09
8 CONDUCTORS : 7604
Amount in
10 TELECOMMUNICATION EQUIPMENTS : 8517
Rs. Lakhs
Amount
10.7 Over Head Cables (Unshielded) 8517
in Rs.
Per
10.10.1 Push Button Telephone 485.04
Unit
Plan 103 P.B. Telephone (1 Main & 1 Extn) with
10.10.2 No. 3589.26
caller ID
10.12 10.12.1 Krone modules for 10 pairs isolation type No. 8517 169.76
10.12.2 Krone modules for 100 pairs (10 nos. each row) No. 8517 388.03
Amount
11.4 Cables : 8544
in Rs.
Current cable - Copper core with c/s 4 Sq mm
11.4.1 multistrand m 280.74
7 core
Voltage cable - Copper core with c/s 2.5 Sq mm
11.4.2 m 111.59
multistrand 4 core
11.8.3 Tension Assembly for Dead End for 24 Fibre OPGW Set 2313.00
11.8.8 Down Lead Clamp assembly for Fibre OPGW No. 255.00
Amount in
11.12 Test Equipment for Fibre Optic Cabling 8544
Rs. Lakhs
OTDR (Optical Time Domain Reflectometer) for
11.12.1 No. 2.69
1310/1550 nm with laser source
Amount
12 TOOLS AND PLANT :
in Rs.
Portable (mobile) Oil Pump (1/2 HP Air Pump 500
12.1 No. 8413 13395.41
to 1000 gallons)
12.7 Double end spanner - 12 nos. per set Set 8207 548.56
12.38 Hydrometer syringe suitable for vent holes No. 9033 595.35
12.40 Wall mounting type holder for Hydrometer No. 9033 1786.06
12.52 Manilla rope 1" (One bundle of 100 m) Bundle 5608 14437.93
12.53 Manilla rope 3/4" (One bundle of 100 m) Bundle 5608 14437.93
12.55 Portable drilling machine with stand (heavy duty) No. 8459 28279.21
HSN Bersimis/
26
13 13.1 HARDWARE
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
13.1.1 Single Tension Clamps with arcing horns No. 7318 2735 2487 1085 993 780 816
13.1.2 Double Tension Clamps with arcing horns No. 7318 4872 4429 3090 2870 2554
13.1.3 Single Suspension Clamps with arcing horns No. 7318 1709 1553 1318 1219 812 861
13.1.4 Double Suspension Clamps with arcing horns No. 7318 3243 2948 2515 2487 2231
13.1.5 P.G. Clamps No. 7318 941 535 513 210 91 266
13.1.6 M.S.C. Joints No. 8538 836 760 442 411 273 303
13.1.7 Pre-formed Armour Rods No. 7221 2434 2212 836 716 578
13.1.8 Repair Sleeves No. 7609 643 585 391 199 146 204
13.1.9 Vibration Damper No. 7308 1122 1020 671 564 606
13.1.10 Automatic Come - along Clamp No. 7318 5760 5236 5031 5031 5031 2757
13.1.11 Pad Clamps No. 7318 818 535 738 210 534
HSN Amount
Sl. No Description of Materials Unit
Code in Rs.
13.3.1 Single Tension Clamp Compression type Drake ACSR No. 2527
13.3.2 Single Tension Clamp Compression type Moose ACSR No. 2527
13.6.1 Twin Falcon ACSR Conductor 127 mm, 220 kV No. 1263
13.6.2 Twin Moose ACSR Conductor 127 mm, 220 kV No. 1080
14 Relays : 8536
14.3 Single pole Directional Over Current/ Earth Fault Relay No. 12125
14.5 Single pole Over Current / Earth Fault Relay No. 9262
15.1.8 9 kV, 5 kA Lightning Arrestor (Metal oxide type) No. 8535 827
15.1.9 9 kV, 10 kA Lightning Arrestor (Metal oxide type) No. 8535 3025
16.2 Cold Shrinkable type termination kit for XLPE Cable 8538
16.2.1 Indoor
16.2.2 Outdoor
16.4.1 Indoor
17.2 Water type (Gas pressure type) 9 litre capacity No. 1656
Erection 13813
Supply and erection of 3 Ph 11 kV/433 V Distribution
19.2.1 8504
Transformer with copper windings
19.2.1.1 250 kVA - Supply No. 280150
As per the
weight of the
167 MVA, 400/220/33 kV single phase Inter - Transformer
21.1 21.1.1 Set 8504 427.85
Connecting Transformer (ICT) (rate / MT
indicated in
labour portion)
As per the
315 MVA, 400/220/33 kV three phase Inter-
21.1.2 Set 8504 1180.09 weight of the
Connecting Transformer
Transformer
As per the
500 MVA, 400/220/33 kV three phase Inter-
21.1.3 Set 8504 1262.51 weight of the
Connecting Transformer
Transformer
As per the
420 kV Class, 125 MVAr Bus Reactor along with
21.2 21.2.1 Set 8504 591.86 weight of the
Neutral Ground Transformer
Reactor
As per the
420 kV Class, 63 MVAr Line Reactor along with
21.2.2 No. 8504 464.27 weight of the
Neutral Ground Transformer
Reactor
21.3.2 420 kV Class 50 kA, 3150 A (with closing resistors) Set 33.00 53411.28
21.4 Controlled Switching device for Circuit Breaker Set 8536 4.57 2750.21
21.5.6.1 3-Pole with single earth switch (Line Isolator) Set 8.64 24543.75
21.5.6.2 3-Pole with double earth switch (C Isolator) Set 9.38 24543.75
21.9.1 Back-up control panel for 400 kV Reactor Set 7.17 6875.53
21.11.8.1 to receive 4" IPS Al. Tube flexible type No. 4800.00
T' Clamp suitable for 4" IPS Al. tube to Twin Moose
21.11.10.1 No. 3004.06
ACSR conductor
21.11.10.2 T' clamp suitable for 4"Al. tube to 4" Al. tube. No. 2949.46
T' Clamp suitable for 4" IPS Al. tube to Twin Bersimis
21.11.10.3 No. 3699.00
ACSR conductor
21.11.10.6 T' Clamp suitable for Moose ACSR to Moose ACSR No. 780.00
21.11.14 Welding sleeve suitable for 4 inch IPS Al. tube No. 7609 1824.28
21.12.3.2 4" IPS Al. tube Rigid through type No. 1983.64
21.12.12 T' Clamp suitable for Moose ACSR to Moose ACSR No. 8535 740.00
21.12.13 T' Clamp suitable for Quad Moose to Quad Moose No. 8535 2960.00
21.12.14 T' Clamp suitable for Quad Moose to Twin Moose No. 8535 3800.00
21.12.15 T' Clamp suitable for Twin Moose to Twin Moose No. 8535 1480.00
21.12.19 PG Clamp suitable for ACSR Moose to ACSR Moose No. 8535 480.00
21.12.28 Welding sleeve suitable for 4 inch IPS Al. tube No. 7609 2094.13
21.12.29 Corona Bell suitable for 4 inch IPS Al. Tube No. 7318 691.54
21.13.5 Clamps for Moose ACSR suitable for BPI No. 8535 560.00
21.13.7 Welding sleeve suitable for 2.5 inch IPS Al. tube No. 7609 664.25
21.13.8 Corona Bell suitable for 2.5 inch IPS Al. Tube No. 7318 324.97
T' clamp suitable for connecting 2.5 IPS Al. tube of 2.5"
21.13.10 No. 8535 3058.65
IPS Al. tube
Supply
Insulator with hardware for Twin Moose ACSR
21.14 8546 rates in
conductor
Rs. Lakhs
Supply
Insulator with hardware for Quad Moose ACSR
21.15 8546 rates
conductor
in Rs.
8535/
21.17.7 T-Connectors No. 1314.45
8536
per
21.19.1 Hilly Terrain 5025.67
km
per
21.19.2 Plain Terrain 3354.11
km
22.3.3 Straight Joint Kit for Optical Fibre cable Kit 8536 0.13
22.3.4 Line Interface Unit for Optical Fibre cable Unit 9001 0.13
23.6 220 kV Line (U.G. Cable) Module : No. 8544 214.27 1.62
23.7 220 kV Line (O.H. Line) Module : No. 7604 212.03 1.62
ii Disconnector :
Transformer Module
23.9 No. 8504 211.09 1.62
(For 150 MVA - 220 kV side)
Transformer Module
23.11 No. 8504 114.77 1.44
(For 150 MVA - 66 kV side)
ii Disconnector:
i Disconnector :
3P/3P/0.2, 50/50/50 VA
66 kV Transformer Module
23.14 No. 8504 113.90 1.44
(For 31.5 MVA)
ii Disconnector :
i Disconnector :
i Disconnector :
ii Disconnector :
Transformer Module
24.1.3 150.82 2.38
(For 100/150 MVA - 220 kV side )
ii Disconnector :
ii Disconnector :
Amount in
26 Covered Conductor and accessories
Rs.
52 kV Grade CCSX 99 ACSR Covered
26.1 Conductor with 99 Sq mm cross section km 7614 1377500
metres area
26.7 Wedge clamps for Coyote ACSR conductor No. 7318 3491
c) Tower Schedule
d) Line Schedule
Digitised Contouring at
undulated/hilly tower locations as
detailed in technical specifications for
assessing the quantum of benching
and revetment required and
submission of draft report on the work
done (as per number of points of levels
vii No. * 31 _
taken).
Remarks:-
i) In case of detailed survey of existing
line for preparation of schedules to
facilitate placing of proposals before
PTCC, 50% of the above costs are to
be adopted.
ix Preparation of Schedules:
a
Running Peripheral Theodolite
traverse along periphery and co-
ordinating and heightening of all
corners/turning points, establishing
permanent co-ordinate axis formation
of Grids at 50 metre intervals for
Hectare 1427
northing and easting with reference to
already established permanent co-
ordinate axis levels at 50 metre Grid
intersection for preparing plot plan of
the entire area with contours.
Including existing structure location.
iii Partially Submerged soil cu m Latest KPWD SR Rate for ordinary soil
v Wet black cotton soil cu m Latest KPWD SR Rate for ordinary soil
i Normal Soil cu m
ii B.C. Soil cu m
C Back Filling :
Note :
a) Extra as indicated in the relevant
KPWD SR may be allowed for
providing concrete in watery
situations including cost of bailing out
water and removing slush.
7 Fixing of Boards
Set
c Fixing Phase Plate 161
(3 Nos.)
12512 with
i For Hilly terrain km 27541 13771
coyote ACSR
5928 with
ii For Plain terrain km 13333 5928
coyote ACSR
Note:
Conductors normally used are:
i) 220 kV - Drake and AAAC Moose
ii) 110 kV - Lynx and Drake
iii) 66 kV - Coyote and Drake
ii) Pre-arranged
replacement/rectification of line
materials.
Note:
1) Conductors normally used are:
i) 400 kV - Quad Moose and
Bersimis
ii) 220 kV - Drake and AAAC
Moose
iii) 110 kV - Lynx and Drake
iv) 66 kV - Coyote and Drake
Grounding of towers/Equipments
excluding the cost of G.I. Pipe/C.I.
Pipe as per specifications with 50 X 6
b mm G.I. Flat 3 metres Long (to be Set 924+975
supplied departmentally). But salt &
Charcoal to be supplied by contractor.
The rates include excavation charges.
13 Station Structures
14 Erection of Transformers
12.5/
100/
Testing & Commissioning of Power 20/ 8/10 5/6.3
17 150
Transformers 31.5 MVA MVA
MVA
MVA
Inspection of wires and Ferrules.
Inspection of wiring of Protective
a 13862 11551 7701 6931
Devices, Cooling fans, Oil flow Pumps,
OLTC, RTCC
Testing:
1. Ratio Test
2. SC test Lump
3. Excitation test Sum for
4. Magnetic Balance test Each
b 5. Vector group test 55449 46205 30805 27722
6. Induced High voltage test
7. OLTC operation
8. Protective Devices operation Checks
9. Stability Checks: For Differential &
REFR protection
18 Erection of Breakers
Testing:
Test for insulation level, gas leakage,
Testing for travel time, Trip and close
Set 35940 27722 27722 27722
timings. Local Trip close test, Remote
trip and close test, Tripping through
relays, operation of interlocks etc.,
Wiring:
Inspection of wiring, Ferruling, Set
4621 2310 2310 2310
Crimping of lugs, Connections up to (3 Nos.)
marshalling box & Control panel.
Wiring:
Inspection of wiring,Ferruling, Set
2310 2310 2310 2310
Crimping of lugs, Connections up to (3 Nos.)
marshalling box & Control panel.
21 Erection of Isolators
Note:
1) Assisting in testing and
commissioning for item nos. 17 to 19
means contractors should provide
labourers for testing and
commissioning by RT/MT/Firm
Engineers.
Heat Shrinkable/Cold
ii No. 2857
Shrinkable/Pushon
26 Control Panels
Sychronising Trolley/Panel:
ii Wiring, Testing, Calibration of meters Each 13512
& Testing for operation
Wiring:
Identification, ferruling, crimping, Rs.2702 upto 3 Bays & Rs.1155 for each
termination of wires in Bus Bar additional Bay.
protection panel.
Testing:
Rs.10810 upto 3 Bays & Rs.4620 for each
1. Testing of relays.
additional Bay.
2. Stability test.
27 11 kV Switchgear
Note:
Assisting in Testing & Commissioning
for item 22, 24 & 23 means
contractors should provide labourers
for wiring & Commissioning by
RT/MT/Firm Engineers.
28 Busbar Formation
29 Groundmat
50x6-135
50x8-152
Same as above but without sodium
ii Rmtr 75x12-429
bentonite clay
75x6-367
75x8-395
c Bentonite Clay kg 17
31 Site surfacing
i
Note : Only 20/25 mm jelly shall be
used.
Commissioning:
i) Fixing of Boost Voltage level
ii) Fixing of Float Voltage level
iii) Fixing of Trickle Voltage level
iv) Testing of alarm, indication and
load ckts, Auto/Manual change overs
etc.
v) Full load test in Boost & Trickle
modes
35 Fencing :
36 A PLCC Equipments
Erection of mounting structures for
a Set 5057 5057 5057 5057
coupling capacitors
Erection of Coupling capacitors/wave
b Set 10078 8049 3837 1827
traps/LMU.
37 Yard Levelling
Yard Levelling and filling up of soil As per Latest KPWD SR
cu m
and consolidation. applicable to respective areas
38 Watch and Ward
39 Transportation
Transportation of Transformer, CTs,
A PTs, Breakers, C&R Panels, 11 kV
Switchgears and EHT LAs only.
1 Using 10 MT Lorry
Up to 50 metres initial
1 Included in the item Rate
lead
43 Dismantling
Udupi District :
b 35%
Udupi, Kundapur, Karkala Taluks
Kodagu District :
d 35%
Madikeri, Virajpet, Somarwarpet, Taluks
Chikkamagalur District :
Kadur, Chikkamagalur, Koppal, Tarikere,
e 25%
Mudigere, Narasimharajapura, Sringeri
Taluks
f Shimoga District :
Davangere District :
g 15%
Chennagiri Taluk only
h Dharwad District :
i Haveri District :
j Belgaum District :
Mysore District :
k 25%
Heggadadevanakote, Hunsur Taluks
Chamarajanagar District :
l 25%
Gundlupet, Chamarajanagar, Kollegal Taluks
Hassan District :
m Sakaleshpur, Hassan, Arakalagud, Belur, 25%
Alur, Taluks only
Note:
1) In case of civil works where KPWD SR rates
are adopted, the locality allowance as
applicable in KPWD SR shall be followed.
2) For all other works the locality allowance
as indicated above shall be followed.
Note:
1. Extra for excavation under
Earth work excavation for laying of UG cable
water condition and or foul
below footpath in the following strata of soil
conditions including
by mechanical/manual means including
bailing/pumping out removal of
removing and re-fixing the kerb and
slush add 20% of the rate.
pavement stone slabs, removing and re-
2. The indicated rates are
fixing masonry of other services with patch
applicable for works in BBMP
2 A work, deposition of earth/rock on bank with
limits of Bangalore. For other
all leads and lifts including shoring,
areas the rates of respective KPWD
strutting, providing caution boards, danger
Circles shall be considered.
lighting, bracing, sheeting, bailing out of
3. No extra area weightage need to
water, barricades and other works not
be added to the rates indicated
specifically mentioned herein but required
here for works in BBMP limits
for the completion of work in all respects
since the PWD area weightage is
already considered.
Note:
1. The indicated rates are
applicable for works in BBMP
Cutting the road surface for laying of cable &
limits of Bangalore. For other
disposing of the excavation/debris with all
areas the rates of respective KPWD
leads and lifts to any notified disposal point
Circles shall be considered.
3 of the local bodies/as directed including
providing barricading, danger
2. No extra weightage need to be
lighting/caution boards etc., in the following
added to the rates indicated here
classifications of road surfaces.
for works in BBMP limits since the
PWD area weightage is already
considered.
Surface Restoration :
Providing road restoration work consisting of
Granular Sub-Base, wet mix macadam,
bituminous macadam, bituminous concrete, Note:-
Primer Coat & Tack Coat as per BBMP
specifications / requirements and drawing 1. The indicated rates
15 are applicable for
including cost of all materials, labour, over
heads, machineries etc., and directions of works in BBMP limits
the Engineer in charge of the work. of Bangalore. For other
(Note: For detailed specifications KPWD SR areas the rates of
of Bangalore Circle and NH SR shall be respective KPWD
referred.) Circles shall be
considered.
2. No extra area
a Cable trench clear width 0.80 metre Rmtr 1269 weightage need to be
added to the rates
indicated here for
works in BBMP limits
b Cable trench clear width 1.00 metre Rmtr 1586 since the PWD area
weightage is already
considered.
i Acidity 1350
ii Resistivity 1650
ix Density 1350
Amount
Sl. No. Description of Materials Unit HSN Code
in Rs.
iii Suitable for 245 kV class / 1250 A bushing No. 8536 38000
i MCB/MCCB
vi OLTC Conservator
vii Oil Surge relay for OLTC No. 8504 / 9010 10000
i Conservator tank
9 Others
Marshalling Box (with IP 55 degree of
protection, TBs, Earthing arrangement,
i No. 15000
mounting arrangements for various
components etc.,)
66/11 kV Class
L/s 8 22991
220/66/11 kV Class
110/33-11 kV Class or
110/11 kV Class
L/s 10 24420
9988
L/s 16/20 48840
220/110/11 kV Class
a 220 kV and above class Transformer L/s 9988 All capacity 400000
b 110 kV and below class Transformer L/s 9988 All capacity 250000
a 220 kV and above class Transformer L/s 9988 All capacity 56000
b 110 kV and below class Transformer L/s 9988 All capacity 32500
a 220 kV and above class Transformer L/s 9988 All capacity 168750
b 110 kV and below class Transformer L/s 9988 All capacity 97500
a 220 kV and above class Transformer L/s 9988 All capacity 135000
b 110 kV and below class Transformer L/s 9988 All capacity 78000
L/s 8 26823
220/66/11 kV
400/220 kV - 33 kV Class
110/33-11 kV Class -
110/11 kV Class
L/s 10 28490
9988
L/s 16/20 56979
220/110/11 kV Class
a 220 kV and above class Transformer Each 9988 All capacity 4000
b 110 kV and below class Transformer Each 9988 All capacity 1500
ii 66/11 kV Class
L/s 8 15327
220/66/11 kV
L/s 10 16280
9988
L/s 16/20 32559
220/110/11 kV Class
66/11 kV Class
L/s 8 6270
400/220 kV - 33 kV Class
L/s 10 6660
9988
L/s 16/20 13320
220/110/11 kV Class
a 220 kV and above class Transformer L/s 9988 All Capacity 75000
b 110 kV and below class Transformer L/s 9988 All Capacity 50000
Reconditioning of accessories like Radiators,
Conservator by hot air circulation along with
9
pressure test of radiators and reconditioning of
Transformer mounted mechanical relays
i 220 kV and above class Transformer L/s 9988 All Capacity 100000
ii 110 kV and below class Transformer L/s 9988 All Capacity 70000
66/11 kV Class
L/s 8 16720
220/66/11 kV Class
400/√3 / 220/√3 kV -
Cleaning, Repairing and painting inside the 33 kV Class
Transformer Tank with hot oil bath and acid proof
epoxy paint and painting outside the tank with
ii L/s 9988 167 72067
enamel paint after thorough cleaning including the
cost of materials including the painting of radiators
at site/Firm. 400/220 kV - 33 kV Class
110/33-11 kV Class -
110/11 kV Class
L/s 10 22199
9988
L/s 16/20 35519
220/110/11 kV Class
66/11 kV Class
L/s 8 15327
220/66/11 kV Class
110/33-11 kV Class -
110/11 kV Class
L/s 10 20350
9988
L/s 16/20 32559
220/110/11 kV Class
B Solid insulation
Providing solid insulation materials for replacement
i of damaged or burnt insulation as per actual kg 9988 All capacity 426.35
weight.
C Winding
Providing re-insulation to HV/LV winding whenever
i necessary for total weight of winding except solid kg 9988 All capacity 166.75
insulation.
L/s 8 15902
220/66/11 kV
L/s 10 20350
220/110/11 kV Class
a 220 kV and above Class (Inclusive of cost of OLTC) L/s 9988 All capacity 1450000
b 110 kV and below class (Inclusive of cost of OLTC) L/s 9988 All capacity 1087500
ii Replenishment of Nitrogen gas (50 kg) No. 9988 All capacity 20000
Provision for refurbishment/overhauling of various items may be made wherever the items seems
2 to be in good condition by visual inspection. Decision regarding replacement of such items may
be taken during Joint inspection for which SR rates are available.
Any Transformer that does not have NIFPS, provision shall be made for fixing of NIFPS to the
3
Transformer for capacities of 20 MVA and above.
GST Reference Code 9988 : Manufacturing services on physical inputs (goods) owned by
4
others.
Note:
1. The towers are designed for
a) Normal Span : 400 m
b) Conductor : Twin ACSR Moose
2. These towers are used for 400 kV DC BTPS - Hiriyur line
Note:
1. The towers are designed for
a) Normal Span : 400 m
b) Conductor : Quad Moose ACSR
2. These towers are used for 400 kV DC Nandikur - Shanthigram line
9 ME
9 ME
2 A+3M 4.629 3.060 158 5.651 4.244 173 6.300 4.810 198 6.63 3.884 167
3 A+6M 5.109 3.649 185 6.202 4.731 190 6.967 5.350 220 7.31 4.283 175
7 C+0M 6.800 3.600 165 6.750 6.089 247 8.300 6.000 240 9.90 6.060 218
8 C+3M 7.852 4.321 196 7.683 7.114 279 9.400 7.490 290 11.25 7.227 251
9 C+6M 8.904 4.940 221 8.616 7.677 285 10.500 8.220 315 12.57 8.133 265
10 D+0M 8.000 4.980 188 10.150 8.588 268 10.200 7.925 300 10.60 7.597 275
11 D+3M 9.206 6.062 229 11.694 10.137 320 11.600 9.905 356 12.07 9.031 314
12 D+6M 10.412 6.777 249 13.328 11.692 364 13.000 10.875 385 13.54 10.175 343
Note: A Type : 0° - 2° Deviation
1 Weight of Stubs is included in Normal Tower weights only B Type : 2° - 15° Deviation
2 At present 220 kV DC Kalpatharu design is being used C Type : 15° - 30° Deviation
3 220 kV SC 'A' Type Tower is of M/s. KEC make D Type : 30° - 60° Deviation & DE Condition
220 kV DC TOWER
(M/s. RPG Design)
Weight of Tower (in kg)
Note:
1. The towers are designed for
a) Normal Span : 320 m
b) Conductor : AAAC MOOSE
2. These towers are used in 220 kV DC Narendra - Ambewadi line
Type of Super
Sl. No. Bolt & Nuts Super Structure Bolt & Nuts
Tower Structure
MS MS HT MS MS
Normal
1 5814 272 4325 6351 404
Tower
+3M Extn
2 678 30 849 526 55
only
+6M Extn
3 - - 1572 815 74
only
Note:
1. The towers are designed for
a) Normal Span : 200 m
b) Conductor : AAAC Moose (61/3.55)
2. These towers are used for 220 kV DC Narrow Based Hoody - HAL line
MB Normal 9.0 x 9.0 3026 11660 14686 613 121 734 776
MD Normal 11.0 x 11.0 7478 18316 25794 1140 225 1365 772
Note:
1. The towers are designed for
a) Normal Span : 320 m
b) Conductor : Drake ACSR
2. These towers are used for 220 kV MC Shimoga - Dugudimane line
Weight of
the pole Embedded Foundation Details
Monopole Type (in kg)
Excavation
HT Total L D Steel RCC (M30)
in m³
P3+0M
PS4/PS5 +0 DC
Monopole with
0M 20585
single sided cross
arm
PS6 +0 SC
Monopole with
0M 8069
single sided cross
arm
Note:
1. These towers are designed for
a) Normal Span : 320 m
b) Conductor : 220 kV circuit : Drake ACSR
110 kV Circuit : Lynx ACSR
2. These towers are used for 220/110 kV MC line from Khemar to Guruvayankere
(Conventional Base)
+9M Extn 6.89 x 6.89 1528 2003 3531 689 0 689 151
Note:
1. The towers are designed for
a) Normal Span : 320 m
b) Conductor : 220 kV - Drake ACSR
: 110 kV - Lynx ACSR
2. These towers are used for 220/110 kV MC VARAHI - KEMAR - KAVOOR Line
(Narrow Based)
+3M Extn
+6M Extn
+6M Extn
Note:
2. These towers are used for 220 kV MC OHL for Vikas Tech Park
Normal
1 9372 332 - - 17303 622 31110 1191
Tower
+3M Extn
2 1031 34 - - 1996 90 3529 144
only
+6M Extn
3 2120 81 - - 3587 132 6257 223
only
Note:
1. The towers are designed for
a) Normal Span : 275 m
b) Conductor : Drake ACSR (220 kV Circuit)
: Coyote ACSR (66 kV Circuit)
2. These towers are used for 220/66 kV MC Hoskote - BIAL line
Stubs and
Fabricated Steel Members Bolts & Nuts
Soil EXCA Cleats
Sl. Type of Base Width (in MT) (in kg)
Classifi- (in (in MT)
No. Tower MxM
cation CMT/Twr)
HT MS Total HT MS Tower Stub Total
2 A PS 7.9 x 7.9 187.23 3.5745 3.9489 7.5234 0.4259 0 602.30 5.70 608.00
5 A+3 PS 8.1 x 8.1 196.83 0.3945 0.3762 0.7707 0.4529 0 539.30 5.70 545.00
8 A+6 PS 8.1 x 8.1 196.83 0.7899 0.7669 1.5568 0.4259 0 111.70 5.70 117.40
11 B PS 9.3 x 9.3 259.47 6.6163 5.6518 12.2681 0.7953 0 681.60 9.90 691.50
14 B+3 PS 9.7 x 9.7 282.27 0.7524 0.5058 1.2582 0.7953 0 76.90 9.90 86.80
17 D PS 11.1 x 11.1 492.84 14.0299 7.3966 21.4265 2.2797 0 1504.50 67.70 1572.20
20 D+3 PS 11.6 x 11.6 538.24 2.6665 0.3233 2.9898 2.2797 0 256.00 67.70 323.70
23 D+6 PS 11.6 x 11.6 538.24 5.0249 0.6667 5.6916 2.2797 0 517.40 67.70 585.10
26 D+9 PS 11.6 x 11.6 592.064 7.3859 1.0193 8.4052 2.2797 0 776.70 67.70 844.40
29 D + 12 PS 11.6 x 11.6 592.064 9.7670 1.4100 11.1770 2.2797 0 957.60 67.70 1025.30
110 kV SC Design 110 kV DC S.A.E Design 110 kV SC Kalpatharu Design 110 kV DC Kalpatharu Design
Basic
Sl. Tower Tower Tower Tower
Tower Base B&N Base B&N Base B&N Base B&N
No. weight with weight with weight with weight with
Extn width weight width weight width weight width weight
Stub Stub Stub Stub
(in m) (in kg) (in m) (in kg) (in m) (in kg) (in m) (in kg)
(in MT) (in MT) (in MT) (in MT)
1 A+0M 3.334 1.660 91 4.200 2.700 135 3.400 1.525 84 4.30 1.974 71
2 A+3M 3.820 2.004 108 4.705 3.128 155 3.868 1.808 100 4.87 2.301 79
SCHEDULE OF RATES - 2019
3 A+6M 4.306 2.362 129 5.211 3.596 178 4.325 2.122 119 5.44 2.672 88
7 C+0M 4.826 2.380 131 6.700 3.790 195 2.218 77 6.00 3.315 86
8 C+3M 5.624 2.875 150 7.699 4.594 220 2.645 101 6.84 4.039 96
9 C+6M 6.410 3.545 159 8.698 5.240 250 2.902 126 7.68 4.493 108
10 D+0M 4.826 3.070 174 7.400 4.910 258 5.000 3.006 141 7.20 4.61 182
11 D+3M 5.624 3.707 201 8.498 5.880 297 5.729 3.540 166 8.36 5.66 210
12 D+6M 6.410 4.453 219 9.596 6.690 331 6.400 4.130 193 9.52 6.127 218
Note:
Note:
1. The towers are designed for
a) Normal Span : 320 m
b) Conductor : LYNX ACSR
KPTCL / S.A.E Design L&T Design KEC Design L&T Design Kalpatharu Design
BASIC
Sl.
TOWER
No. Tower Tower Tower Tower Tower
/EXTN Base Base Base Base Base B&N
Weight B&N wt Weight B&N wt Weight B&N wt Weight B&N wt Weight
width width width width width wt
With Stub (in kg) With Stub (in kg) With Stub (in kg) With Stub (in kg) With Stub
(in m) (in m) (in m) (in m) (in m) (in kg)
(in MT) (in MT) (in MT) (in MT) (in MT)
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
1 A+0M 2.000 1.126 137.72 2.495 1.210 75.000 2.800 1.506 93.220 3.323 1.658 83.000 4.200 1.293 56
2 A+3M 2.311 1.454 176.98 2.948 1.545 96.007 2.257 1.839 109.880 3.899 2.041 104.551 4.852 1.578 65
3 A+6M 2.622 1.756 213.82 3.404 1.888 111.761 3.727 2.164 127.140 4.476 2.443 121.000 5.695 1.897 70
7 C+0M 3.000 1.619 156.69 4.250 1.669 84.700 4.600 2.355 129.700 4.360 2.500 150.400 5.250 1.910 63
8 C+3M 3.549 1.992 183.01 5.156 2.143 106.164 5.480 2.865 152.510 5.240 3.046 173.801 6.250 2.304 73
9 C+6M 4.099 1.395 209.33 6.063 2.566 120.388 6.361 6.113 3.504 198.109 7.206 2.762 80
10 D+0M 4.300 1.885 224.44 4.700 2.279 127.720 5.700 3.112 142.020 4.428 3.620 188.770 7.800 2.487 83
11 D+3M 5.162 2.506 258.16 5.518 2.821 149.926 6.660 3.744 168.870 5.325 4.296 215.157 6.868 3.030 97
12 D+6M 6.024 2.886 277.62 6.636 3.335 174.170 7.620 4.291 180.020 6.222 4.936 238.838 7.936 3.699 115
Note:
1. The towers are designed for
a) Normal Span : 250 m (Coyote ACSR)
140 m (AAAC Moose)
140 m (ACSR Drake)
Note:
1. The towers are designed for
a) Normal Span : 200 m
b) Conductor : Coyote ACSR
2. These towers are used for 66 kV DC Kushalnagara - Madikere line
Note:
1. The towers are designed for
a) Normal Span : 275 m
b) Conductor : Coyote ACSR
E C 6.78 48.92 - 5.073 41.760 9.00 73.73 5.82 0.72 52.27 166 C
T D 7.08 50.72 - 7.260 59.050 11.33 95.00 8.27 1.11 84.27 219 D
A 10.55 66.01 939 4.600 37.363 8.39 56.44 4.51 0.62 36.99 118 A
D 11.67 74.08 - 9.910 76.250 13.24 107.03 10.46 1.51 111.63 274 D
A 10.55 66.01 939 6.712 56.400 14.20 82.42 6.05 0.80 50.69 154 A
D 18.49 102.18 - 15.475 106.170 19.54 144.02 13.04 1.99 142.83 351 D
66 kV SC KPTCL Design
66 kV SC L&T Design 66 kV DC KEC Design 66 kV DC Kalpatharu Design
BASIC (S.A.E Modified Design) BASIC
FDN TYPE TOWER CONC (in CMT) EARTH Steel TOWER
EXTINS CONC EXCA REINF CONC EXCA REINF CONC EXCA REINF
EXCA REINF EXTINS
(in CMT) (in CMT) (in kg) (in CMT) (in CMT) (in kg) (in CMT) (in CMT) (in kg)
1:02:04 1:03:06 (in CMT) (in kg)
A 8.30 76.82 - 9.693 106.171 261.42 17.07 127.00 592 8.84 1.36 74.00 206 A
SCHEDULE OF RATES - 2019
D 14.85 87.87 - 14.779 167.020 548.24 35.95 246.96 1245 18.90 3.04 211.68 593 D
B - - - 1.190 1.010 - - - - B
Hard Rock
C 1.62 1.44 65 1.191 1.008 1.12 1.00 61 - - - - C
A - - - 3.12 - 5.49 44 A
D - - - 9.51 - 40.11 61 D
A - - - 5.91 - 18.98 44 A
D - - - 16.50 - 67.79 60 D
DETAILS OF FOUNDATION OF TRANSMISSION LINE TOWERS NORMALLY USED
160
1:02:04 1:03:06
A 4.70 4.83 4.94 31.55 32.41 43.37 4.83 0.56 35.38 110
B 5.30 5.58 5.88 36.60 38.60 40.70 6.94 0.90 59.74 118
Normal Wet
C 7.27 49.46 8.16 1.06 73.01 212
A 6.82 7.22 7.59 45.50 47.67 49.85 6.69 0.9 52.71 166
Partially B 6.93 7.65 8.50 47.20 51.80 56.60 9.21 1.30 82.85 242
Submerged
C 12.23 75.14 10.60 1.49 99.15 303
A 10.42 10.98 11.54 64.40 67.02 69.63 8.49 1.87 71.27 218
Fully B 11.70 12.90 14.20 72.30 78.00 83.90 11.79 1.75 108.40 341
Submerged
C 13.60 109.60 384 13.37 1.97 127.80 421
Dry Soft B 3.98 4.25 4.55 9.00 10.00 11.10 2.49 8.57 41
Rock
C 6.47 6.72 6.59 18.03 18.52 19.49 2.68 9.65 41
A 12.25 13.00 14.36 105.50 192.50 116.50 34 12.17 1.86 101.00 308
Wet Black B 14.36 15.20 14.62 116.50 1223.70 131.00 39 16.21 2.52 151.59 515
Cotton C 18.10 163.00 39 18.30 2.83 178.02 651
A 6.37 17.88 25
Submerged B 7.81 0.38 24.32 41
Fissured
C 7.95 35.93 194
161
Rock (SFR)
B 8.54 66.64
Normal Wet
C 10.50 10.93 10.93 78.64 81.12 81.12 9.41 1.22 92.06 260
A 1.49 1.31 43
B
Hard Rock
C 2.66 2.48 83
A 9.96 34.90 51
Submerged B 12.56 62.06 61
Fissured
C 17.95 72.21 61
163
Rock (SFR)
D 5.46 41.28 7.820 60.550 12.672 98.40 9.37 1.48 109.44 492
A 4.82 33.93 5.910 41.990 7.816 56.60 6.14 0.76 50.63 167
D 11.60 85.64 16.720 111.080 19.016 197.40 990.84 17.34 2.66 187.13 806
A 9.60 59.69 9.520 61.250 8.792 86.10 427.52 9.11 1.12 71.29 226
D 20.46 128.86 24.870 146.110 24.308 256.70 1354.70 21.07 3.43 236.50 1270
A 14.94 80.14 18.680 94.170 11.842 118.20 580.56 11.88 1.53 94.25 297
D 29.28 162.53 39.910 196.020 30.848 328.90 1793.20 26.67 4.25 289.30 1409
220 kV SC (S.A.E Design) 220 kV DC KEC Design 220 kV DC L&T Design 220 kV DC Kalpatharu Design
BASIC
FDN TYPE TOWER CONC CONC (in CMT)
EXCA REINF CONC EXCA REINF CONC EXCA REINF EXCA REINF
EXTINS (in CMT) (in CMT) (in kg)
(in CMT) (in CMT) (in kg) (in CMT) (in CMT) (in kg) (in CMT) (in kg)
1:02:04 1:03:06
A 2.09 1.90 46
B
Hard Rock
C 2.53 2.34 55
A 10.98 36.32 53
Concrete Mix.
Type of Soil/ (in CMT/Twr) Earth Exvn. Steel Re inf (in
Tower Type
Foundation (in CMT/Twr) kg/Twr)
M20 1:3:6
MB - - - -
Normal DRY
MC 21.0 2.05 150 1612
MB - - - -
Normal WET
MC 40.0 4.04 280 2700
Partially Sub- MB - - - -
Merged MC 45.08 4.60 315 3136
Fully Sub- MB - - - -
Merged MC 44.28 4.60 315 3136
Wet Black MB - - - -
Cotton MC 52.76 5.40 365 3728
Dry Fissured MB - - - -
Rock MC 39.00 4.04 215 2828
Concrete Mix.
Type of Soil/ (in CMT/Twr) Earth Exvn. Steel Re inf
Tower Type
Foundation (in CMT/Twr) (in kg/Twr)
M20 1:3:6
MB - - - -
Normal DRY
MC 32.8 3.2 225 2856
MB - - - -
Normal WET
MC 58.9 6.0 390 5100
Partially Sub- MB - - - -
Merged MC 66.7 6.8 450 5832
Fully Sub- MB - - - -
Merged MC 75.0 7.7 510 6224
Wet Black MB - - - -
Cotton MC 76.0 7.7 510 6468
Dry Fissured MB - - - -
Rock MC 58.0 6.0 320 4872
Concrete Mix.
Type of Soil/ ( in CMT/Twr) Earth Exvn. Steel Re inf
Tower Type
Foundation (in CMT/Twr) (in kg/Twr)
1:2:4 1:3:6
MA 3.53 0.40 39 82
MA
MB
Normal WET
MC
MD
MA
Wet Black MB
Cotton MC
MD
MA 6.12 0.76 33 82
Type of Soil/ Concrete Mix. (in CMT/Twr) Earth Exvn. Steel Re inf
Tower Type
Foundation (in CMT/Twr) (in kg/Twr)
1:2:4 1:3:6
MA - - - -
MB - - - -
Normal DRY
MC - - - -
MD - - - -
MD - - - -
MD - - - -
MA - - - -
Fully Sub- MB - - - -
Merged
MC - - - -
MD - - - -
MA - - - -
Wet Black MB - - - -
Cotton MC - - - -
MA - - - -
Submerged MB - - - -
Fissured Rock MC - - - -
Concrete Mix.
Type of Soil / (in CMT/Twr) Earth Exvn. Steel Re inf
Tower Type
Foundation (in MT/Twr) (in kg/Twr)
1:2:4 1:3:6
DA - - - -
Hard Rock
DB & DE 65.93 - 93.26 3141
Hard
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Rock
Hard
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Rock
Hard
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Rock
Hard
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Rock
Hard
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Rock
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Tower Type NDS Wet PS FS WBC DFR SFR PSFR Cmtr Cmtr kg
Tower Type NDS PSS FSS WET WBC DFR SFR Cmtr Cmtr kg
Tower Type NDS PSS FSS WET WBC DFR SFR Cmtr Cmtr kg
Tower Type NDS PSS FSS WET WBC DFR SFR Cmtr Cmtr kg
Tower Type NDS PSS FSS WET WBC DFR SFR Cmtr Cmtr kg
Tower Type NDS PSS FSS WET WBC DFR SFR Cmtr Cmtr kg
Tower Type NDS PSS FSS WET WBC DFR SFR Cmtr Cmtr kg
Tower Type NDS PSS FSS WET WBC DFR SFR Cmtr Cmtr kg
A NT /+3/+6/+9 HR
DD +6/ +9
1138.63 15.66 152.31 12258.78
HR
DD+18 +25
434.15 5.72 59.35 4324.71
i Station structures Tower - 2T1 with peak No. 1.502 0.076 1.578
ii Station structures Tower - 2T2 without peak No. 1.272 0.053 1.325
i Station structures Tower - 1T1 with peak No. 0.908 0.044 0.952
iii Station structures Tower - 1T2 without peak No. 1.020 0.066 1.086
i Station structures Tower - 6T1 with peak No. 0.891 0.041 0.932
ii Station structures Tower - 6T2 without peak No. 0.732 0.042 0.774
iii Station structures Tower - 6T3 with peak No. 0.865 0.047 0.912
i Station structures Tower - 3T1 with peak No. 0.348 0.017 0.365
1 Isolator
a 220 kV Isolator
b 110 kV Isolator
c 66 kV Isolator
d 33 kV Isolator
2 Current Transformer
4 Surge Arrestors
As per
Columns out of 8.0 metre Length RCC pole of
i No. ESCOM
working load 115 kg (using TOR Steel)
SR
Beam out of Channel 100 x 50 with
D arrangements for stringing power conductor on
11 kV side
F Mounting Structures