You are on page 1of 23

POWER PLANT

IDENTIFICATION SYSTEM
KRAFTWERKS-KENNZEICHNUNGS-SYSTEM (KKS)

Export Classifications
AL:N ECCN:EAR99
POWER PLANT IDENTIFICATION SYSTEM

KKS Basics

Identification of:
Plants

Systems

Equipments

Signals
Protection notice / Copyright notice

Page 2 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS - CATEGORIES OF KKS CODE

• Process-related identification
Identification of systems and items of equipment according to their
functions in mechanical, civil, electrical and I&C (Instrumentation
and Control) engineering.

• Mounting location – identification


Identification of mounting locations of electrical and I&C equipment
in mounting units such as cabinets, panels and consoles.

• Topographic location – identification


Identification of topographic allocations in structures, floors, rooms
and enclosures

Protection notice / Copyright notice

Page 3 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS - PROCESS RELATED IDENTIFICATION

FID SID
11MBY10CS901.XQ01
Function Identification Code (FID) – Signal Identification Code (SKZ/SID) –

the unique identification of a component the unique identification of a signal defined


or function plan (logic). on a function plan.

Protection notice / Copyright notice

Page 4 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS - PROCESS RELATED IDENTIFICATION

1 2 MBP 13 AA 001 _ XB 01 -> practical example


-> systematics: N = number
A/N N AAA NN AA NNN A AA NN A = character

Signal Serial Number


Signal Identification Code

Equipment Redundancy (Optio


Equipment Serial No.
Equipment Identification Code
System Area Serial No.
System Identification Code
Unit Code
Plant Code
Protection notice / Copyright notice

Page 5 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

 Plant Identification: code with two numbers

1 2 MBP 13 AA 001 _ XB 01
Example: Plant with 4 gas turbine units:
Plant Code (here plant 1)
identifies largest grouping of PLANT /
UNIT
plant equipment. UNIT
CODE
The plant can include multiple 00 STATION
generating sets and common
systems 10 GENERATING UNIT #1, COMMON
SYSTEMS
Unit Code (here: Block 2) 11 GENERATING UNIT #1, GAS TURBINE #1
identifies the specific
12 GENERATING UNIT #1, GAS TURBINE #2
generating unit within the
plant. 20 GENERATING UNIT #2, COMMON
SYSTEMS
21 GENERATING UNIT #2, GAS TURBINE #1
22 GENERATING UNIT #2, GAS TURBINE #2
Protection notice / Copyright notice

Page 6 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

 System Identification: Code with 3 characters and 2 numbers.

1 2 MBP 13 AA 001 _ XB 01

 Major system:  Sub group of major  Individual System of major

Numbering
system: system:
o M – Main Machine Set
o MA – Steam Turbine o MAA – HP Steam Turbine
o H – Steam Generation
o MB – Gas Turbine o MBD – GT bearing
o E – Fuel Delivery
o MK - Generator o MBV – GT lubricant
o L – Steam-Water-Cycle
system

Protection notice / Copyright notice

Page 7 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

 System Identification

… 41

… 31

… 52
… 42
… 21
… 43
… 10 … 30 … 50
… 22
… 44
… 23

… 51
10 20 30 40 50

Protection notice / Copyright notice

Page 8 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

 System Identification

12
20

11

25

Protection notice / Copyright notice

Page 9 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

 Equipment identification: code of two letters and three numbers

1 2 MBP 13 AA 001 _ XB 01

component group equipment unit code component code


A/B = mechanical AA - valve, dampers, etc.
component AP - pumps
C = direct measuring CE – electrical measurement
circuit
CF – flow measurement
D = control loop
CP – pressure measurement, etc.
E = analog and binary
signal conditioning EC – sub group control
(SGC)
EE – sub loop control (SLC)

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

 Equipment identification : component code

valves (AA)
001-100 valves in main pipes
101-190 control valves
191-199 safety valves
301-399 shut off valves for measurements
401-499 drain valves
501-599 vent valves
601-699 dosing valves and valves in sampling lines
pipes (BR):
001-190 main pipes
191-199 inlet and discharge pipes to safety valves
301-399 pipes to pressure measurements
401-499 drain lines
501-599 vent lines
601-699 sampling and dosing lines

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – FID

 Equipment identification : component code

measurements (C)
001-199 binary and analog measurements
201-299 for testing automatics
401-499 performance test measurements
501-599 local measurements
901-999 combined measurements

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID

 Signal identification: code of two letters and two numbers

1 2 MBP 13 AA 001 _ XB 01

 first letter  second letter Signal number

X – indication of origin XQ – analog signal

Y – indication of the usage of ZQ – linked analog signal


signals. XS – functional group control step signal
Multi usage possible.
XH – binary limit signal that is derived
Z – indication for linked from analog process signal
signal
ZV – linked security or alarm signal
YP – supervisory control signal

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS - SID

Examples

XM20

ZV23
XM20

XM20

X-signals Link Z-signal


(origin) (linked signal)

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number –ACTUATOR

XB01

XB51

XB02

XB01 – feedback OPEN


XB51 – feedback NOT OPEN XB02 – feedback CLOSE

XB52 – feedback NOT CLOSE


Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number - MOTOR/PUMP

XB01

XB02

XB01 – feedback ON

XB51 – feedback NOT ON


XB02 – feedback OFF
XB52 – feedback NOT OFF

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number – ASMON

XH01
XH03

XH03 – limit value > MAX2

XH53 – limit value < MAX2


XH01 – limit value > MAX1
XH51 – limit value < MAX1
XH52 – limit value < MIN1
XH02 – limit value > MIN1
XH54 – limit value < MIN2
XH04 – limit value > MIN1
Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number –STEP

XS02

XS01 – command step 01

XS02 – command step 02

XS03 – command step 03

XS04 – command step 04

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number –SERVO

XC01

XC02 XC52
XC11

XC12

XC01 – feedback OPEN XC11 – feedback CLOSED LOOP (CL)

XC51 – feedback NOT OPEN XC12 – feedback OPEN LOOP (OL)

XC02 – feedback CLOSE Protection notice / Copyright notice


XC52 – feedback NOT CLOSE
Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number – CONTINUOUS CONTROL (CCTRL)

XC01
XC02

XC52

XC11

XC12
XC01 – feedback OPEN
XC11 – feedback CLOSED LOOP (CL)
XC51 – feedback NOT OPEN
XC12 – feedback OPEN LOOP (OL)
XC02 – feedback CLOSE Protection notice / Copyright notice
XC52 – feedback NOT CLOSE
Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number – PRESEL

XA31 – preselection SEL1


XA31
XA32 – preselection SEL2
XA33 – preselection SEL3
XA34 – preselection SEL4
XA32

XA33

XA34

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99
KKS – SID: Signal number – SLC

XA41

XA42

XA41 – SLC ON

XA42 – SLC OFF

Protection notice / Copyright notice

Page 2011-03
Export Classifications
E S SF REU 444 AL:N ECCN:EAR99

You might also like