For the latest prices, please check AutomationDirect.com.

CLICK I/O Module Specifications

C0-04DA-1
4-Channel Analog Current Output Module
4-channel analog current sourcing output module, 12-bit resolution,
range: 4-20 mA. External 24VDC power required, removable
Output Specifications
terminal block included (replacement AutomationDirect p/n C0-8TB).
Outputs per Module 4
Output Range 4-20 mA (source)
Resolution 12-bit, 3.9 uA per count
Wiring Diagram Current sourcing at 20mA max. (1 com-
Output Type mon)

C0-04DA-1
Output Value in Fault Mode Less than 4mA
4-20mA
0-600 at 24VDC; minimum load: 0
Load Impedance 32° to 131°F (0° to 55°C) ambient temp.

Maximum Inductive Load 1 mH


Allowed Load Type
OUTPUT

Grounded
Maximum Inaccuracy ±1% of range
Ch1 Max. Full Scale Calibration ±0.2% of range maximum
Load Error (Including Offset)
Max. Offset Calibration Error ±0.2% of range maximum
Ch2
±75 PPM/°C maximum full scale calibra-
Load Accuracy vs. Temperature tion change (±0.005% of range/°C)
CH1
Ch3 All ‘0V’ Max. Crosstalk at DC, 50/60Hz -72dB, 1 LSB
CH2 terminals are
Load
CH3 connected
Linearity Error (End to End) ±4 LSB max., (±0.1% of full scale)

CH4 internally. Output Stability and ±2% LSB after 10 minute warmup period
Repeatability typical
Ch4 0V
Load Output Ripple ±0.1% of full scale
0V
0.3 ms maximum, 5µs min. (full scale
0V Output Settling Time range)
0V All Channel Update Rate 10ms
0V Max. Continuous Overload Outputs open circuit protected
24VDC + 24V 1800 VAC applied for 1 second (100%
Power –
0V Field to Logic Side Isolation tested)
Supply
Type of Output Protection Electronically limited to 20mA or less

Output Signal at Power Up and 4mA


Power Down
NOTE: When using this module you must also use CLICK External VDC Power Required 145mA
programming software and PLC firmware version V1.40 or later. Base Power Required (24VDC) 20mA
Terminal Block Replacement AutomationDirect p/n C0-8TB
Weight 2.9 oz (82g)

ZIPLink Pre-Wired PLC Connection


Cables and Modules for CLICK PLC

11-pin connector cable


ZL-C0-CBL11 (0.5 m length)
ZL-C0-CBL11-1 (1.0 m length)
ZL-C0-CBL11-2 (2.0 m length)

ZL-RTB20 20-pin feed-


through connector module

www.automationdirect.com/click-plc CLICK PLCs tCLP-119

You might also like