3300/15
DUAL VIBRATION
MONITOR
•
MAINTENANCE MANUAL
•.
B E N T LY r \
N E VA D A \ . )
• db
NOTICE
READ THE FOLLOWING BEFORE INSTALLING OR OPERATING EQUIPMENT.
Bently Nevada Corporation h a s a t t e m p t e d t o i d e n t i f y areas o f r i s k c r e a t e d
by improper installation a n d / o r operation o f t h i s product. T h e s e a r e a s o f in—
formation o r e n o t e d a s WARNING o r CAUTION f o r y o u r p r o t e c t i o n a n d f o r t h e
safe a n d e ff e c t i v e operation o f t h i s equipment. R e a d a l l i n s t r u c t i o n s b e f o r e
installing o r operating t h i s p r o d u c t . P a y particular a t t e n t i o n t o t h o s e a r e a s
designated b y t h e following symbols.
ANWARNING C.M710H
High voltage present
could cause shock
burns o r death Machine P r o t e c t i o n C o u l d
Be Discontinued
Do not touch exposed
wires o r terminals
SYMBOLS •
Special s y m b o l s a r e u s e d i n t h e manual t o illustrate specifics i n t h e step—by—
step process. F o r example:
etil$017 a
660
II •
0
1SID2 •
Dual Vibration Maintenance 8 0 1 7 7 - 0 1
• FOREWORD
This document is for maintenance personnel who install and maintain the 3300 Monitoring System. T h e procedures
presented should aid service personnel to maintain a Dual Vibration Monitor in a typical 3300 System.
RELATED DOCUMENTS
• 3300 System Overview, 80171
No part of this publication may be reproduced, transmitted, stored in a retrieval system nor translated into any human
or computer language, in any form or by any means, electronic, mechanical, magnetic optical, chemical, manual, or
otherwise, without the prior written permission of the copyright owner,
iii
80177-01 D u a l Vibration Maintenance
Blank Page
iv
Dual Vibration Maintenance 8 0 1 7 7 - 0 1
• CONTENTS
TITLE S E C T I O N
MONITOR FUNCTIONS 2
MONITOR OPTIONS 3
PROGRAMMABLE OPTIONS 4
OK 5
BYPASS 6
ALERT 7
DANGER 8
MONITOR RANGES 9
1
0
SELF TEST 1 4
DISASSEMBLY PROCEDURE 1 5
FRONT PANEL R E M O VA L 1 6
• EXPANDER BOARD I N S TA L L AT I O N / R E M O VA L 2 5
80177-01 D u a l Vibration Maintenance
CONTENTS (Continued)
TITLE S E C T I O N
CHANNEL BYPASS 2 6
DANGER BYPASS 2 7
CALIBRATE CHANNEL 3 9
TEST OK LIMITS 3 0
SPECIFICATIONS 3 3
SCHEMATICS A N D DRAWINGS 3 4
vi
Dual Vibration Maintenance 80177-01
• 1 DUALVIBRATIONMONT
IORSYSTEM
1.••=.••••••
3300/15
VIBRATIONMONT
I OR
0°0 i t di
®6® 6
73
—a-— —
3300 RACK
- — -L
S2 — — 2 5
P — P
— —
A— - — A
0— — —
P _ - _ - r PROXIMITOR
f _ _ E
— _
•
—1
CHANNEL A...-----v.
PROXIMITOR PROBE
o—
A0
0 DANGER
ALERT
0
013
0PE J
:=E
CHANNEL B
PROBE
0 BYPASS 0 RF
SHAFT
CHANNEL A CHANNEL B
RECORDER RECORDER
/7 KC
OUTPUT
LI OUTPUT
DANGER A L E R T 0
• 1 S I D3
1
80177 01 D u a l Vibration Maintenance
MONT
IORFUNCTO
I NS
RADIAL VIBRATION - Radial vibration is defined as shaft dynamic motion in a direction perpendicular to the shaft
centerline. The Dual Vibration Monitor displays vibration values for two channels (Channels A and B).
PROBE GAP VOLTAGE - Probe gap is measured as a negative dc voltage that is directly proportional to the gap
distance between the face of a proximity probe and the surface being monitored. Probe gap voltage for each chan-
nel is displayed on the front panel meter by pressing the GAP switch.
OK - When the Proximitor output voltage is within its upper/lower OK voltage limits, the transducer is defined as
OK. The OK detection circuit controls the channel OK LED and the monitor relay drive to the OK relay.
OK RELAY - The OK Relay is located on the Power Input Module. Every channel in the rack must be OK or
bypassed to energize the OK Relay.
TIMED OK/CHANNEL DEFEAT - Timed OK/Channel Defeat prevents faulty transducer wiring from causing false
alarms. If the probe input signal level on a given channel is not within upper/lower limits, that channel OK LED
goes off, the BYPASS LED goes on, the channel is disabled, and the OK- Relay deenergizes. I f the channel input
signal level is restored within the upper/lower OK limits for 30 seconds, the channel OK LED will start flashing at 1
Hi to indicate the OK state is restored, the BYPASS LED goes off and monitoring is enabled. The RESET switch
on the front panel of the System Monitor must be pressed to stop the OK LED from flashing (it remains on). If the
channel remains in the NOT OK state, a Channel Bypass switch on the monitor circuit board can be set to put the
channel "out of service". The monitor can then be operated as a single-channel monitor. Without this feature, the
OK Relay could not be reactivated. In the Timed OK/Channel Defeat and Channel Bypass modes, there is no
recorder output and the meter registers zero.
ALARM - Pressing the ALERT or DANGER switch on the front panel of the monitor causes the corresponding
Alert (first-level alarm) or Danger (second-level alarm) alarm setpoints on each channel to be displayed on the front
panel meter. A L E R T and DANGER LEDs light when the vibration signal level exceeds preset levels for the
selected time delay, and appropriate Alert and Danger alarm relay contacts are activated. Voting logic options
determine when the Danger alarm relay contacts are activated.
FIRST OUT - Separate First Out circuits exist for Alert and Danger alarms. A monitor with First Out option
selected flashes a channel alarm LED if that channel was the first channel in the rack to go into alarm. Pressing the
RESET switch acknowledges the First Out condition. This allows the next channel in the rack that goes from non-
alarm-to-alarm condition to indicate First Out by flashing its alarm LED.
ALARM RELAYS - Monitor alarms can be programmed for either latching or nonlatching mode. I n the nonlatching
mode, the alarm resets automatically when the alarm no longer exists. I n the latching mode, the alarm condition
must be reset manually by pressing the RESET switch on the front panel of the System Monitor (or by closing
external Reset contacts). The alarm will not reset if the alarm condition still exists.
DANGER BYPASS - For maintenance functions, a DANGER BYPASS switch on the monitor circuit board is set to
inhibit the Danger relay drive. This function turns on the BYPASS LEDs. Other front panel functions arc not
effected. This function can be disabled using a jumper within the monitor.
BUFFERED OUTPUT - The Channels A and B coaxial cable connectors on the front panel of the monitor and
terminals on the Signal Input Relay Module provide buffered signals from the respective channel transducers.
These connectors can be used for connection of external equipment.
TRIP MULTIPLY - The Trip Multiply function multiplies set points by 2X or 3X in response to an external contact
closure through terminals on the Power Input Module. The front panel meter and recorder outputs could saturate
in this mode.
RECORDER OUTPUTS - Depending on the option selected, the recorder output levels proportional to measured
vibration are either 0 to -10 Vdc, +1 to +5 Vdc, or +4 to +20 mA.
SELF TEST - The monitor has three categories of self test: cyclic, power up, and user invoked.
• Power up self test is performed automatically each time the monitor power is turned on. A series of basic
tests and transducer OK tests are performed. upon completion of the tests, if no errors, the monitor will
perform timed OK/Channel Defeat and monitoring will resume in 30 seconds.
• Cyclic self tests is performed automatically during monitor operation. Errors encountered during cyclic tests
disable the monitor, and flash a lcd bargraph error code. Should the error be intermittent the monitor will
return to operation, but the error codes arc stored for retrieval during user-invoked self tests. Stored error
codes are indicated by OK LED's flashing at 5 HZ provided that the channel is OK
• User invoked test performs power up self test and allows error messages stored during cyclic tests to be read
and cleared. Stored errors arc annunciated by flashing the OK LEDs at 5 HZ and displaying the error codes
on the front panel LCD bargraph.
+3203
2
Dual Vibration Maintenance 80177-01
3 MONT
IOROPTIONS
D U A L V I B R AT I O N M O N I T O R
PART NUMBER F U L L SCALE RANGE T R A N S D U C E R INPUT A L A R M RELAY A P P R O V A L S B A R R I E R S USED T R I P MULTIPLY
3300/15 AA C BB C D D EE FF
0 1 = 0 - 3 MILS p k - p k 01=7200 PROXIMI TOR 00= NONE 00- N O 00-NONE
00=NONE
0 2 = 0 - 5 MILS p k - p k 200 m V / M I L 01=5A EPDXY 01- G S A 01= YES 01=24 TRIP MULTIPLY
0 3 = 0 - 1 0 MILS p k - p k 0 2 = 3 0 0 0 PROXIMITOR SEALED 02 - BASEEFA 0 2 - 3 X TRIP MULTIPLY
0 4 = 0 - 1 5 MILS p k - p k 200 m V / M I L (MUST 0 2 = 5 A HERMETI- 03-CITY OF L A
0 5 = 0 - 2 0 MILS p k - p k BE USED WITH POWER CALLY SEALED
11 = 0 - 1 0 0 MICROMETRES p k - p k SUPPLY PROGRAMMED 03=0UAD RELAYS
1 2 = 0 - 1 5 0 MICROMETRES p k - pk TO - 1 8 V d c ) EPDXY SEALED
1 3 = 0 - 2 0 0 MICROMETRES p k - p k
1 4 = 0 - 4 0 0 MICROMETRES p k - p k
1 5 = 0 - 5 0 0 MICROMETRES p k - p k
4 PROGRAMMABLEOPTO
I NS
PROGRAMMABLE OPTIONS
• 10435
3
80177-01 Dual Vibration Maintenance
5 OK
• OK •
0 DANGER 0
AOALERT O B
O BYPASS 0
LLD I) S P L AY OK E L A Y
CONDIT ON
A B DANE*
CHANNEL.. A A N D B I N OPERATING ON
• O K •
RANGE.
0 OK • RESPECTIVE CHANNEL A O R B
TRANSDUCER I N N O T OK CONDITION, OFT*
• OK 0 OR BYPASSED. *
,----,,,,
( . * OK _,9/ CLASHING A T 1 H z = TRANSDUCER
,s'-L.-'. — HAS BEEN N O T OK SINCE L A S T RE -- 1q,i
(kTk 0 K •
-..-.-:::::,
/T---•
• O K (0.2*
i
4
Dual Vibration Maintenance 80177-01
• 6 BYPASS
_
0 - 0
0 OK 0
0 DANCER 0
AOALERT O B
• BYPASS •
LED DISPLAY
CO\ DI TI Ofd
A B
• • B Y PA S S •
o MONITOR IN DANGER BYPASS MODE
o SYSTEM I N POWER U P MODE
o USER INVOKED SELF TEST I N
PROGRESS
o TIMED O K CHANNEL DEFEAT
o BOTH CHANNEL BYPASS
0 B Y PA S S • o CHANNEL A O R B BYPASSED
o TIMED O K CHANNEL DEFEAT
• B Y PA S S 0
• B Y PA S S 0
• 1S6D7
5
80177-01 Dual Vibration Maintenance
7 ALERT
0 OK 0
0 DANGER 0
A• ALERT • B
0 BYPASS 0
,r1
ALERT
1_1-1) f)1`PLA`i'
CONDITION RELAY DRIVE.
A B
• ALERT 0 ON
- - — EITHER CHANNEL A OR B (OR
0 ALERT • BOTH) H A S EXCEEDED ALARM ON
— LEVEL. (SEE 1 2 )
• ALERT • ON
/...,,,,•-• FIRST OUT CONDITION FOR
O ALERT L I ) RESPECTIVE A OR B CHANNEL ON
THAT HAS EXCEEDED ALARM
LEVEL. TWO CHANNELS M AY
,----- INDICATE. FIRST OUT FOLLOWING
(ei0 ALERT 0 ON
. SELF TEST. *
25701
6
Dual Vibration Maintenance 80177-01
• 8 DANGER
0_ I
O ac 0
• DANGER •
A 0 ALERT 0 B
O BYPASS 0
_F11
• i l l ) DISPLAY
CONDITION
DANGER RELAY
uppir _.___..
A B OR VOTING AHD VOTING*
-
• DANGER 0 ON OFF
- EITHER CHANNEL A OR B ( O R
0 DANGER • BOTH) H A S EXCEEDED ALARM ON OFF
LEVEL. (SEE 13 )
• DANGER • ON ON
. .
• FIRST OUT CONDITION FOR
0 DANGER 0 RESPECTIVE A O R B CHANNEL ON OFF
— THAT HAS EXCEEDED ALARM
LEVEL. TWO CHANNELS M AY
INDICATE FIRST OUT FOLLOWING ON OFF
)DANGER 0 SELF TEST.**
• 2SBD1
7
80177-01 Dual Vibration Maintenance
9 MONT
IORRANGES
3300/1f;
- -
0 1 - 0 - 3 MILS p k - p k 1 -
C 2-0
0(0)1 -AV
02 0 - 5 MILS p k - p k -
-
03:, 0 - 1 0 MILS pk--pk E
-
0 4 - 0 - 1 5 MILS p k - p k [60-: -GO
5 7 5
= 0 - 7 0 MILS p k - - p k
P
1 2 - 0 - 1 5 0 MICROMETRES p k - p k
P
1,3-n 0- 200 MICROMEIRLS p k - p k A20-
14---0 - 4 0 0 MICROMETRES p k - p k
15 0 - 5 0 0 MICROME IRLS p k
0- -0- - 0 G.L - 0 - - 0
279D1
8
Dual Vibration Maintenance 80177-01
• 10 READCHANNELVIBRATION
MONITOR CONTINUOUSLY INDICATES MEASURED VIBRATION VALUES FOR CHANNELS A A N D B
•
PROBE
VIBRATION
SHAFT
• 2 5 1 0 D 1
9
80177-01 Dual Vibration Maintenance
11 READGAPVOLTAGE
1. P R E S i CAP SWITCH A N D READ GAP VOLTAGE FOR BOTH CHANNEL A A N D
CHANNEL L3 O N METER USING CENTER METER SCALE.
C) BYPASS 5
DANGER
GAP 0 ,
BUFFEREDTRANSDUCERSB
0
( I IANNI l A 'I.,HAF
CHANNEL. 13
2S11D1
10
Dual Vibration Maintenance 80177-01
• 12 READALERTSETPOINTLEVELS
1. PRESS ALERT SWITCH A N D READ ALERT SETPOINTS (FOR BOTH CHANNEL A A N D
B) ON METER SCALE.
0 BYPASS 0
DANGER ALERT
A
BUFFEREDTRANSDUCERS
0
• 13 READDANGERSETPOINTLEVELS
1PRESS DANGER SWITCH A N D READ DANGER SETPOINTS (FOR BOTH CHANNEL A
AND B ) ON METER SCALE.
• 2 5 1 2 D I
11
80177-01 Dual Vibration Maintenance
14 SELFTEST
THE. MONITOR H A S THREE LEVELS OF SELF TESTS:
UAN
A
BUFFEREDTRANSDUCERS
0
12
Dual Vibration Maintenance 80177-01
• 14 SELFTEST[CONTI
INI IIATE USER INVOKED TE`..)I. B Y SHORTING ACROSS I W O SEL F T E S T ( S I )
O a
o aim 0
0 MACHINE PROTECTION WILL B E
0 o n 0
o o LOST FOR DURATION O F TEST
0 BOOM
NBRA10NMONC
IR
_-
-
NOTE
ALTHOUGH BOTH COLUMNS ON
=-a BARGRAPH FLASH, ERROR CODE
IS ONLY THE SUM O F BARGRAPH
SEGMENTS DISPLAYED I N ONE
COLUMN. EXAMPLE SHOWS ERROR
CODE 6 .
0 OK 0
0 DANGER 0
A0 ALERT 0 1 1 o READ CODES ON LIST; STEP THROUGH EACH ERROR
0 BYPASS 0
•
DANCER
111
CODE= ON LIST B Y PRESSING A N D HOLDING ALERT
SWITCH FOR APPROXIMATELY 1 SECOND.
o A T THE END O F LIST, LCD BARGRAPH DISPLAYS A L L
SEGMENTS. T O REREAD LIST PRESS ALERT SWITCH. T O
CLEAR LIST FROM MEMORY, PRESS A N D HOLD DANGER
SWITCH FOR APPROXIMATELY 1 SECOND.
• BUFFERED
TRANSDUCERS
O
2514D2
13
80177-01 Dual Vibration Maintenance
14 SELFTEST[CONT]
.;300j15
ERROR CODE DESCRIPTION
NERA1101MOMIOR
2. ROM CHECKSUM H A S FAILED. *
; 3. EEPROM FAILURE NO.1. * *
4. [EPROM FAILURE NO.2; A D J U S T SET
POINTS. ( S E E I n A N D 0-1) * * *
I 2 - -II. - 2 1 5. -1-7.5/—vT NODE OUT OF TOLERANCE. * *
6 +vRi.i NODE OUT O F TOLERANCE. *4,
7. -1-.5v NODE OUT O F 1 OL FRANCE . * *
H. MVRIT NODE OUT O r TOLERANCE. *
_ 9. +- 7.5V NODE OUT OF TOLERANCE. * *
-
1111. M
10. + VRL NODE OUT OF TOLERANCE. * *
11. M V R E F / - 6 . 5 V NODE OUT O F TOLERANCE. * *
C,) OK 0 12. 5V/— 7. 5V NODE OUT O F TOLERANCE. * *
0 DANCER ( 2 ) 13. SCIC CLOCK FAILURE * *
A 0 ALERT 0 8 14. RAM FAILURE. *
C)BYPASS 0
15. IC U 4 OUTPUT DISAGREES WITH G A P VOLTAGE
VALUE. *
251403
14
Dual Vibration Maintenance 80177-01
• 15 DS
I ASSEMBLYPROCEDURE
1. LOOSEN SCREWS A N D PULL VIBRATION MONITOR FROM RACK.
C&U,v[lOhr_
MACHINE PRO TLC TION I S DIS—
CONTINUED WHILE MONITOR I S
REMOVED FROM RACK.
STANDOFF ( 4 PLACES)
SIDE
•
COVER
1
(-4
(-4 W 2
12211 P3 TP7
a
R6
w3 TP41 0
TP42 0
TP39 TciPto
W4Ili
tv1UNI TOR W5
mpg
FRONT R14
w6f
PANEL OTP40
TP25 a a a
W8
W9 ii
SW1 l C I TP14 1 p 5
r l TP18 CI w11 W 1 2 I
J3NO
ri
11
iP2 J 2 W15
a
W16
W14 EEOWI 7
AGND TP15
a
4 1111 2 5 1 5 0
15
80177-01 Dual Vibration Maintenance
16 FRONTPANELASSEMBLYREMOVAL
R6
1P39
U
FR14
Ell T0 40
V)
r � D TP14 T P 5
SA/1 O T P 1 8 0
D=C
RIBBON CABLE
CONNECTOR J 2
2516DI
16
Dual Vibration Maintenance 80177-01
• 17 t SIGNALINPUTRELAYMODULES
*WARNING
High voltage present
could cause shock
burns or death
Do not touch exposed
wires or terminals
• RELAYS— . . o 0 0 o
0 0 0 0
70000
0 0 0 0
0
VA I/O k Raw U1114.0 0
0 CHB
FOR FIELD 0 CIRCUIT BOARD
awz 11211
WIRING COO
REFER TO
I 2 JUMPL.R*
MONITOR ar IZ
Q
I( ALERT RELAY
MANUAL IN O U T
NORMALLY ENERGIZED W3 V V 4 , W 11
0
NORMALLY DEENERGIZED W4 ,W1'I W 3
JUMPER'
DANGER RELAY
IN O U T
NORMALLY ENERGIZED W2 W 1 ,W12
0
NORMALLY DEENERGIZED Vv1,W1 2 W 2
17
80177-01 Dual Vibration Maintenance
17 SG
I NALINPUTRELAYMODULES[CONT.]
•
.)\ WARNING
High v o l t a g e p r e s e n t
could c a u s e s h o c k
burns o r d e a t h
Do n o t t o u c h e x p o s e d
wires o r t e r m i n a l s JUMPERS
W4 A —F
SIC,NAL I N P U T R E L AY MODULE S
°,1;,1°,L
;'°i
I]
JUMPERS on m
00 3
0 0 OHO
W3 A D
g
JUMPERS
PEA AYE
W2,W1
CIRCUI T B O A R D
QUAD R E L AY S
•
xf(R K R I M HUNS
M
SIGNAL. INPUT/QUAD R E L AY CARD OPTION
mill o FOR H E L D
WIRING RELAY OPTIONS I N S T A L L R E M O V E
REFER T O
ALERT RELAYS W 2 , 3 C W 3 A , 4 c ,
I_ MONITOR
NORMALLY W 3 D , 4 D
off MANUAL DE—ENERGIZED
ALERT RELAYS W 3 A , 4 C W 2 , 3 C
NORMALLY W 3 D . 4 D
AIR ENERGIZED
41 *FOR INSTALLATION O F
lkif DANGER RELAYS W 1 , 3 { 3 W 4 ,,4f'
ETU AW RELAY MODULES, REFER
113 TO INSTALLATION MANUAL. NORMALLY W 4 A , 4 E
1IC
DE—ENERGIZED
11211
1:1 tp.) DANGER RELAYS W 4 B , F W 1 ,3B
NORMALLY W 4 A•
ENERGIZED
AIAMMAYMMIS
•
WI I I ( ) I IAD E L I A R S
18
Dual Vibration Maintenance 80177-01
• 18 N
I STALLEDPROGRAMMABLEOPTIONS
THE VIBRATION MONITOR I S SHIPPED WITH THE FOLLOWING OPTIONS INSTALLED:
N c\I
a a W2 TP17 0
F- W1 HH
I SEI TP3
•
❑ T P 7 C1
W3
TP41 0
P6
TP42 0
1-P39 TP10
❑ W4 J1
W5
P14 TP 9
G
-4- - 4 -
❑ TP40 CIIE2 a o_ W7
W8
V)
CID
TP25
0 0 0A A
C13
0 TP14 W9 g e CC
TP5 0 0 E
`,EW1 T P 1 8 W 11 W12 _OF
co
CC W16 J3 W 1 0
A
oA
TP2 EEC
10 0]
0 W15 > D W14
A EN D caTA W17
TP15
❑
19
80177-01 Dual Vibration Maintenance
19 FR
I STOUTA
, LARMDELAYSF
,REQUENCYRESPONSEOPTO
I NS
JU V 9ER
0 11N
LOC A 11ON S
I- II,`.1 01.,ij-
JUMPERS W16
w wol : 1
—Ir4.5TALLED REMOVED c
0 1.11A131.1:1) W160 22 D 6 [
ALARM 1I1ELAYS
JUMPERS
A 0 0
INSTALLED REMOVED
e JA
CO —
0 0.1 ; E C O N D - - W15B,C D0 0
W15
20
Dual Vibration Maintenance 80177-01
• 20 ALERTMODED
, ANGERMODED
, ANGERVOTINGOPTIONS
J U VI 9 :_-_-i-
O P T O \
L O C A T I O \ S
ALERT MODE
JUMPERS
A00
INSTALLED REMOVED Bo o
c oo --
o LATCHING W15D D;152
W15
o NON 22.2
---- W15D
LATCHING ____.
•
DANGER MODE
JUMPERS W16
i 4::,
INSTALLED REMOVED
o LATCHING W16B - - - oo c
000
o HON —
W16B
I ATCHING
DANGER VOTING
JUMPERS W16
INSTALLED REMOVED p 121 22:12i
o AND W16D - - - II '/1410 W
'
a OR W16D
• .3`20Di
21
80177-01 Dual Vibration Maintenance
21 RECORDEROUT,MONITOROKLIMITS,DANGERBYPASSSWITCH
+4 TO + 2 0 n i A
JUMPERS I N S TA _ L L M
__... ___W7A,C,E_,F______
W8B,C
W10A,B
r: W7
A MI
B OM
W8
a r
,30.1„
C Fr_ _4
W118.0 0 - ( 1 ;Z.,
• W9 D r F
E r• e'
W12A.-C,F,F A rar F 4?."-11 f
W12 B ' • 41,
i t TO 1:, Vic W11
JutAI,FRI) I f L D a
,,
6.;c7.
4A 91 1
0 TO - 1 0 Vdc
JUMPERS I N S TA L L E D
W-7[3,0
-----TV8D,F
* REMOVE A L L JUMPERS FROM W 7 , W 8 , W 9 , W 1 0 , W11, AND W 1 2
W9A, B
W11D,F THEN REINSTALL ACCORDING T O TA B L E
- - - - --------
W12B,D -
1
0 o
MONITOR O K LIMITS JUMPERS 00
•
OPTION
INSTALL REMOVE W4 4-V
3000 PROXIMI TOR W4 A, W5B W5 Li
W4B,W5A
._..---- - . _ ___ . . _
/ 7 0 0 PROXIMI1OR VIP), \W_,A W4A, W5B I c5-61
,--- -
DANGER JUMPERS
_
BYPASS SWITCH W20
OPTION INSTALL REMOVE
ENABLE W20 _ __
DI SABLE SW1
——— W20
352101
22
Dual Vibration Maintenance 8 0 1 7 7 - 0 1
• 22 REPLACEMETERSCALE
VERFIYMONT IORFULLSCALEOPTOI N(SEE 23
2.OS
BH
TO
AWN
IMN.ETERSCALEFROMREAROFMANUALANDN I SERTINFRONTPANELAS
NOTET: OENSURECORRECTFITTINGANDALG I NMENTT
, HEMETERSCALEMUSTBE
CUTFROMTHEPLASTC I SHEETEXACTLYALONGTHEMARKEDOUTLN I E.
METERSCALE
4
/111
3 T
IA
SPACERBAP
• //
/
/
// ///
/
// //
/
SLOT
/
/
/
/
/
//
VEIWROTATED
FORCLARTIY
MON TIOR
FRONT
PANEL
• 3S2?0 I
23
80177-01 Dual Vibration Maintenance
23 MONT
IORFULLSCALEOPTIONS
JUMPER LOCATIO\ c
____)
/- ____------_____----- -- , ..
._.../ 9_2 W2 .
W3' A B C D
r W W I I ) II 0 likil I 1151161131 ..,„ g
6- 6 A R ? l 1
CHANCING [ L IU C( :A I L '40F) I
REQUIRLS RE.CALIHRA - 0 0 EL 6aa6 6
-twirl 01- Boll I aNNEI-3 it,Y -00 F.
(SEE [-_-2A)
\ . { W6
6 oo
.o;oDBA
14,E
VA4'F
V O \ I T C R RHI.._L-SCALE OD I- ONS
JUMPERS INSTALLED*
U - - 3 MILS W2A, W2C, W3B, W3D, W6C, W6E
0 5 MILS W2A, W3B, W3D, W6(_:, W6L.
24
Dual Vibration Maintenance 80177-01
24 EXPANDERBOARDINSTALLATION/REMOVAL
REMOVE MONITOR FROM RACK A N D REMOVE SIDE COVER. ( S E E
J3 CONNECTOR --..
MONITORING I S DISCONTINUED
JUMPERS W H I L E MONITOR I S REMOVED
FROM RACK.
U
r-3
00
00 U
0 0
0 0 0 0
00 0
0
0
0
0 0 0 0
b 0 0
00
0 0
00
00
0
EXPANDER BOARD
0 0
00
0 0
0 0 0000
0 0
0 0
00
00
-6§ 00
ID
J3
.3S?4(11
25
80177-01 Dual Vibration Maintenance
25 ALARMSETPOINTADJUST
NOTE
SET POINTS CAN N O T B E ADJUSTED
WITH TRIP MULTIPLY INSTALLED A N D
AC1IVATED B Y CONTACT CLOSURE.
r) 0 3300/15
I ) c 3 3,100/DI
NBRhnCNIICNTOR
SW111MONA
BA
BB
DB
AA
AB
.„,<„,/\ O N OFF
.21r
SUPPLE01( ' a ( 0
• 0 M R 0B
1RP1,(t1f. Ao AIER1
0 BYPASS 0
(0
' 1/CiADJUSI`111"
L
I 1”11' A(1.1(I
® 0 )
(9) RII
KQIf K02 fiffIREDR
I ANSCOCR
IS
c) 0
352501
26
Dual Vibration Maintenance 80177-01
26 CHANNELBYPASS
SET BA (CHANNEL A BYPASS) OR BB (CHANNEL B BYPASS) SWITCH T O ON.
CORRESPONDING BYPASS LED GOES ON, OK LED GOES OFF, A N D AMPLITUDE GOES TO 0 .
caRproorm
MACHINE PROTECTION WILL
BE LOST WHILE CHANNEL
BYPASS I S ON.
NOTE
WHEN CHANNEL BYPASS I S SWITCHED ON,
CHANNEL ALARMS ARE CLEARED.
• ( -3 0 moo/is
4\8RA1ION
MON
TIOR
BA
'7 7 '
BB
DB
; 1 _
AA
AB
O
K •
0 BAKER 0
AO CRT 0 8
v i e MASS o p
BUFFEREDTRANSDUCERS
e
4111 3 T 2 1 ; 1 1 1
27
80177-01 Dual Vibration Maintenance
27 DANGERBYPASS
SET DB DANGER BYPASS SWITCH T O ON; BOTH CHANNEL BYPASS LEDs GO ON. DANGER
ALARM LEDs ON FRONT PANEL CAN GO ON B U T DANGER RELAY DRIVE WILL NOT B E
ACTIVATED IF A DANGER SET POINT I S EXCEEDED. SEE 1 3 T O READ DANGER
SET POINTS.
0 3300/15
NBRATO
I NICHIOR
4 r,
(:3A
BB
DB
AA
) AB
ON
,?.
0( 0
0 DANGER 0 r,
AO ALERT 0 GI
BYPASS�r •
111
I• f l c J
NOTE
DANGER BYPASS CAN
BE DISABLED B Y DAN—
RIPRiftfRANTUCERS GER BYPASS DEFEAT.
0 (SEE[1 ).
I
3S27DI
28
Dual Vibration Maintenance 80177-01
• 28 TESTCHANNELALARMS
1 PROXIMITOR
tt. WARNING
High voltage present
could cause shock
burns o r death
Do not touch exposed
wires o r terminals
• PROBE
;SHAFT
SIGNAL
INPUT RELAY
MODULE
4S2&)1
29
80177-01 Dual Vibration Maintenance
28TESTCHANNELALARMS[CONY.]
() 0 3300/15
WPMNCHKR
7 "*"
-
1r - - ; : 2 i
5. INCI-ZEASE FUNCTION GENERATOR AMPLITUDE PA S T
ALERT SET POIN T. LEVEL A N D VERIFY THAT ALERT LED
GOES ON (FLASHING I F FIRST OUT OPTION).
0 OK 0
o NW 0
VI *IF i ' H A I A l l PT RELAY CHANGED STATE. lir • CRT 0 B
0 WASS 0
BORED1RANTUIRS
7. PRESS RESET S W I T C H A N D VERIFY THAT 0
ALERT LED REMAINS ON STEADY.
30
Dual Vibration Maintenance 80177-01
• 28 TESTCHANNELALARMS[CONT.]
11. PRESS RESET SWITCH. VERIFY ALERT A N D NIGER L E D S REMAIN O N A N D STE ADY.
0 33C0/01
Snit11
. uonuc
SOFRESOK
0
TPJPWIRY
t5E/ FIVICIAD.USI
Li
OW
(.0)) RESU
KO1 X 0 2
4T28D3
31
80177-01 Dual Vibration Maintenance
29 CALB
I RATECHANNEL
1 PROXIMITOR
cwrflom]
PRcr..1-:DuRE coot I) E XCEEDALARM SET
POIN r LEVLLS CAUSING ALARMS TO
ACTIVATE. T H I F. , COULD RESULT IN
RELAY CONTACTS CHANGING STATE.
(SEE DANGER BYPASS 127 )
0 XDCR1/0 k WORDIFRIktikS
CHA C H B
A\ WARNING
High voltage present
could cause shock
burns o r death
Do not touch exposed
IIlfll wires or terminals
eu
C011
RFC
PROBE
/SHAFT
A
INPUT RELAY
MODULE
4`,2901
32
Dual Vibration Maintenance 80177-01
• 129 1 CALIBRATECHANNEL[CONT.)
4. LOOSEN RETAINING SCREWS, SLIDE FRONT PANEL T O RIGHT, A N D MEASURE PRO-
PROTIONAL SIGNAL OUTPUT A T APPROPRIATE SIGNAL OUTPUT TEST POINTS
(A O R B ) .
PROPORTIONAL OUTPUT —
GAIN POTENTIOMETER
0 a0/15
V3
IRAPCNARATOR / 4 /
GAIN A( GA )
POTENTIOMETER
CHANNEL A
TEST POINT
GAIN B ( GB )
POTENTIOMETER
33
80177-01 Dual Vibration Maintenance
30 TESTOKLIMITS
1. CONNECT MULTIME TER 7 0 CHANNEL A O F SIGNAL INPUT RELAY MODULE
XDCRI/O kRECORDIIININAIS
c , iiC0/15
Wa t t * uniirCR
I , 1 O 0 DANS
1 0 Aim 0 1
0
0 BYPkss 0
O
0
(0)
0 fiff11411 MAIGI 1 6
0
34
Dual Vibration Maintenance 80177-01
• 30 TESTOKLIMITS[CONT.]
INCREASEGAP UNTILOKLEDGOESOFF (UPPER LIMIT).
CHECKPROBE GAPVOLTAGE ONMULTIMETER:
1 Vdc8 TO. —16.8
5 1Vdc
— 7200 TRANSDUCER
—10.5 Vdc TO —11.6 Vdc 3000 TRANSDUCER
8. VERIFYCHANGESTATE OF OK RELAY. NOTE THAT ALL CHANNELSMUST BE OK
ORBYPASSED IN ORDERFOR THEARNAND NOCONTACTS OF THE OK RELAY
(NORMALLYENERGIZED) TO BE CONNECTED.
1) 0 B0/15
MIN PM UPPEROK LIMIT
INCREASING
GAP
• a o
o toon of l
0 MS 0
• GA
V
OV
—
O
P
T
G
(LE
T
A
L
— (V
dc)dc)
V
PROBE GAP
(MILSOR MILLIMETRES)
9.GRADUALLYDECREASEPROBE GAP TO —9 Vdc AND WAIT 30 SECONDS.PRESS
RESETUNTILOKLEDGOES ON.OKLEDSHOULD BE ONBETWEENUPPERAND
LOWEROK LIMITS.
10.DECREASEPROBE GAP UNTILOKLEDGOESOFF(LOWER LIMIT).
11.CHECKPROBE GAPVOLTAGE ON MULTIMETER:
—2.7 Vdc TO —3.3 Vdc 7200TRANSDUCER
—1.7 Vdc TO —2.1 Vdc 3000TRANSDUCER
-41.4
DECREASING
GAP
LOWEROK LIMIT
• A
PROBEGAP •
(MILSOR MILLIMETHES)
M M O
wom
35
80177-01 Dual Vibration Maintenance
31 FE
I LDWIRINGDA
I GRAMS
a EXTENSION CABLE
6-\
CONNECTOR
PROTECTOR
0
CHANNEL B
ALERT PROBE
DANGER
RELAY - - RELAY SHAT T
CON TACTS CONTACTS
5 r n rn I ' i - " I r M TO R
VT ( - 1 8 1 0 - 7 4 VDC
SIGNAL INPUT RELAY PROBE D A . 5 m m ( . 2 0 0 I N . )
COM
SCALE FACTOR 2 0 0 1AWKAIL ( 3 / m m )
TEMP RANGE - 5 5 ' TO 1 0 0 - C
36
4S3 1i'
•
Dual Vibration Maintenance 80177-01
• 31 FE
I LDWIRINGDA
I GRAMS[CONT.]
EXTENSION CABLE
CHANNEL B
ALERT PROBE
DANGER
RELAY 11110:1111011 RELAY SHAFT
CONTACTS MINL701; CONTACTS
11::I
• MODULE
1. W I R I N G RECOMMENDATIONS:
SIGNAL MODULE T O PROXIMITORS: 1 8 — T O 22— AW G SOLID O R STRANDED, 3
WIRE SHIELDED WITH INSULATING SHEATH.
SIGNAL MODULE T O RECORDER/READOUT: 1 8 — T O 22— AW G SOLID O R
STRANDED, 2 —WIRE SHIELDED WITH INSULATING SHEATH.
A SHIELDS TERMINATED T O SIGNAL MODULE COMMON.
4 5.322
37
80177-01 Dual Vibration Maintenance
31 FE
I LDWIRINGDA
I GRAMS[CONT.]
SAFE A R E A O R ZONE 2 DIVISION 2 HAZARDOUS AREA
0 0
7 2 0 0 PROXIMITOR
CONNECTOR
PROTECTOR
CHANNELTO
RECORDER TO CHANNEL B
ARECORDER TO PROBE
5 n u n PROXIMITOR
VT(- 1 8 TO - 2 4 ADO
ALERT DANGER
PROW D A Y o n ( ZOO s k i
C O I L O O M S io ( 1 . 4 f l )
RELAY COM
— RELAY
CONTACTS S O 4 . 1 T O . TOO kwAst.
R V R M . P S • TO 100•C(S/AA,)
WIRING RECOMMENDATIONS:
SIGN AL MODULE T O BARRIER- BARRIER TO PROXIMITOR: 1 4 - T O 1 8 -
AWG SOLID OR STRANDED, 3 WIRE SHIELDED WITH INSULATING SHEATH
SIGNAL MODULE T O RECORDER/READOUT; 1 8 - T O 2 2 - AWG
SOLID O R STRANDED, 2 -WIRE SHIELDED WITH INSULATING SHEATH.
38
Dual Vibration Maintenance 80177-01
• 32 RECOMMENDEDSPAREPARTS
Q1Y
PER DESCRIPTION REPLACEMENT PART NUMB! R
MON
- -------
1 SIGNAL INPUT R E L AY MODULE
NO RELAY 81544-01 *
EPDXY SEALED RELAY 81545-01 •
W19 Wl?
1C3
W15
DUAL. MBRATION MONITOR S/N
39
80177-01 Dual Vibration Maintenance
33 SPECF
IC
I ATO
I NS
INPUT
Signal Input Two channels, proximity input, 10IS2 input impedance
Signal Scale Factor 2(0)mV/mil (8v/mm)
SIGNAL CONDITIONING
Monitor Range Full scale meter range selected per Option Table.
Frequency Response 240 to 240,000 rpm and 60 to 36,000 rpm
Accuracy ±0.33% of full scale error typical at 77°F (25°C)
±1% of full scale error maximum at 77°F (25°C)
±2% of full scale error maximum at 77°F (25°C) with 2x trip multiply option selected
±3% of full scale error maximum at 77°F (25°C) with 3x trip multiply option selected
ALARMS
Alarm Set Points Alert/Danger alarm levels (adjustable from 0 to 100% of full scale)
Alarm Delay Alarm delay times are user-programmable per options
DISPLAYS
Meter LCD bargraph, dual scale with outside scales marked per monitor full scale
range and center scale marked for probe gap voltage at 1.6% resolution.
LEDs Green LEDs annunciate transducer OK condition, red LEDs annunciate DANGER,
ALERT, and BYPASS conditions.
CONTROLS
Front Panel Front panel switches (3) for reading ALERT and DANGER setpoint levels, and for
reading probe Gap voltage
Internal Switches on circuit board for setpoint adjustment, Danger Bypass, and Channel Bypass
External External remote controls: Reset, Trip Multiply, Inhibit, and setpoint adjust ( t and j )
OUTPUT
Recorder Output proportional to selected full scale monitor range and protected against con-
tinuous short circuit to ground:
+ 4 to + 20mA, 12 V compliance
+ 1 to + 5 Vdc, 100-ohm output impedance
0 to -10 Vdc, 100-ohm output impedance
Transducer Power -24 Vdc or -18 Vdc determined transducer option selected in power supply, short-
ciruit protected
Alarms & OK Relay drives for alarms (ALERT and DANGER) and monitor and transducer OK
Dual Relays 5 Amps @1 20 Vac 50/60 Hz
5 Amps 28 Vdc
Quad Relays 0.6 Amp @120 Vac 50/60 Hz
2 Amps 30 Vdc
ENVIRONMENTAL
Temperature Operating: + 32°F to 149°F (0°C to 65°C)
Storage: -40°F to + 185°F (-40°C to + 85°C)
Humidity 0 to 95%, noncondensing
40
Dual Vibration Maintenance 80177-01
• 34 SCHEMATC
I S&PWADRAWN
I GS
DRAWING T I T L E D R A W I N G NO. . . . . . N O . O F SHEETS
PWA
D U A L R A D I A L VIBRATION MONITOR 7 8 3 9 2 S H E E T 1 OF 1
3300/15 SIGNAL NAMES S H E E T 1 OF 1
SCHEMATIC D I A G R A M
D U A L R A D I A L VIBRATION MONITOR 7 8 3 9 3 S H E E T S 7 OF 7
SCHEMATIC D I A G R A M
D U A L R A D I A L VIBRATION FRONT PANEL 7 8 4 1 3 S H E E T 1 OF 1
ASSEMBLY
SIRM EPDXY 7 8 4 6 2 S H E E T S 3 OF 3
SCHEMATIC D I A G R A M
SIRM EPDXY 7 8 4 6 3 S H E E T S 2 OF 2
SCHEMATIC D I A G R A M
QUAD R E L AY 8 3 7 3 0 S H E E T S 2 OF 2
1110 s w a m
41
•
•
ad d a
m ®
1\
f
00 F, 0 0 0 0 0 0 0 0 0 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 06928
.4 a .
••• I - 0 4028
0. I - 0. a _ 11 2 0 0 0 0 0 0 0 0 0 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
80.28
900111
2M 0 1 c p 20201 04028
9801• N M •
$38• M N •
§lEEErint g l ▶ 0 1 t3
1.
6 1 OM•
08028
8228
•040
063.
IMO BIE;;30 ;E71,,,
00 • E1 2 0 0 0 0 0 oo o
g0
00 0 0 0 o 2 1 2 1 •8
5 0000 412210 £1221
LEO • M i n i • 902210
0 0821 • N M I •
6L21 • IMIIM . 888
688
•
• m .
• MN
0
• 61221
•02201
• NMI •
•
•
o 0621 • 14021 0 8 1 0
3.; E P O K E E 1.601 1• 0 0 0 0 0 0 0 0
0 £601 08 07
51MOI
eLd
0601
0 0 /00 0 0 0 0 0 0
RJ •-qgsea• M E M • 0
BS
SZ 0 6 8
as
CFI zi041•• IMMO
la IEEE •
• 0. ■
o
668 0 0 0 0 r 6 - 6 - 6 0000
rsr) 0101 O MEN . II • II •
H 3 • MEE • 1--utILD
920 t PIN 0
0 0 0 0 0 0 0 018101
923 • IMIE1 00010 0 o 0oo ooo
) 0oo
ti 6218 • = M N •
1113 0-1
42.•.‘ 0 0 031- 0E l d 1 R 3 • O M 0 • IMMO 010a
• 021a
061a0-11-0al 00 0 0 0 0 0 l i 0 0Do o
S32:ibicIS 9 8 0833 2 =M W Mili• •=1 MEM • 01213
•
• Old
HEIEEEEREE88 ins •
cal ONO •
• inn
• N M • 22101 8030-11 - 0
000000 0 '438i
*dialto- TO1 Lain n c • • MEM • £218
• 603 in
....go.
• OMNI
1•01
‘08
0
Odl 9 S 8
Et1OS 1 , 2 /I 0 000000 13
11.11.835 I O N 8018
2101 £09:211k1110 00 o
4980-1 080 PL 0210
0898 93 ° i ; ; 3 - 0
L2110
9921 0 06E8
0OLD098 9008 i y a e2800000000 0 0 0 0 0 0 0 0
421210-
204 .00 9
6000 0• 0 o eato-r
o- r ,4;u001a.y..g00 ° 0 o 00
ILO 1 - 0 ad e n
000 0
CO• • • 890001)000 O
. 1 1 f t w . Z9021
t9
"coa 0 0 0 0 0 0 0
200 • M I
003 • M M I I
6601 • .11111 sw 0
0 0 k )
REHR. . f t . 0 0928
. f t w .
0908
M 0 0 0 0 0 0 C a l l l 0
1421 • N E N L28
Owl 063 —
0 0 0 0 1 7 0 - 0 0 0 En
0 0 0 0 0 0 0 0 0 0
0 841t18
0000
802,1 n u
0 0 0 0 0 0 4 -
1 - 0
0 _ 11 0 0
CH 693 CH 8
7 w r. / r T 6 ;
• PRINTED W I R I N G ASSEMBLY
DUAL R A D I A L V I B R AT I O N MONITOR
78392
SHEET 1 O F 1
•
,iSsil . i g
CLK
CLX PRR6 v
DS
ICL
C
I
g
! r
lavnla g ! W V ,:aiiiwi ▪ !.!
• f12' V 2 ' •
—We—•
• S U • 9221
• /19' I C
--•AAr-
09V •
9g
ECU I I L E 2 tti
• S C H E M AT I C D I A G R A M
DUAL R A D I A L V I B R A T I O N M O N I T O R
78393
SHEET 1 O F 7
•
L a
•
a
iiiFif d 1 66
7
gb
a
5.
1
gb
F.
g
• sGEM
k r M-1 YE
r i • AS " i ' V q 3 4 1
• " '• •
3
6
Ida
EI I
8W
raila'
ampp
k'
QSY ".5
a 11 , 7 M Q V M kigt I
^S9 4 IDU.•
p A C
74: C i i i I r . R q r ! " t o m w i g WV
'111161—r,!
,dt& L ' . i a 1 1 , 4 g
A
I
A
=EE
iSig i t
I des '•=19 ;
„:„A1 I
2• . l2.i 9e . 9.
0.
•
11111 2 . 2. V3 NO.,1
S C H E M AT I C D I A G R A M 7 8 3 9 3
DUAL R A D I A L V I B R A T I O N M O N I T O R S H E E T 2 OF 7
•
•
cr)
a a
•
k 6
0 Pi
dg
II 8
0
5 )611s s
WI,
WM
. 1
, 5 6 F
slr<nr-,:r4
11 C. Me et
/MI
' 1
" 1 §
s M
e -m-
aa9/1 31921 O I N
Mr • LI
1
Mt LE N M I r ';‘2,',
• rrii S P I N
E O M g a l a
a
73
3219
0
yJJ ;
• -----\,F4t71:1-4
L.n
ra
2
N
a a 9,1
6 tin. 6 1 1 3332
1
1M W 1
is
61.1' t 9 W I N
4 p2
2
W
*----14k—
. e i _ D A
5 A
2 of
I
LN
•
09
N
•
L
•
o
Bb F
241
4
-1
000411
elVIMeiv
LA SLR 11
A
' "8'6' MOD1WCC
WV W V
URA U M
MOT
5 0 0
5000
• In
441414,mti
In
g)16f0
1.10.0L5011
VICti111125
8525
Ei r e
03 9.
co
n4I A
•
'A 5
1
S C H E M AT I C D I A G R A M 7 8 3 9 3
DUAL R A D I A L V I B R A T I O N M O N I T O R S H E E T 4 OF 7
•
•
8
ti
e!!
EY7
:Joe
1 1
%Clnmd
-—
r Y N
MIL
r
NC', O I L
• 8
Y42
LI
C&L.
ss i o g
3— g , 8
31 1 i
2
;>1-i11v :vN b I PI ' A i r . . . aim rh
,.24....„,.sw.,41Axlvalsgwviabtp,wainflotmeimAN
_,111 I
I
1111,11.111,11 [ 11 , 1 , 11 , , i , n r i i , „ , „ - - i i i i l l i n i i ,
1111[111111 1 1 1 1 1 I T j 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 I I I 11111 I
" w
"wnggigeg i t h
• O
F1
f 9
S C H E M AT I C D I A G R A M 7 8 3 9 3
DUAL R A D I A L V I B R A T I O N M O N I T O R S H E E T 5 OF 7
• •
9 4 3
02
S A n . . EPDXY RELAYS
ANO,NeF ,IOC 1 0 8
ACOM
• H S - l e MILS
‘12A
DC.011
MONITOR RECCRDER OPTIONS
H () KR
II - I S MILS 4160 ,116F AOC ,I13/1
114 47.6v
N29 ,N2C ,I0D
• C7 INSTALL JUMPERS I/11B M I IC,1412A,LIIZC ,1412E ,4112F
111119,NNIA,40B,HOC,N7A,N7F,W1C,NnE
-7.60
H OS
0 - 2 0 MILS NED ,46F ,At3C Al3A
MONITOR OPTIONS . 4 TO . 2 0 wA
REMOVE ROPERS W I WA n t A w 11 E , 8 11 0 W I 2 E I A 1 9 0
-VI
920,4420 DANCER BYPASS ENABLE INSTALL JUMPER I N S WIN,11120,186,NOA,14116,1.eD,1179,147D ArAL
H N• n .0841
II if - 1 0 0 u n 430 ,W39,18C AIRE DANCER BYPASS DISABLE REMOVE JUMPER N 2 0
424,420 XDUC
INSTALL JUMPERS NtIAAMIE,W410,1110A,W128,1412D
1103A,6E4471 A170 AllUC
0 - I S O 811 'DANGER AND" INSTALL JUMPER 8 1 6 0 •1 T O . S 2
12 NED AIRE ,NCIC ,N3A
12A ,NEC KOP
REMOVE JUMPERS N I I F, N 1 2 F, N 11 0 , 6 111 C , W I I S A l 6 A I S A
'DANGER OR" RETICNE JUMPER 8 1 6 D
1-3 WIRE ,146IF A I M ACK N W AMIC ,147C Al I2C ASID A116 A4124. STA
H 13 6 - 2 0 0 um WED ,116, m3c ,113/1
FIRST OUT INSTALL JumPER 1416C INSTALL JUMPERS N I IF ,Il 1 ID 01121,1112D ADO MDR 919
1211,420 • TO - I S O
WEE mini ,4478 ,1410
NO FIRST CUT CAP
14 6 - 4001/1 REMOVE JUMPER I I I 6 C
NW ,N4F , I I X ,N3A REMOVE JUMPERS N I IA ,W 1 WI ,N I IC ,1412A ,A11 IE ,111119 Ad IAA ,1412F
GAP
1420,112C AIRE ,W12C NSA ,Well ,NBC ARE ,117A ,51F APE ,WIC
yyz LATCHING ALERT ALARMS INSTALL JUMPER NIRO
4460,146F ACC ,W3.4 9PR
IS 0 - 5 0 0 All
1429,142D NON-LATCHING ALERT ALARMS REMOVE JUMPER WISD
BPP
z LATCHING DANGER ALARMS INSTALL JumPER 11168
SIGNAL
INDEX OF TERMINOLOGY
COmPLETE 'TONAL NAPS EH
H cm
NOTE BEFORE COSIGURINC A FULL SCALE RANGE SO0 SERIAL CLOCK
NON-LATCHING DANCER ALARMS REMOVE JUMPER N 1 6 9
REMOVE J U P E R S W2A-0,1138-30 11 W6C-6F SCIC C
6051 MASTER OJT SLAVE I N
TEEN INSTALL THE APPROPRIATE DOPERS TCH RES
LOAD SHIFT REGISTER LATCHES LOAD
0 . I SEC ALARM DELAY REMOVE JUMPERS 415E 41151 TO
%SCR INVERTED SERIAL CLOCK
TO
INSTALL JUMPER RISC SERI SERIAL COMMUNICATIONS TRANSMIT
I 0 SEC ALARM DELAY
REMOVE JUMPER 111103 CLOCK
SERE SERIAL conmuNIcArtows RECEIVE
INSTALL JUMPER 14159 0129
3 . 0 SEC ALARM DELAY RECA RECORDER CNA/44EL A
REDONE JUMPER 4 1 6 0
-6
RECO RECORDER CHANNEL 0
ONGS
6 . 0 SEC ALARM DELAY INSTALL JUMPERS R I S S AIISC
!MOCHA DOM STATIC DATA CHAN.A
)ALRT
MONITOR FREQUENCY OPTIONS 2000418 DOM STATIC DATA C1AN.9
CAPS4
MOSOE141 RACK SLOT POSITION D A V I E
PSC - O
JUMPERS N I ,W612,143F
31,11111 RPM 1101 5 E 11 MONITOR SELECT PC4 4 P
REMOVE N68,143E
CORNER FREQUENCY OPTION BASE BUFFERED DIM STATIC DATA SELECT L I N E C
4 ' T R I P MULTIPLY COmPoNENT OPTIONS MON RES
9059 BUFFERED D I M STATIC DATA SELECT L I N E 9
JUMPERS 146A,43E ODRA BUFFERED D I M STATIC DATA SELECT L I N E A MOIS
240101111 RPM U60. MC33172 IEDENI LED DRIVER ENABLE
REMOVE 9 1 , 9 6 0 Al3F PAS A
[CANER FREGUENC0 OPTION R 2 7 7 - 1 4 2 ! : 2201 SEROAT SERIAL DATA
4274,11276 . . 1 8 1 CHASSIS CHASSIS W i e r / PEA -
R273,R275 : 321.14 MORI MONITOR OK BUS DRIVER
2X T R I P MULTIPLY rSP
R44,RS2 : 4 7 5 K IF0A1 ALERT F I R S T a n DRIVER
MONITOR PROCESSOR OPTIONS
R41,R55 : 15611 WODI DANGER F I R S T OUT DRIVER iSH
1243,1163 : 2 3 7 K IA F O I N 1 ALERT F I R S T OUT INPUT UP
8269,82713 , 2 3 1 ID FO 1 6 1 DANCER FIRST OUT INPUT
INVCKE SELF TEST MOMENTARY SHORT 4 1 3 BL
REMOVE 1142,RS4
TTLAA TTL ALERT DRIVE CHANNEL A
TTLAB TTL ALERT DRIVE CHANNEL
PROCESSOR RESET MOMENTARY SHORT WIA USED 011
U60 : MC33172 TTLDA TTL DANCER DRIVE CHANNEL A 332,0
R211- t e e : 2 0 K TTLINI TTL DANGER DRIVE CHANNEL I I
SIAGLE C H I P MODE JUMPER P I N S 9 - 4 0 C r 03 9274,0276 . lox DR
ARDAV ALERT RELAY DRIVE
38 TRIP MULTIPLY R273,R275 : 4 9 . 9 K CM(
ORORy DANGER RELAY W O W
EXPANDED MODE PLUG PIGGY BOARD 844,1152 : E B I K
'DATA OW STATIC DATA
RNA 7 8 4 8 2 - 0 1 RAI,RSS : 1 3 7 K ERG PA U L HOSEIT
'REF .5V REFERENCE SOLRCE
INTO .r3 Ft43,RS3 : 3 6 1 X APPD
-REF •SF REFERENCE RETURN
Ft 261,14270 : I N N
ACOMA TRANSDUCER c o m o w OMAN. A NEXT NIGHER ASS?
NOTE: 11 DENOTES ACTIVE Low REMOVE R 4 2 , R 5 4
ACOMB TRANSDUCER CE MOM GNAWS 77SSIS
IA:ASAS
8 7 6 4 3
8
k X
5
" kin t
1
S a
"btio
6 2 ; 4 6-
t 4
• S
6
a
6,
58 8 e 6 h
66
68 "
•; 8
S
S
9
CO
• a
S C H E M AT I C D I A G R A M 7 8 3 9
a)
3
DUAL R A D I A L V I B R A T I O N M O N I T O R S H E E T 7 OF 7
• • •
3300/15 SCHEMATIC SIGNAL NAMES
ABBREVIATIONS OF THE SIGNALS USED IN THE SCHEMATIC
SIGNALS ON THE SCHEMATIC COMPLETE SIGNAL N A M E SIGNALS O N THE SCHEMATIC COMPLETE SIGNAL N A M E
ga 2
•
e
Ea
6
y,*
la a g H
gl
lgIll§sai l
z gg 999999"
ILL4
• rig§
992 ggg
lig
gAt!
999999
Ill9eliPSM3E33N19.111:r.
gfillYiwwwwwwam
g2209999991922g
rr
a
A8 H i
1
155 555515
tit; 62 i i i
bS9S
999 9 9 9 9 9 9 ggg gn Ogg g g g r g
if41,441Alk
J
i d ag ;
f I V
•
i
!I M I M I ! ! ! 5 "'"iggigg
gillIgliglg g glglIgglIgg g O g g
99 9 9 9 g ggggIgggggg g g g g
•
gg ggggggggggg
SCHEMATIC DIAGRAM 7 8 4 1 3
DRV FRONT PA N E L S H E E T 1 OF 1
• •
JO
8 7 5
cn
H CD
UJ D
t-4
1-‹ PL
,t1
0
2 PL
cn
H
A . . . K . _ N O K E E N APPLICABLE_
• . REF 50-CPAAT C 1)1 AGANA 7 8 1 6 5 ,
A A 4 4 0 6 SEA I AL NO PRECEDED BY S R
101[6. a n . . I be SPEC •
7 5 5
•
SEE S E P A A T E _Y
B E N T LY A
N E VA D A N40,•••••••••
A S S E M B LY
.."^ • .".344Ario S I P M , E D O X • f / S I M
040. I 78E1707
I 7
20230 0 72462
some. 0 , 3
4 3 2 1
• • •
8 I 7 6 I 5 I q 3
Cf) X V .
H Cf)
D
X
1-<
trl
ro
C/1
H
2 PL
C/)
-02 ASSEMBLY
020
trite
ttrn
1-3 N)
0 SEE 5 KET
6 5 T 4 I 3 I 2
•
O T2210
£2eo
22210
02b0
salo
pao 2213
f1B-C1=-0
O 0 0 rn
O 0 0 0
O 0 0
O 0 0 0
G
m o [m1 ] oL J oo zn 0 0 0 0 0
a -cr• 0
O O
O O R
O 0
3 3 0 0 0 0 p 00
w0, 0m00
0 0 0 0 0 0 0 0 O 0
0c.cc O 0
0 ch O 0
0 U O 0
0
ap,,54.000.-'2132IWW N
- C T - . c0 . 0 . . . m
O
00
0
0
0
-,iscir ,x E l
0 0000 ° Lo
' rO
-moo 0° O 0
O 0 ) ) ) M Fil O 0
O 0 O 0
O
O o
o 0 o i.iii 00 0
O 0 00, O 0
0
0 0 0 0 0 0 0 0 0 C.CD
If) u,in r o 0 . 3 r i O 0
O 0
O 0 ;Offo a ' o o M 0 0 0
0 O 0
O 0
0
O 0
0
O 0 0 0 0
0
0
0
O
C3 a
0
0 0 0 0 0 0 0 N
O N N I N O V: .
M INIX
0 UM
O 0 C/Cr OCEMM
O 0
Njm:4[D
00W
—29OBLASSU
•
ASSEMBLY 7 8 4 6 2
S I R M EPDXY/ S I M S H E E T 3 OF 3
•
• SCHEMATIC DIAGRAM
SIRM EPDXY
78463
SHEET 1 O F 2
110NANANINIMININANIMONIMMEMOIXIMINIF5NEwsmaggusligwfw OVER5
T. W L I C O M A X4 I l i T
M 41 U P 4 5
7 =MM O1I M P R7 1 1 , 7 4 . 1 . . 1 W ^ W H M - 1 2 1 . 1 2 . 1 V1:1.1
V
9/9 e r
•-• V - 4 V t Z
0400
!IP
ii!!!
!!!!!
7C
, C .7t; a iii.
il
• 5
• S C H E M AT I C D I A G R A M
SIRM EPDXY S H
7 8
E
4
E
6
T
3
2 OF 2
•
• S C H E M AT I C D I A G R A M
QUAD R E L A Y
83730
SHEET 1 O F 2
• N A U I N A l i f i E t l i i i i a X l i a Z i d A I M ! h E E I N I M i i . V 0 . 1 a N n 5 H f _ _ g g S R K S E 5 Yq W A N A = 1 5
: I : VA r . ; ISMISIRZTP:: T 1111'.11151VP111-T21L'IT7.1111"-117151V:OM:Y.17-1*M rs X* 2 *WI. . 2 1 * 21-1
zr Y V 0 . .
`±'
• SCHEMATIC DIAGRAM
QUAD R E L AY
83730
SHEET 2 O F 2
80177-01 Dual Vibration Maintenance
• INDEX
A
Alarm Delays Option 2 0
Alarm Set Point Option 2 6
Alert 6
Alert Mode Option 2 1
B
Bypass 5
C
Calibrate Channe 3 2
Channel Bypass 2 7
D
Danger 7
Danger Bypass 2 8
Danger Bypass Switch Option 2 2
Danger Mode Option 2 1
• Disassembly Procedure 1
Dual Vibration Monitor System 1
E
5
F
Field Wiring Diagrams 3 6
First Out Option 2 0
Frequency Response Option 2 0
Front Panel Removal 1 6
M
Monitor Full Scale Options 2 4
Monitor Functions 2
Monitor OK Limits Option 2 2
Monitor Options 3
Monitor Ranges 8
•
Index-1
Dual Vibration Maintenance 8 0 1 7 7 - 0 1
0
Options
Alarm Delays 2 0
Alarm Set Point 2 6
Alert Mode 2 1
Danger Bypass Switch 2 2
Danger Mode 2 1
First Out 2 0
Frequency Response 2 0
Installed Programmable 1 9
Programmable 3
Monitor Full Scale 2 4
Monitor OK Limits 2 2
Monitor Options 3
Recorder Out 2 2
p
Programmable Options 3
R
Read Alert Set Point Levels 1 1
Read Danger Set Point Levels 1 1
Read Channel Vibration 9
Read Probe Gap Voltage 1 0
Recorder Out Options 2 2
Recommended Spare Parts 3 9
Replace Meter Scale 2 3
S
Schematics 4 1
Self Test 1 2
Signal Input Relay Module 1 7
Specifications 4 0
Drawings 4 1
T
Test Channel Alarms 2 9
Test OK Limits 3 4
Index-2
Artisan Technology Group is your source for quality
new and certified-used/pre-owned equipment
• FAST SHIPPING AND SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT
DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment
• TENS OF THOUSANDS OF at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins
IN-STOCK ITEMS www.artisantg.com/WeBuyEquipment
• EQUIPMENT DEMOS
• HUNDREDS OF InstraView REMOTE INSPECTION
SM
LOOKING FOR MORE INFORMATION?
MANUFACTURERS Remotely inspect equipment before purchasing with Visit us on the web at www.artisantg.com for more
SUPPORTED our interactive website at www.instraview.com information on price quotations, drivers, technical
• LEASING/MONTHLY specifications, manuals, and documentation
RENTALS
• ITAR CERTIFIED
SECURE ASSET SOLUTIONS
Contact us: (888) 88-SOURCE | sales@artisantg.com | www.artisantg.com