SN Description of Problem Action Owner Action Owner Status Closed Date Remarks

New signals to be configured as


132kV Protection(IED) Signals: When Main-1 Distance Protection Active is ON & OFF, Following Siemens SCS/Siemens SIEMENS Open per protection sync list and
Signals are reported with duplication of events,Refer Attachment and please rectify -Main-1 Prot. same to incorporated at
Distance Protection PIcked Up Zone-1 -Main-1 Distance Protection PIcked Up Zone-2 -Main-1 PAS/SCC level. Site Note Ref: 16,
C.1.17 Distance Protection PIcked Up Zone-3 Sno: 100

FO Link Fail Observation: 1. When IED/FO Link Faulty is given in 132 kv relays following behaviours
observed in the event list. Please Rectify. -IED FO Channel 1 or 2 & its group signal Fail reporting SCS Support SIEMENS Open
two times without reset. -Unwanted signals reported from corresponding relay & BCU. -General Support ticket raised. Site Note
interrogation signals reported after reset. - Same behaviour was not observed while doing the Ref: 27, Sno: 125 Tentative date
C.1.27 same signals after restarting the WinCC.Refer Attached. of Closing: 30/12/2018

RTCC Functionality: TCC Block/ Release command should be independent of parallel operation NCC NCC Open
mode. When transformer in parallel mode, if any one transformer TCC is blocked from REMOTE,
other transformer also blocked due to transformers in parallel mode but the release command is
C.1.28 executing only to the transformer to which blocked command issued. Kindly clarify. Site Note Ref: 28, Sno: 127
RTCC Functionality: Control Command Feedback Via AVR is not appropriate, Command Fail is not NCC NCC Open
C.1.30 reporting for Negative checks Site Note Ref: 29, Sno: 131

when Control supply MCB FCM1.1 is off or VT metering healthy circuit (KFA5) is dropped from VT
panel, 01. Bus VT unhealth and Sync Blocked signals appear in all feeders connected in that section
but not in A12. 02. During this condition, Local and remote CB operations are blocked for all Siemens Prot./NCC SIEMENS/NCC Open
feeders connected in that section but A12 CB operation is blocked from local only not in remote.
03. In above mentioned condition, NCC/DGCC/DCC may not know the reason for outgoing CB
C.1.40 operation blocked. Site Note Ref: 42, Sno: 168
Awaiting reply from Schneider
Schneider Prot. SIEMENS Open Support Site Note Ref: 43, Sno:
C.1.41 Fault Record Transmission test: P633 disturbance file name is incorrect. Please correct. 169