Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 1
Abstract—This paper proposes a single-stage three-phase four- Distributed generation (DG) systems based on RES have
wire grid-connected photovoltaic (PV) system operating with a contributed to find new modern solutions for planning
dual compensating strategy and feed-forward control loop conventional power systems [1]. Inserted in this scenario,
(FFCL). Besides injection of active power into the grid, the PV solar energy has emerged as a promising RES due to its
system operates as a unified power quality conditioner (UPQC), abundance across the earth’s surface. In particular, by means
suppressing load harmonic currents and compensating reactive
power. Furthermore, regulated, balanced and harmonic free
of photovoltaic (PV) cells, photovoltaic panels have been
output voltages are provided to the load. Since the PV-UPQC is properly designed to produce energy by converting sunlight
based on a dual compensation strategy, the series converter into electricity.
operates as a sinusoidal current source, whereas the parallel Normally, grid-connected PV systems can be deployed by
converter operates as a sinusoidal voltage source. Thus, seamless means of single-stage (S-S) or double-stage (D-S) power
transition can be achieved from the interconnected to the conversion [2], [3]. S-S PV systems are usually composed of
islanding operation modes, and vice-versa, without load voltage only a grid-tied inverter (dc/ac converter) [4]-[9]. In this case,
transients. Moreover, to overcome problems associated with the PV array is directly connected to the dc-bus of the grid-
sudden solar irradiation changes, fast power balance involving
tied inverter. On the other hand, in D-S PV systems, an
the PV array and the grid is obtained, since the FFCL acts on the
generation of the series inverter current references. As a result,
additional dc/dc converter is placed between the PV array and
the dynamic responses of both inverter currents and dc-bus the inverter [10]-[12]. In this configuration, the maximum
voltage are improved. Detailed analysis involving the active power point tracking (MPPT) is performed by the dc/dc
power flow through the inverters is performed allowing proper converter [11]. Considering SS-PV systems, the task to
understanding of the PV-UPQC operation. Experimental results perform the MPPT is assumed by the grid-tied inverter,
are presented to evaluate both dynamic and static performances combined with the advantage of achieving more efficiency
of the PV-UPQC tied to the electrical distribution system. when compared to DS-PV systems [7], [8]. In both mentioned
PV system topologies, the dc/ac converter controls the
Index Terms—NPC inverters, feed-forward control loop, amplitude of the currents injected into the grid, in order to
PV-UPQC system, universal filtering capability.
guarantee the balance between the power produced to the PV
array and that absorbed by the grid.
I. INTRODUCTION
In most applications, PV systems are connected to the
HE production of electrical energy from renewable energy
T sources (RES) has grown a lot in recent decades, mainly
due to increased demand for electricity, as well as the global
electrical distribution system, as well as microgrids where
local generation is carried out [1], [13], [14]. Besides energy
production, and according to a suitably adopted control
intensive efforts to overcome the harmful environmental strategy, PV systems can also carry out other roles in a
impacts caused by pollutant energy sources, such as oil, coal, microgrid, such as active filtering and/or reactive power
natural gas, and others. compensation. In other words, PV systems can perform tasks
similar to those performed by conventional parallel active
power filters (P-APF) [11], [15], [16].
Manuscript received October 01, 2016; revised November 11, 2016; In this paper, an S-S 3P4W grid-connected PV system with
accepted January 13, 2017. Date of publication month day, 201x; date of
current version month day, 201x. combined operation with a unified power quality conditioner
L. B. G. Campanhol is with the Electrical Engineering Department, Federal (UPQC) is presented. The power circuit of the system, which
University of Technology (UTFPR-AP), Apucarana, PR, CO 86812-460 is denominated PV-UPQC, is composed of two back-to-back
Brazil (e-mail: campanhol@utfpr.edu.br). connected neutral-point clamped (NPC) inverters. Thereby,
S. A. O da Silva, and V. D. Bacon are with the Electrical Engineering
Department, Federal University of Technology (UTFPR-CP), Cornélio series-parallel active power line conditioning, as well as
Procópio, PR, CO 86300-000 Brazil (e-mail: augus@utfpr.edu.br; injection of active power into the grid and load can be
vinicius_vd@hotmail.com). simultaneously performed. As a result, apart from the role of
A. A. de Oliveira Jr. is with the Electrical and Computing Engineering P-APF (load harmonic suppressing and reactive power
Department, São Carlos Engineering School, University of São Paulo
(EESC-USP), São Carlos, SP, CO 13566-590 Brazil (e-mail: compensation), the PV-UPQC system is also able to provide
azauri@sc.usp.br). regulated, balanced, and harmonic free output voltages.
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 2
In other words, although the PV-UPQC system can also be parallel inverter changes its operation mode from current
connected to ac microgrids, in this paper it is employed to source to voltage source, and vice-versa, when the system
deliver active power to the conventional electrical distribution operates either in islanding or interconnected modes,
system and load from a distributed generation source occasioning voltage transients in the load.
composed of a PV array, while universal filtering is carried In the presented PV-UPQC system, the amplitudes of the
out. currents drained from the grid, as well as the direction of
A dual compensating strategy is adopted to operate the PV- power flow through the series and parallel converters vary
UPQC system, where the parallel converter is controlled to act depending on the amount of energy produced by the PV array
as a sinusoidal voltage source, while the series converter is and how much energy is consumed by the loads. Thus, at night
controlled to operate as a sinusoidal current source [17]-[19]. or when the power generated by the PV array is not enough to
Usually, the UPQC is controlled using a conventional be provided to the grid, the PV-UPQC system keeps operating
compensating strategy, in which the parallel converter behaves as a classical UPQC.
as a non-sinusoidal current source and the series converter The dc-bus control loop adjusts the amplitudes of the
behaves as a non-sinusoidal voltage source [20]-[22]. sinusoidal currents injected into the grid by means of the
The PV-UPQC can work based on two operation modes. In series converter, in which the dc-bus voltage reference is
the first, called interconnected mode, the PV array provides determined by the MPPT algorithm. Normally, the dynamic
power to the electrical distribution system, as well as to the response of the dc-bus control loop must be slower than those
load. In the second, called islanding mode, the PV array found in the current control loops of the grid-tied inverter [7].
provides power only to the load, similar to an uninterruptible Thus, adequate adjustments in the gains of both mentioned
power supply system [17]. If the conventional compensating controllers are mandatory to guarantee the injection of non-
strategy is being adopted to operate the PV-UPQC system, in distorted currents into the grid, since the dc-bus control loop
islanding mode, the parallel inverter mandatorily needs to must not affect the performance of the current control loops.
change its operation from a non-sinusoidal current source to a On the other hand, abrupt solar irradiation variations can result
sinusoidal voltage source. A contrary procedure also happens in significant oscillations in the dc-bus voltage [7], which
when the PV-UPQC operates in islanding mode and changes could interfere in proper PV-UPQC power balance, and,
to interconnected mode. As a result, the need to change the hence, impair the computation of the inverter current
operation mode of the parallel inverter can cause voltage references.
transients (overvoltage) in the load. On the other hand, if the To overcome this problem, this paper also proposes the use
PV-UPQC operates using a dual compensation strategy, the of a feed-forward control loop (FFCL) acting in conjunction
aforementioned control changes do not occur, since the with the dc-bus control loop to accelerate the calculation of
parallel inverter always remains operating as a voltage source the series converter current references. As a consequence,
in both interconnected and islanding modes. As a even under fast solar irradiation changes, the dc-bus voltage
consequence, no voltage transients occur in the load, as the oscillations are properly attenuated, speeding up the power
parallel inverter input control references are the output voltage balance of the system. Furthermore, since the dynamic
references ( VL∗_ abc ) and the estimated utility frequency ( ω ∗ ). response is improved, both the setting time and the
overvoltage/undervoltage of the dc-bus voltage are strongly
In a microgrid, for instance, the multifunctionality of the reduced.
proposed PV-UPQC system can be highlighted. In the case of This paper is organized as follows: Section II presents the
the grid being disconnected, the series converter is inhibited PV-UPQC system description, as well as the control structures
and the parallel converter could operate as a grid-feeding involving the two back-to-back connected NPC inverters. In
power converter [1], as the parallel converter could also be addition, the strategies employed to generate the series and
controlled as a current source. In the case of the existence of parallel converter input references, as well as the phase-locked
either a storage energy system or DG connected to the dc-bus, loop (PLL) system description are discussed. In section III
the parallel converter can operate as a grid-forming power both the open-loop and closed-loop transfer functions are
converter [1], since it can remain controlled as a voltage presented, as well as the procedures employed to calculate the
source. controller gains. Section IV describes the FFCL and its main
Several DG systems associated with unified power quality function. In Section V the power flow through the PV-UPQC
conditioners have been proposed in the literature [23]-[25]. In is analyzed, while in Section VI the extended experimental
[23], an S-S three-phase three-wire (3P3W) PV system results are shown to highlight the dual compensating strategy
configuration using two 3-Leg voltage source inverters and the FFCL action. Finally, Section VII presents the
operating associated with UPQC was presented. Nevertheless, conclusions.
experimental results were presented considering its operation
only as a dynamic voltage restorer. Thereby, suppression of
the utility voltage harmonics, and its operation as a P-APF II. PV-UPQC SYSTEM DESCRIPTION
were not taken into account. In [24], the D-S PV system was The complete power circuit scheme of the proposed S-S
applied to a 3P3W system by means of only computational 3P4W grid-tied PV system is composed of two back-to-back
simulations. However, no utility voltage or load current connected NPC inverters and their respective passive filtering
harmonic suppression were considered. Combined operation elements, and three single-phase coupling transformers
of UPQC with distributed generation is presented in [25]. As a employed to connect the series NPC inverter to the grid, as
conventional compensating strategy was employed, the shown in Fig. 1.
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 3
Fig. 1. Complete power circuit of the PV-UPQC system connected to a conventional electrical distribution system.
The distributed generation source, without storage, is as voltage unbalances, sags/swells, and harmonics will always
composed of a PV array, which is formed by a single string appear across the single-phase series transformers.
with twenty series-connected PV panels, making possible the As can be noted, since the input references are sinusoidal,
direct connection between the PV array and the dc-bus of the there is no need to compute non-sinusoidal input references by
inverters. means of the specific methods normally used in the
The PV-UPQC system is designed to operate with dc-bus conventional compensation strategy. Furthermore, the input
voltage reference vdc ∗ determined by the MPPT algorithm. references are continuous in the dq synchronous rotating
Thus, at MPP and under standard test conditions (STC), the frame, due to the controlled quantities of current and voltage
PV system operates with a dc-bus voltage amplitude of around being sinusoidal in the abc stationary frame. This allows the
616 V, since at MPP the PV voltage is equal to 30.8 V per- use of the classical proportional-integral (PI) controllers with
panel. On the other hand, the lower dc-bus voltage is limited null errors in steady-state.
∗
to vdc B. Series Current References and Output Voltage References
_ min = 460 V, meaning that below this voltage limit the
PV-UPQC operates out of the MPP. Furthermore, at night, for The signal flow graph shown in Fig. 2(a) presents the series
instance, the system is controlled to operate only as a UPQC, current control loop. The d-axis current into the synchronous
such that vdc ∗
_ min is also set to 460 V.
reference frame (SRF) iLd represents the sum of the active
and harmonic components of the load currents, which can be
A. UPQC with Dual Compensation Strategy computed by measuring the load currents ( iLa , iLb , iLc ), as
The dual compensation strategy applied to UPQC differs given by:
from the conventional compensation strategy due to the
parallel converter being controlled to operate as a sinusoidal 2 1 3 1 3 iLa
voltage source providing balanced and regulated sinusoidal iLd = cosθ − cosθ + sinθ − cosθ + sinθ i Lb (1)
voltages to the load. As the parallel converter behaves as a
3 2 2 2 2 iLc
sinusoidal voltage source, a low impedance path is achieved.
In this case, the flow of the load harmonic currents through the where sinθ and cos θ are the coordinates of the rotating unit
parallel converter is allowed. On the other hand, the series vector, and θ = θ pll is the estimated utility voltage phase-
converter is controlled to operate as a sinusoidal current angle.
source, draining balanced sinusoidal currents from the utility As can be noted in Fig. 2(a), a low-pass filter (LPF) is used
grid. In this case, since a high enough impedance path is to extract the continuous current iLd dc , which represents the
achieved, the flow of the load harmonic currents through the total active components of the load currents.
grid is blocked. Finally, the input current reference of the series converter in
In addition, both the sinusoidal voltage and current input the d-axis is given by:
references are in phase with the utility voltages. Thus, the
series converter is responsible for indirectly compensating i*scd = iLd dc + idc − i ff (2)
reactive power and unbalances of the load, as well as
suppressing harmonic currents. where idc is the output signal of the dc-bus voltage PI
Simultaneously, the parallel converter is responsible for controller, and i ff is the feed-forward current.
regulating the output voltages and, indirectly compensating
utility voltage unbalances and suppressing utility voltage The quantity idc determines the amount of active power that
harmonics. In this case, the utility voltage disturbances, such will be absorbed from the grid or furnished to the grid in order
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 4
(b) where u sc _ abc _ pwm are the PWM output voltages of the series
Fig. 2. Signal flow graphs of the control loops of the series and parallel NPC NPC inverter; v RLsc _ abc and v Lsc _ abc are the respective
inverters: (a) reference current generation and series current control loop; (b) voltages across the resistances and inductances of the L-filters
parallel output voltage control loop.
( Lsc _ abc ); vTsc _ abc = vs _ abc − v L _ abc are the voltages across the
The signal flow graph shown in Fig. 2(b) represents the series transformers; and n is the transformation ratio, which in
parallel voltage control loop. As aforementioned, the input this paper was adopted equal to 1.
voltage references of the parallel converter are set to VL∗_ abc in The series PWM voltages can be represented in the
dq0-axes, in which the state-space equation is given by:
the stationary reference frame (abc-axes) and v ∗Ld in the SRF
direct axis (d-axis), as shown in Fig. 2(a). As sinusoidal and x& sc _ dq 0 (t ) = Asc x sc _ dq 0 (t ) + Bsc u sc _ dq 0 (t ) + Fsc wsc _ dq 0 (t ) (4)
balanced voltages are provided to the load, the quadracture
where:
voltage v∗Lq and zero sequence component v∗L 0 are both set to T
di discq disc 0 i i i ;
T
zero. x& sc _ dq0 (t ) = scd ; x (t ) =
dt dt dt
sc _ dq 0 scd scq sc 0
C. Phase-Locked Loop System T
The utility voltage phase-angle detection is achieved by u sc _ dq 0 ( t ) = u scd _ pwm u scq _ pwm u sc 0 _ pwm ;
means of the three-phase PLL system presented in Fig. 3 [26].
It is based on a power-based PLL system (3pPLL) and uses T
wsc _ dq 0 ( t ) = vTscd vTscq vTsc 0 ;
non-autonomous adaptive filters (AFs) to extract the
fundamental components of the three-phase utility voltages in
order to reject utility disturbances related to voltage RLsc 1 0 0 1 0 0 1 0 0
harmonics. After the adaptive filtering, the positive sequence Asc = − 0 1 0 ; Bsc = 1 0 1 0 ; Fsc = − 1 0 1 0 .
Lsc 0 0 1 Lsc 0 0 1 Lsc 0 0 1
components of the utility voltages are achieved using a
positive-sequence detector (PSD) in order to reject voltage
After some mathematical manipulations in (4), the open-
unbalances, as shown in Fig. 3.
loop TF of the series converter average model is given by:
Details related to the design of the PI controller gains
( K Ppll , K Ipll ) and AF gain ( K c ), as well as the stability isc _ dq 0 ( s) Vdc / 2
Gsc _ dq 0 ( s) = = (5)
analysis requirements are presented in [26]. d sc _ dq 0 ( s) ( Lsc s + RLsc )
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 5
the PWM output voltages of the parallel NPC inverter the dq0-axes.
( u pc _ abc _ pwm ) can be represented by: Thereby, from Fig. 5, the closed-loop TFs are given by:
u pc _ abc _ pwm = v RLpc _ abc + v Lpc _ abc + v L _ abc (7) vL _ dq0 (s) X2 + X3
= (10)
vL∗ _ dq0 (s) Y1s 3 + Y2 s 2 + Y3s + Y4
where vRLpc _ abc and vLpc _ abc are the respective voltages
across the resistances and inductances of the L-filters where:
( L pc _ abc ), and v L _ abc are the output voltages. X 2 = K Pvp K Pip K pwm (Vdc / 2) ; X 3 = K Ivp K Pip K pwm (Vdc / 2) ;
The parallel PWM voltages can also be represented in the
dq0-axes, in which the state-space equation is given by: Y1 = L pc C p ; Y2 = RLpc + K Pip K pwm (Vdc / 2) C p ;
x& pc _ dq 0 (t ) = A pc x pc _ dq 0 (t ) + B pc u pc _ dq 0 (t ) + F pc w pc _ dq 0 (t ) (8)
Y3 = K Pvp K Pip K pwm (Vdc / 2) + 1 ; Y4 = K Ivp K Pip K pwm (Vdc / 2) .
where:
T
diLpd diLpq diLp0 dvLd dvLq dvL 0
x& pc _ dq 0 (t ) =
dt
;
dt dt dt dt dt
T
x pc _ dq0 (t ) = iLpd iLpq iLp 0 vLd vLq vL 0 ;
T
u pc _ dq0 (t ) = u pcd _ pwm u pcq _ pwm u pc0 _ pwm ;
T
w pc _ dq 0 (t ) = vLd vLq vL0 (iLd − iscd ) (iLq − iscq ) (iL 0 − isc0 ) ; Fig. 5. Signal flow graph in dq0-axes of the voltage controllers and average
model of the parallel NPC inverter.
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 6
C. DC-bus Voltage Controllers where v pv and i pv are the respective PV array voltage and
The dc-bus voltage PI controller ( PI v dc ) is presented in current, and v dc1 and v dc 2 represent the dc-bus voltages of
Fig. 2(a). It is used to control the total dc-bus voltage at the NPC inverters.
∗ , which is obtained from the MPPT technique
reference vdc The grid-tied series inverter currents, as well as the utility
based on perturb and observe (P&O) [16]. voltage grid are assumed to be balanced. In this case, the
The procedure used for obtaining the open-loop TF of the active power ( Pac ) provided from the PV-array to the grid is
dc-bus voltage is detailed in [28], which is given by: given by:
vd 3Vs pk I s pk
Gvdc ( s) = (11) Pac = 3Vs rms I s rms = (14)
vdcCdc s 2
where vd is the grid voltage into the SRF (d-axis), vdc is the where Vs rms and I s rms are the rms values of the respective
dc-bus voltage and C dc is the dc-bus equivalent capacitance. fundamental utility voltages and currents, respectively, and
A PI controller ( PI v dc ) is used to control the dc-bus Vs pk and I s pk are their respective peak amplitudes.
voltage. In this case the closed loop TF is found by: Neglecting any system losses, Ppv is assumed equal to Pac .
vdc ( s) K Pvdc vd.s + K Ivdc vd Thus, from (13) and (14), I s pk can be estimated by:
= (12)
vdc ( s) vdcCdc s 2 + K Pvdc vd .s + K Ivdc vd
∗
2v pvi pv
I s pk = (15)
where K Pvdc and K Ivdc are the PI controller gains. 3Vs pk1
An additional dc-bus voltage denominated PI vdcu is used where Vs pk1 represents the peak amplitude of the utility
to compensate voltage unbalances in the dc-bus voltage, as voltage (positive sequence component). This quantity is
shown in Fig. 2(b). In this case, the difference between the dc- estimated by the PLL system shown in Fig. 3.
bus voltages ( vdc1 − vdc 2 ) is compared to the voltage reference Finally, the current i ff represented in the dq rotating frame
equal to zero. The PI v dcu output signal ( vdcu ) is added to the is given by:
zero sequence component v ∗L0 (0-axis).
i ff = 3 2.I s pk (16)
In this paper, all the procedures employed for tuning the
current and voltage PI controllers are based on the frequency Thus, i ff is used in (2) to compute the input series
response method detailed in [29]. Phase-margins and
converter reference ( i*scd ) in the dq-axes.
crossover frequencies at 0dB are the input design
specifications to determine the controller gains. Therefore, as can be seen, although the PV-UPQC power
balance can be ensured only through the dc-bus voltage
IV. FEED-FORWARD CONTROL LOOP controller, the current i ff allows improvement in the dynamic
In this Section, the functionality of the FFCL is responses of both the dc-bus voltage and grid-tied series
emphasized, since its main function is realized when the PV inverter currents. Furthermore, there is no need to use
array is under sudden solar radiation changes. additional voltage or current transducers, since the quantities
The FFCL is needed because the dynamic response of the employed to calculate i ff have been previously measured
dc-bus control loop is always slower than the series converter ( v pv and i pv ) or estimated ( Vs pk1 ).
current control loops. Thereby, the FFCL acts in conjunction
with the dc-bus controller, determining the proper current V. ACTIVE POWER FLOW THROUGH THE NPC INVERTERS
amplitudes of the series converter, so that fast power balance
The active power flow through the PV-UPQC system is
of the PV-UPQC is achieved. In other words, the FFCL
presented in Fig. 6. It is determined taking into account the
contributes to speed up computation of the input current
following aspects: i. the amount of energy generated by the
references during the occurrence of fast variations in solar
PV array; ii. the amount of energy consumed by the load; and
radiation. As a consequence, possible disturbances in the
dc-bus, such as voltage oscillations and voltage iii. the difference between the rms grid voltage ( Vs ) and the
overshoot/undershoot are reduced. In addition, the setting time rms load voltage ( VL ). In Fig. 6 (a) to (f) the active powers
of the dc-bus voltage during transients is also reduced. involved to establish the analysis are: grid power Ps , PV array
The strategy consists of estimating, in the abc-frame, the
power Ppv , series converter power Psc , parallel converter
peak amplitudes of the fundamental series converter currents
( I s pk ) that would be injected into the grid. After that, I s pk is power Ppc and load power PL .
transformed from the abc-frame into the dq-frame such that In Fig. 6 (a), (b) and (c) Vs > VL In Fig. 6 (a), as PL = 0 W,
i ff is obtained. all energy produced by the PV array is delivered to the grid by
The power produced by the PV array ( Ppv ) is given by: means of both the series and parallel converters. The majority
of energy is always handled by the parallel converter. In
Ppv = v pvi pv = (vdc1 + vdc2 )i pv (13) Fig. 6 (b) PL ≠ 0 W and Ppv > PL . In this case, part of the
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 7
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 8
neutral current ( iLn ), grid voltages ( vsa , vsb , vsc ), and load
voltages ( v La , v Lb , v Lc ) are shown. As current harmonic
suppression and load unbalance compensation are performed,
sinusoidal and balanced grid currents are achieved. In
addition, regulated and almost sinusoidal and balanced load
voltages are also obtained.
In Figs. 9 to 11, static results for the PV-UPQC system
injecting active power into the grid are presented, considering
Load 2. In Fig. 9 the load is disconnected and only active
power is being injected into the grid (OPM 2), where
Fig. 7. PV-UPQC prototype setup. Ppv ≅ 3000W. As can be seen, the source currents are
sinusoidal and in opposite phase to the respective utility
TABLE II
PARAMETERS ADOPTED IN THE EXPERIMENTAL TESTS voltages. In Fig. 10, Ppv is higher than the load active power
Nominal utility voltages (rms) Vs = 127.27 V PL (OPM 3). In this case, the load is fed by the PV-UPQC
Series inverter inductive filters Lsc = 3.5 mH
Resistance of the series inverter inductive filters RLsc = 0.5 Ω
and the surplus of the produced active power is sent to the
Parallel inverter inductive filters Lpc = 1.7 mH grid, and the series converter also synthetizes sinusoidal
Resistance of the parallel inverter inductive filters RLpc = 0.4 Ω currents in opposite phase to the respective utility voltages.
Parallel inverter capacitive filters Cp = 60 µF The OPM 4 occurs when Ppv is smaller than PL , as shown in
Equivalent dc-bus capacitance Cdc = 2350 µF Fig. 11. As can be noted, the PV-UPQC system, in
dc-bus voltage at MPP Vdc = 616 V
conjunction with the grid, supplies the load. As can be
Lower dc-bus voltage limit ∗ = 460 V
vdc observed, in both OPM 3 and 4 the PV-UPQC system
Switching frequency of the NPC inverters fsw = 20 kHz performs the active power-line conditioning.
Sampling frequency of the DSC A/D converters fad = 60 kHz Fig. 12 shows the PV-UPQC operating in the OPM 5. In
Sampling frequency of the P&O-based MPPT fMPPT = 10 Hz this case, it is connected to a programmable AC power source
P&O-based MPPT step size voltage ∆v = 1V that provides distorted input voltages, such as voltage
PWM gain Kpwm = 0.002
unbalances, harmonics, and sags. As can be noted, even under
Load 1 - Single-phase full-bridge rectifiers followed by RL and RC loads
Phase A Phase B Phase C
distorted voltage conditions, the output voltages ( vL _ abc ) are
R = 6 Ω - L = 15.6 mH R = 8 Ω - L = 24.2 mH R = 53 Ω - C = 470 µF always balanced, regulated, and harmonic free. As the output
Sa = 1730 VA Sb = 1410 VA Sc = 870 VA voltages are controlled to be sinusoidal and balanced, the
Load 2 - Three-phase full-bridge rectifier followed by R load difference between the input voltages and output voltages
R = 40 Ω appears across the series transformers ( vTsc _ abc ).
Sa = 730 VA Sb = 720 VA Sc = 730 VA
Table IV presents the total harmonic distortion (THD) and
TABLE III rms values of voltages and currents related to the grid and
DESIGN SPECIFICATIONS AND GAINS OF THE P AND PI CONTROLLERS load. As can be seen, the THDs of both grid currents and
Series inverter PI current controller output voltages were reduced in all operation modes.
PIis crossover frequency ωcis = 10,472 rad/s Furthermore, Table IV also presents the power factors (PF)
PIis phase margin PMis = 85º related to the grid and load. As can be noted, effective PF
PIis current controller gains KPis = 820.05 KIis = 860,900
corrections were achieved.
Parallel inverter PI voltage and P current controllers The dynamic results for abrupt solar radiation changes are
PIvp crossover frequency ωcvp = 3,927 rad/s
presented in Figs. 13 and 14, in which are shown the total dc-
PIvp phase margin PMvp = 85º
PIvp voltage controller gains KPvp = 0.2347 KIvp = 80.643
bus voltage ( vdc ), dc-bus controller output signal ( idc ), feed-
Pip crossover frequency ωcip = 12,560 rad/s forward current ( i ff ), and PV array power ( Ppv ). The tests
Pip current controller gain KPip = 472.624
were performed disconnecting and reconnecting the PV array
dc-bus PI voltage controller
to the dc-bus at 2.5s and 15s, respectively. Fig. 13 shows the
PIvdc crossover frequency ωv dc = 22.619 rad/s
results when i ff is used to speed up generation of the series
PIvdc phase margin PM v dc = 80º
inverter current references. Fig. 14 shows similar tests
PIvdc voltage controller gains K Pv dc = 0.1095 K Iv dc = 0.4366
disregarding the FFC action. According to the results, the
PLL parameters and PI controller gains oscillations in the dc-bus voltage are reduced when i ff is used
PIPLL controller gains KPpll = 141.7 KIpll = 7,777.4
AF gain Kc = 300 during the PV array transients.
AF adaptation step-size µ = 0.005 Table V compares the experimental results presented in
Fig. 13 (with FFCL) and 14 (without FFCL). It can be
Fig. 8 presents the static results of the PV-UPQC system observed that the dc-bus voltage ( vdc ) dynamic response
operating as a classical UPQC feeding Load 1 (OPM 1 – (setting time and overshoot/undershoot) was strongly reduced
Operation Mode 1), where the grid currents ( isa , isb , isc ), under abrupt solar radiation changes when the FFCL is
grid neutral current ( isn ), load currents ( iLa , iLb , iLc ), load employed.
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 9
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 10
TABLE IV
THD, RMS VALUES OF THE VOLTAGES AND CURRENTS AND POWER FACTORS
Operation Total harmonic distortion (%)
Modes vsa vsb vsc isa isb isc vLa vLb vLc iLa iLb iLc
OPM 1 1.8 1.6 1.5 2.0 1.9 2.2 3.0 2.9 3.1 29.7 30.4 77.1
OPM 2 1.7 1.9 1.8 2.8 2.7 2.6 2.3 1.9 1.4 --- --- ---
OPM 3 2.1 2.2 2.1 6.7 6.5 6.0 2.6 2.2 1.7 27.2 27.1 26.4
OPM 4 1.8 1.8 1.9 5.4 5.4 4.5 2.5 2.2 1.7 27.2 27.1 26.4
OPM 5 10.6 10.9 11.1 4.5 3.9 3.9 2.2 2.0 1.5 26.7 27.3 26.6
rms Voltages (V) and Currents (A)
OPM 1 124 125 126 10.9 10.5 10.4 128 126 128 14.2 11.4 7.5
OPM 2 130 130 130 7.2 7.1 7.1 127 127 127 --- --- ---
OPM 3 127 128 128 2.6 2.5 2.5 126 127 127 5.6 5.6 5.7
OPM 4 127 127 126 3.1 3.0 3.0 127 126 127 5.6 5.6 5.7
OPM 5 110 100 90 5.0 4.8 4.6 102 100 100 4.5 4.4 4.4
Power Factor
utility grid loads
phase A phase B phase C phase A phase B phase C
OPM 1 1.0 1.0 1.0 0.93 0.93 0.63
OPM 2 -0.99 -0.99 -0.99 --- --- ---
OPM 3 -0.99 -0.98 -0.98 0.96 0.96 0.96
OPM 4 0.98 0.99 0.99 0.96 0.96 0.96
OPM 5 1.0 0.99 0.99 0.96 0.96 0.96
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 11
REFERENCES
[1] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodríguez, “Control of power
converters in AC microgrids,” IEEE Trans. Power Electron., vol. 27, no.
11, pp. 4734-4749, Nov. 2012.
[2] S. B. Kjaer, J. K. Pedersen, and F. Blaabjerg, “A review of single-phase
grid-connected inverters for photovoltaic modules,” IEEE Trans. Ind.
Appl., vol. 41, no. 5, pp. 1292-1306, Sept.-Oct. 2005.
Times [s] [3] W. Li, Y. Gu, H. Luo, W. Cui, X. He, and C. Xia, “Topology review and
(b) derivation methodology of single-phase transformerless photovoltaic
Fig. 15. Abrupt solar radiation change from OPM 1 to OPM 3 (Load 2 for inverters for leakage current suppression,” IEEE Trans. Ind. Electron.,
RL = 60 Ω): PV-UPQC performing active power injection plus active filtering vol. 62, no. 7, pp. 4537-4551, Jul. 2015.
with Ppv > PL (200V/div, 10A/div, 10ms/div): (a) Abrupt solar variation [4] L. Zhang, K. Sun, L. Feng, H. Wu, and Y. Xing, “A family of neutral
change with FFCL (0 % to 100 %): Phase “a” grid voltage (vsa), grid current point clamped full-bridge topologies for transformerless photovoltaic
(isa), load voltage (vLa) and PV array current (ipv); (b) Abrupt solar variation grid-tied inverters,” IEEE Trans. Power Electron., vol. 28, no. 2, pp.
change without FFCL (0 % to 100 %): Phase “a” grid voltage (vsa), grid 730-739, Feb. 2013.
current (isa), load voltage (vLa) and PV array current (ipv). [5] F. A. S. Neves, M. Carrasco, F. Mancilla-David, G. M. S. Azevedo, and
V. S. Santos, “Unbalanced grid fault ride-through control for single-
stage photovoltaic inverters,” IEEE Trans. Power Electron., vol. 31, no.
4, pp. 3338-3347, Apr. 2016.
[6] H. Xiao, and S. Xie, “Transformerless split-inductor neutral point
clamped three-level PV grid-connected inverter,” IEEE Trans. Power
Electron., vol. 27, no. 4, pp. 1799-1808, Apr. 2012.
[7] W. Libo, Z. Zhengming, and L. Jianzheng, “A single-stage three-phase
grid-connected photovoltaic system with modified MPPT method and
reactive power compensation,” IEEE Trans. Energy Convers., vol. 22,
no. 4, pp. 881-886, Dec. 2007.
[8] M. C. Cavalcanti, A. M. Farias, K. C. Oliveira, F. A. S. Neves, and J. L.
Afonso, “Eliminating leakage currents in neutral point clamped inverters
Time [s] for photovoltaic systems,” IEEE Trans. Ind. Electron., vol. 59, no. 1, pp.
(a) 435-443, Jan. 2012.
[9] Y. Tang, W. Yao, P. C. Loh, and F. Blaabjerg, “Highly reliable
transformerless photovoltaic inverters with leakage current and pulsating
power elimination,” IEEE Trans. Ind. Electron., vol. 63, no. 2, pp. 1016-
1026, Feb. 2016.
[10] Y. Kim, H. Cha, B. M. Song, and K. Y. Lee, “Design and control of a
grid-connected three-phase 3-level NPC inverter for building integrated
photovoltaic systems,” in Proc. IEEE PES Innovative Smart Grid
Technologies (ISGT), 2012, pp. 1-7.
[11] S. A. O. Silva, L. P. Sampaio, F. M. Oliveira, and F. R. Durand, “Feed-
forward DC-bus control loop applied to a single-phase grid-connected
PV system operating with PSO-based MPPT technique and active
Time [s]
power-line conditioning,” IET Renewable Power Generation, 2016.
(b)
[12] G. Ding, F. Gao, H. Tian, C. Ma, M. Chen, G. He, and Y. Liu,
Fig. 16. Load changes for OPM 3 (Load 2 for RL = 60 Ω): PV-UPQC
“Adaptive DC-link voltage control of two-stage photovoltaic inverter
performing active power injection plus active filtering with Ppv > PL
during low voltage ride-through operation,” IEEE Trans. Power
(100V/div, 10A/div, 10ms/div): (a) Load change (100 % to 0 %): Phase “a”
Electron., vol. 31, no. 6, pp. 4182-4194, Jun. 2016.
grid voltage (vsa), grid current (isa), load voltage (vLa) and load current (iLa); (b)
[13] S. Bacha, D. Picault, B. Burger, I. Etxeberria-Otadui, and J. Martins,
Load change (0 % to 100 %): Phase “a” grid voltage (vsa), grid current (isa),
“Photovoltaics in microgrids: An overview of grid integration and
load voltage (vLa) and load current (iLa).
energy management aspects,” IEEE Ind. Electron. Mag., vol. 9, no. 1,
VII. CONCLUSION pp. 33-46, Mar. 2015.
[14] J. M. Guerrero, P. C. Loh, T. Lee, and M. Chandorkar, “Advanced
This paper proposed a single-stage 3P4W grid-tied PV control architectures for intelligent microgrids-Part II: Power quality,
system, performing the tasks of a UPQC operating with a dual energy storage, and AC/DC microgrids,” IEEE Trans. Ind. Electron.,
compensating strategy, as well as the FFCL. The system vol. 60, no. 4, pp. 1263-1270, Apr. 2013.
[15] T. Wu, H. Nien, C. Shen, and T. Chen, “A single-phase inverter system
named PV-UPQC was built by means of two back-to-back for PV power injection and active power filtering with nonlinear
connected 3-level NPC inverters. Along with providing active inductor consideration,” IEEE Trans. Ind. Appl., vol. 41, no. 4, pp. 1075-
power from the PV arrangement, the PV-UPQC system was 1083, Jul./Aug. 2005.
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPEL.2017.2659381, IEEE
Transactions on Power Electronics
TPEL-Reg-2016-10-1873.R1 12
[16] F. M. Oliveira, S. A. O. Silva, F. R. Durand, L. P. Sampaio, V. D. Professor of Electrical Engineering. His research interests are
Bacon, and L. B. G. Campanhol, “Grid-tied photovoltaic system based related to power electronics applications involving UPQC
on PSO MPPT technique with active power line conditioning,” IET
Power Electronics, vol. 9, no. 6, pp. 1180-1191, May 2016. systems, active power-line filters, photovoltaic systems, power
[17] R. A. Modesto, S. A. O. Silva, and A. A. O. Júnior, “Power quality quality and digital signal processing and applications. He is
improvement using a dual unified power quality member of Brazilian Power Electronics Society.
conditioner/uninterruptible power supply in three-phase four-wire
systems,” IET Power Electronics, vol. 8, no. 9, pp. 1595-1605. Aug.
2015. Sérgio A. Oliveira da Silva (M’ 13) was
[18] R. A. Modesto, S. A. O. Silva, A. A. Oliveira, and V. D. Bacon, “A
versatile unified power quality conditioner applied to three-phase four- born in Joaquim Távora, Brazil, in 1964.
wire distribution systems using a dual control strategy,” IEEE Trans. He received the B.S. and M.S. degrees in
Power Electron., vol. 31, no. 8, pp. 5503-5514, Aug. 2016. electrical engineering from Federal
[19] B. W. França, L. F. Silva, M. A. Aredes, and M. Aredes, “An improved University of Santa Catarina (UFSC),
iUPQC controller to provide additional grid-voltage regulation as a
STATCOM,” IEEE Trans. Ind. Electron., vol. 62, no. 3, pp. 1345-1352, Florianopolis, SC, Brazil, in 1987 and
Mar. 2015. 1989, respectively. He received Ph.D.
[20] V. Khadkikar, “Enhancing electric power quality using UPQC: A degree from Federal University of Minas
comprehensive overview,” IEEE Trans. Power Electron., vol. 27, no. 5, Gerais (UFMG), Belo Horizonte, MG, Brazil, in 2001.
pp. 2284-2297, May 2012.
[21] H. Fujita, and H. Akagi, “The unified power quality conditioner: The Since 1993, he has been with the Electrical Engineering
integration of series- and shunt-active filters,” IEEE Trans. Power Department of Federal University of Technology (UTFPR-
Electron., vol. 13, no. 2, pp. 315-322, Mar. 1998. CP), Cornélio Procópio, PR, Brazil, where he is currently a
[22] M. Aredes, K. Heumann, and E. H. Watanabe, “An universal active full Professor of Electrical Engineering and coordinator of the
power line conditioner,” IEEE Trans. Power Del., vol. 13, no. 2, pp.
545-551, Apr. 1998. Laboratory of Power Electronics, Power Quality and
[23] M. C. Cavalcanti, G. M. S. Azevedo, B. A. Amaral, F. A. S. Neves, D. Renewable Energies. His research interests are related to
C. Moreira, and K. C. Oliveira, “A grid connected photovoltaic power electronics applications involving UPS systems, active
generation system with compensation of current harmonics and voltage power-line filters, photovoltaic systems, control systems and
sags,” Brazilian Power Electronics Journal, vol. 11, no. 2, pp. 93-101,
Jul. 2006. power quality. He is member of Brazilian Power Electronics
[24] S. Devassy, and B. Singh, “Dynamic performance of solar PV integrated Society and IEEE Industrial Electronics Society.
UPQC-P for critical loads,” in Proc. Annual IEEE India Conference
(INDICON), 2015, pp. 1-6.
[25] B. Han, B. Bae, H. Kim, and S Baek, “Combined operation of unified Azauri Albano de Oliveira Jr. was born
power quality conditioner with distributed generation”, IEEE Trans. in 1955. He received the B.S and M.S.
Power Del., vol. 21, no. 1, pp. 330-338, Jan. 2006.
[26] V. D. Bacon, and S. A. O. Silva, “Performance improvement of a three-
degrees in electrical/electronic
phase phase-locked-loop algorithm under utility voltage disturbances engineering from São Carlos Engineering
using non-autonomous adaptive filters,” IET Power Electronics, vol. 8, School (EESC), University of São Paulo
no. 11, pp. 2237-2250, Nov. 2015. (USP), São Carlos, SP, Brazil, in 1977
[27] S. Buso, and P. Mattavelli, Digital Control in Power Electronics.
Lincoln, NE, USA: Morgan & Claypool, 2006.
and 1984, respectively. He received the
[28] L. B. G. Campanhol, S. A. O. Silva, and A. Goedtel, “Application of Ph.D degree in electrical engineering
shunt active power filter for harmonic reduction and reactive power from Polytechnic School, University of São Paulo, São Paulo,
compensation in three-phase four-wire systems,” IET Power Electronics, SP, Brazil, in 1991.
vol. 7, no. 11, pp. 2825-2836, Nov. 2014.
[29] B. A. Angélico, L. B. G. Campanhol, and S. A. O. Silva, “Proportional–
Since 1978, he has been with the Electrical and Computing
integral/proportional–integral–derivative tuning procedure of a single- Engineering Department, EESC, USP, where he is currently a
phase shunt active power filter using Bode diagram,” IET Power professor of Electrical Engineering the coordinator of the
Electronics, vol. 7, no. 10, pp. 2647-2659, Oct. 2014. Power Electronics and Control Laboratory. His research
[30] K. Karanki, G. Geddada, M. K. Mishra, and B. K. Kumar, “A modified
three-phase four-wire UPQC topology with reduced dc-link voltage
interests include power electronics, electric machinery drives,
rating,” IEEE Trans. Ind. Electron., vol. 60, no. 9, pp. 3555-3566, wireless power transfer and engineering education.
Sept. 2013.
0885-8993 (c) 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.