Professional Documents
Culture Documents
2011-11 Energy Impacts of Chilled - Water-Piping Configurations
2011-11 Energy Impacts of Chilled - Water-Piping Configurations
Chilled-Water-Piping
Configuration
Examining the energy-saving potential Delta-T = chilled-water-temperature range
of three commonly used arrangements In a CPF configuration, load changes are reflected
by changing delta-T. Typically, a three-way valve is
By ROY S. HUBBARD placed on the discharge of each coil. The valve’s job is
Johnson Controls Inc. to maintain the set-point temperature of the air leaving
A
York, Pa. the coil. If the temperature of the air ventures above
or below its set point, the valve modulates the amount
As the cost of energy continues to rise, it behooves of chilled water flowing through the coil, with excess
chiller-plant owners and designers to consider the water bypassing the coil. This modulates the temperature
energy impacts of virtually everything under their control, of the chilled water within the coil in accordance with the
including chilled-water piping. formula above; coil capacity is adjusted until leaving-air
This article will discuss the energy consumption of temperature once again is at its set point. Throughout
the three basic configurations of chilled-water piping this process, operating chillers experience (roughly)
currently in use: constant primary flow (CPF), constant constant water flow.
primary flow/variable secondary flow (P/S), and variable Attributes. CPF designs have several advantages:
primary flow (VPF). Also, it will discuss the attributes • Equipment-room space is minimized because there
of equipment-room space, installed cost, and control is only one set of chilled-water pumps.
complexity. • Installed cost is low because constant-speed pumps
Senior marketing manager for Johnson Controls Inc., Roy S. Hubbard has more than 30 years of experience in sales, marketing,
and applications, with particular focus on chilled-water systems. He is the architect of YORKcalc,
FIGURE Johnson Controls’ operating-cost
1 (26p8 wide)
software for chiller plants. He has a bachelor’s degree in engineering from the United States Military Academy at West Point. He
can be contacted at roy.s.hubbard@jci.com.
Condenser
Primary pumps,
1,000 gpm each
are used, avoiding the expense of Secondary pumps,
Evaporator 3,000 gpm at 44°F
variable-speed drives (VSDs). Also,
low-pressure-differential-rated
Condenser VSD
three-way valves, which are less
expensive than high-pressure- VSD
Evaporator
differential-rated two-way valves,
are used. VSD
Circle 162
November 2011 HPAC Engineering 23
ENERGY IMPACTS OF CHILLED-WATER-PIPING CONFIGURATION
off, and the chiller was isolated Condenser 1,500 gpm at 44°F
with an automatic isolation valve
(not shown). Water velocity in the
Evaporator
two active evaporators is 4.5 fps VSD
Cooling coils
(0.75 × 6 fps), well above the 1.5-fps with two-way
Condenser
lower limit, so there is no need to valves
use the bypass pipe just yet.
Evaporator
Figure 7 shows the bypass operat- VSD 0 gpm
ing at 6.7-percent system load. 375 tons each
Primary pumps, Bypass valve
A ttr i b u t e s . Because only one 750 gpm each
set of chilled-water pumps is used,
1,500 gpm at 56°F Flow meter 1,500 gpm at 56°F
the VPF configuration takes up
less equipment-room space than FIGURE 6. At 50-percent load, one pump and one chiller in this VPF arrangement have cycled
the P/S configuration and the off, and the chiller has been isolated from any water flow. The water-flow rate is well above
same as the CPF configuration. The the minimum of 250 gpm, so the bypass pipe is not used.
installed cost is midway between
that of the P/S and CPF configu- Low-Delta-T Syndrome two-way
FIGURE 6 (26p8 wide) valves, and the use of air-
rations; there are no secondary All chilled-water systems with two- side economizers.1
pumps, valves, installation labor, way valves experience low-delta-T Chillers in a system suffering
or wiring, but bypass piping and syndrome. Low-delta-T syndrome from low-delta-T syndrome cannot
a bypass valve, as well as more is a reduction in chilled-water- be loaded above the ratio of actual
complex controls, are required. temperature range independent delta-T to design delta-T (i.e., if ac-
Additionally, the design is newer of load change. It increases the tual delta-T is 8 and design delta-T
than the CPF and P/S configurations energy consumption of variable- is 12, 8/12, or 67 percent, of chiller
and, thus, not as well understood speed-driven pumps and chiller capacity is all that is available, unless
by designers and operators. plants. It has many causes, including some mitigating action is taken). As a
Pump energy consumption is less dirty coils, controls out of calibration, result, chiller-plant energy consump-
than with the CPF and P/S arrange- leaky two-way valves, coils piped tion increases, as chillers, along with
ments. The variable-speed pumps backward, the mixing of three- and their associated pumps and towers,
save as much as 60 to 70 percent
annually, compared with a CPF de- Off and isolated
sign. Compared with a P/S arrange- Condenser
ment, design energy is reduced. This
is because: Evaporator
• Eliminating secondary pumps VSD