You are on page 1of 1

F = 5/8'' - 11 bolt & lockwasher

Z = min. 0.79'' [min. 20 mm]

Insulator - Number of sheds 21


dimensions - Line Post spacing X = 27.4 '' [ 697 mm ]
- Arcing distance 23.0 '' [ 585 mm ]
- Leakage distance, min. 59.4 '' [ 1508 mm ]
- Approximate weight 20.7 Lbs [ 9.4 kg ]

Electrical - Low frequency flashover voltage dry 231 kV


Characteristics wet 210 kV
- Critical impulse flashover voltage positive 392 kV
negative 484 kV
Mechanical - Specified Tensile Load (STL) 5,000 Lbs [ 22.2 kN ]
Characteristics - Max. Design Cantilever Load (MDCL) 1,250 Lbs [ 5.6 kN ]
- Specified Cantilever Load (SCL) 2,500 Lbs [11.1 kN ]

Component parts - Rod, nom. diam. = 1.75'' [ 45 mm] Epoxy impregnated glass fibers
- Housing HTV Silicone
- Insulator end-fittings Hot dip galvanized cast iron
- Gain base GB-12 Hot dip galvanized cast iron

This drawing contains confidential information that is the property of MacLean Power, L.L.C. ("MacLean"). Use of MacLean's confidential information without MacLean's express written consent is strictly prohibited and may expose you to legal liability. If you
believe that you received this material in error, please destroy it or return it to "MacLean Power, L.L.C., 11411 Addison, Franklin Park, Illinois 60131, USA."

NPKG 20 XG M21 S0
BKNG12XGM0AP IOE94129 IOE94100 IOE93571

Print date : 11/1/2006