You are on page 1of 53

12.05.

11
B.B.N.

V6/1087 12.05.11
12.05.11
B.B.N
V6/1087 12.05.11
12.05.11
B.B.N
V6/1087 12.05.11
12.05.11
B.B.N
V6/1087 12.05.11
14.06.11
B.B.N.
V6/1142 14.06.11
Alarms, Indications: for UPS(i4 series)

ALARMS Hi-Rel’s Reply at In drawing (drwg


prebid stage no: REL-
BGCPP-405-
D-000041)
AC input under voltage Input UV alarm provided Under voltage
through LCD. through LCD.
DC output over voltage DC over voltage alarm DC over voltage text
provided through LCD. readout through LCD.
DC output under voltage Low Batt trip alarm Low Batt through
provided through LCD. LCD
DC output circuit breaker fuse Visual Indication Batt iso. LA LED
trip provided. indication on MIMIC.
Common trouble alarm for Common alarm indication Common alarm
switchboard bus under voltage provided. through LED
indication on MIMIC.
Battery ground detection DC ground LED indication DC ground Alarm
provided through LCD. through LCD.
Switch board breaker / Fuse Not Envisaged. ----
open
Static switch transferred to other Transfer to ALT alarm Transfer to ALT alarm
source shall be provided through shall be provided
LCD. through LCD.
Manual Bypass transfer to Transfer to ALT alarm Transfer to ALT alarm
alternate source shall be provided through shall be provided
LCD. through LCD.
Bypass source fail ALT OV & UV alarm ALT OV & UV alarm
provided through LCD. provided through
LCD.
AC input fail Input UV & OV alarm Input UV & OV alarm
provided through LCD. provided through
LCD.
AC output fail Inverter UV & OV alarm Inverter UV & OV
provided through LCD. alarm provided
through LCD.
UPS battery fail Battery LOW alarm LOW BATT through
provided through LCD. LCD
DC Ground fault DC ground indication DC Ground through
provided. LCD.
Load on Battery LED indication provided Load on Battery
on Mimic. indication on MIMIC
through LED.

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-405-D-0000 41
HI-REL DOC NO : 105UL12341
Rev : A
---------------------------------------------------------------------------------------------------------------------
Alarms, Indications: for UPS(i4 series)

Load on Bypass LED indication provided BYP/ALT ON led


on Mimic. indication on MIMIC.
UPS failure (Common Alarm) Common Alarm Common alarm
through LED
indication on MIMIC.
Charger / Inverter Trip Charger /Inverter UV & Charger /Inverter UV
OV alarm provided & OV alarm provided
through LCD. through LCD.
Charger / Bypass AC mains fail Charger /ALT UV & OV Charger /ALT UV &
alarm provided through OV alarm provided
LCD. through LCD.
Charger / Battery output hi DC over voltage alarm DC over voltage text
provided through LCD. readout through LCD.
Charger output voltage low Not provided. ----
Fan failure or Temperature Hi LED indication, OT alarm INV OVER LD TRIP
provided through LCD. through LCD.
Charger / Inverter fuse failure LED indication LED indication
provided.
UPS overload Inverter Overload alarm Overload through
provided through LCD. LCD.
Battery disconnected LED indication Batt iso. LA LED
indication on MIMIC.
Inverter and bypass not Frequency out of limit Frequency out of
synchronized alarm provided through limit alarm provided
LCD. through LCD.
Earth output (if floating) No alarm. ----

We confirm that common alarm will be generated when any alarm is raised from
the above list of alarms.

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-405-D-0000 41
HI-REL DOC NO : 105UL12341
Rev : A
---------------------------------------------------------------------------------------------------------------------
12.05.11
B.B.N.
V6/1087 12.05.11
12.05.11
B.B.N
V6/1087 12.05.11
12.05.11
B.B.N
V6/1087 12.05.11
12.05.11
B.B.N.
V6/1087 12.05.11
12.05.11
B.B.N.
V6/1087 12.05.11
! ! " # $ %& '

!! !
! " # $ %& % & ' ! () *
+ # , - . / ) # 0 !
. / ) 0
* . / ) 0
0 . / ) 0
1 2 " % " /' * 3 *
4 5 " /' 5( 55 * 3 * !
5 /' 5( 55 * 3 *
-. 5 /' 5# 0 *
- 6 785 - ! 9
! - 785 !
+ 6 : 9 : 6 + 2 ;
6 785 *! 12.05.11
* ' ( # 7 < /( + B.B.N.
0 ' ( # 7 + =( *
1 - - 5 , / ( # 5 !9
4 - 5 , / ( # 5 9
# , >> % ( # (0 !
>> % ( # (1
-+ ; : 8 %> ' % ( # (* V6/1087 12.05.11
! -+ / % ( # (
+ -+ . ? % ( # (
6; % ( # (+
* -+ /6 " @ 6 %> % ( # (
0 A % ( # (
1 !; " % ( # (!
4 : % ( # (+
! 5 / / $ 2
! ; 9 (- ( 9
! =; > > = ? - % " 65#
!! =; > = ? - % " 65#

;# B 5 C! 62 7 .# =; ;5- ; 2 # ;# B 5
7- &5 # 7- & -& # 5#= 5=# 75 <
#-& # 2. & < # 7 . ;; &+ D +0
(-# 7 2. & < = !+ # E
; .
DETAIL BILL OF MATERIAL OF ACDB FOR 5KVA UPS

Sr. Components
No. Description Make Ckt. Ref. Rating Qty(n)
1 Incomer DPMCB L&T CBI 63A 10KA 1
2 Incomer Fuse Ge/Bussman/Farraz FL,N 63A 2
3 Feeder DPMCB L&T CBF1-3 32A 3
4 Feeder DPMCB L&T CBF4-10 16A 7
5 Feeder DPMCB L&T CBF11-14 10A 4
6 HRC Fuse Ge/Bussman/Farraz FL,N1-3 32A 6
7 HRC Fuse Ge/Bussman/Farraz FL,N4-10 16A 14
8 HRC Fuse Ge/Bussman/Farraz FL,N11-14 10A 8
9 I/P Voltmeter (72X72) Meco/Rishabh VM1 0-300VAC 1
10 I/P Ampmeter (72X72) Meco/Rishabh AM1 0-50A 1
11 Terminal Elmex/Connect Well - - -
12 Panel SKE/ABHISHEK - - -

12.05.11
B.B.N.

V6/1087 12.05.11

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 48
HIREL DWG NO. 105AB12341 REV:B
PAGE 1 OF 1
DETAIL BILL OF MATERIAL OF AUXILLARY PANEL FOR 5KVA UPS
Sr. No. Components Description Make Ckt. Ref. Rating Qty(n)
1 Input MCCB L&T CBI 32A 50KA 1
2 Bypass Isolation Transformer (3Ph-1Ph) HI-REL TF1 5KVA 1
3 Servo Control Voltage Stabilizer (240V,1Ph/240V, 1Ph) HI-REL SCVS 5KVA 1
4 O/P Voltmeter (72x72) Meco/Rishabh VM1 0-300V 1
5 O/P Ampmeter (72x72) Meco/Rishabh AM1 0-50A 1
6 Power Terminal Elmex/Connect well DPBB-50 - -
7 Panel SKE/ABHISHEK - - -

12.05.11
B.B.N.

V6/1087 12.05.11

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 49
HIREL DWG NO. 105XB12341 REV:B
PAGE 1 OF 1
DETAIL BILL OF MATERIAL OF BATTERY JUNCTION BOX FOR 5KVA UPS

Components
Sr. No. Description Make Ckt. Ref. Rating Qty(n)
1 Fuse Ge/Bussman/Farraz F8,9 32A 2
2 Power Terminal ELMEX/Connect Well DPBB-50 DPBB-50 -
3 Panel SKE/ABHISHEK - - -

12.05.11
B.B.N.

V6/1087 12.05.11

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 50
HIREL DWG NO. 105DB12341 REV:B
DETAIL BILL OF MATERIAL OF MANDATORY SPARES FOR 5KVA UPS

Sr. No. Components Description Make Rating Qty(n)


1 Static Switch Thyristor Semikron TT-26A, 1600V 2
2 Manual Bypass Switch Kaycee / Switch on 40A 2W 1P 2
3 IGBT Semikron 75A 600V 1
4 Diode Semikron DD-26A,1600V 1
5 Input MCCB L&T 32A 50KA 1
6 Bypass Isolator L&T 32A 1
7 Battery MCCB L&T 63A 1
8 Rectifier Input Fuses Ge/Bussmann/Farraz 75A 3
9 Rectifier output Fuse Ge/Bussmann/Farraz 75A 1
10 Battery Fuse Ge/Bussmann/Farraz 75A 1
11 Bypass Fuse Ge/Bussmann/Farraz 75A 1
12 Electronics Card Module 1 SET
12.1 Rectifier Snubber Card HI-REL - 1
12.2 Static Snubber Card HI-REL - 1
12.3 I4 Power Supply & Feedback Card HI-REL - 1
12.4 I4 System Control Card HI-REL - 1
12.5 I4 Gate Driver Card HI-REL - 1
12.6 SMPS Card HI-REL - 1
12.7 I4 System Manager+ Modbus Card HI-REL - 1
12.8 Bypass Square Card HI-REL - 1
12.05.11
12.9 3Ph Charger Card HI-REL - 1
B.B.N.
12.10 Switcher Card HI-REL - 1
13 Current Transformer (i/p) G.Mexwell CT 50/5 1
14 Current Transformer (o/p) G.Mexwell CT 50/5 1
15 Cooling Fans (4”) Rexnord/Nadi/Nisiki 230Vac 50Hz 1
16 LED Lamp Precifine 230VAC 5 V6/1087 12.05.11
17 AC Capacitor ALCON/Epcos/Systec 50uF 500VAC 4
18 DC Capacitor ALCON/Epcos/BC(philips) 3300uFD 350V 8

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-0000 51
HIREL DWG NO. 105SB12341 REV:B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
A UPS SYSTEM

1.0 Model : I4 Series

1.1 Make : HI – REL ELECTRONICS PVT LTD

1.2 Type : PWM IGBT based

1.3 Reference Standard : IEC 62040 – 3

2.0 Dimension & Weights :

2.1 Number of cabinets : Three

2.2 Dimension of Inverter cabinet (W x H x : 660 X 1715 X 750


D) mm

2.3 Dimension of static switch cabinet (W x : Included in inverter panel


H x D) mm

2.4 Dimension of Charger cabinet (W x H x : Included in inverter panel


D) mm

2.5 Dimension of D.C. distribution board : 650 x 550 x 300


(batt jn Box ) (W x H x D) mm

2.6 Dimension of A.C. distribution board (W : 700 x 1500 x 750


x H X D) mm

2.7 Dimension of transformer and stabilizer : 660 x 1715 x 750


panel (WxHxD) mm

2.8 Dimension of any other UPS cabinet, if : NIL


furnished (WxHxD)mm

2.9 Overall dimension (LxHxD) mm : 1360 x 1715 x 750 12.05.11


B.B.N
2.10 Weight of the following with all
equipment installed.

a. Inverter cabinet (Kg) : 300 Kg (approx)


V6/1087 12.05.11

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
b. Static switch cabinet (Kg) : Included in inverter panel

c. Charger cabinet (Kg): : Included in inverter panel

d. D.C. Distribution boards (Kg.) : 50 Kg (approx)

e. A.C. Distribution boards (Kg.) : 150 Kg (approx)

f. Transformer and stabilizer panel : 200 Kg (approx)


(Kg)

g. Other UPS cabinet (Kg.) : NIL

h. Total weight (Kg) : 500 Kg (approx)

3.0 Heat load for Ventilation/Air Conditioning


requirement

a. Inverter and static switch at 100% : 0.44 KW


load

b. Inverter and static switch at 50% : 0.26 KW


load

c. Inverter and static switch at 33% : 0.2 KW


load

d. Charger and accessories at 100% : 0.34 KW


load

e. Charger and accessories at 50% : 0.28 KW


load

f. UPS battery : Not in scope of Hi-Rel

B. STATIC INVERTER

1.0 General

1.1 Make : HI-REL ELECTRONICS PVT LTD

1.2 Cat. No : I4 Series

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
1.3 Type : PWM using IGBT

1.4 Reference Standard : IEC 62040 – 3

2.0 D.C. Input :

2.1 Voltage (Volt) : 220 VDC – Nominal

2.2 Current

a. No load (Amp) : 0.8 Amp

b. Full load (Amp) : 18.16 Amp

3.0 A.C. Output

3.1 Voltage + % variation (Volt) : 230VAC, 1Ph +/- 1%

3.2 Frequency +_ % variation (Hz) : 50 Hz +/- 0.1% (free running


mode)
3.3 No load Current (Amp) : Nil

3.4 Full load Current (Amp) : 21.74 Amp

3.5 Maximum inrush current during inverter : Nil, soft start provided
energisation (Amp)

4.0 Capacity

4.1 Rated full load capacity at unity power : 4 KVA / 4KW


factor

4.2 Rated full load capacity at 0.8 power : 5 KVA / 4 KW


factor

5.0 Performance

5.1 Regulation for 0-100% rated load at all : +/- 1%


Input voltage (%)

5.2 Transient output voltage regulation on : +/- 5%, 98% recovery within 20ms
application and removal of 100% load
(%)
---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name

5.3 Frequency variation for all conditions of : +/- 0.1% (Free Running), +/- 1% to
input supply, load and temperature +/-6% field settable
occurring simultaneously or in any synchronization range in step of
combination (%) 1%

5.4 Total harmonic content at rated load : <2.5% for linear load

5.5 Overload capacity at 100 percent voltage

a For 4 milliseconds (%) (for clearing) : 300%

b For 100 milliseconds % : 200%

c. For 60 seconds (%) : 150%

d. Capacity to clear maximum fuse : Semi conductor fuse of 30%


rating and duration of rated capacity & 4 msec

5.6 Overload capacity at 90 percent voltage

a. For 4 milliseconds (%) : 300%

b. For 100 milliseconds (%) : 200%

c. For 60 seconds : 150%

5.7 Inverter Efficiency (Watt output/Watt


input)

a. Rated load at 1.0 PF/0.8 PF(%) : 89%

b. 50% Rated load at 1.0 PF/0.8 PF : 87%


(%):

c. 33% Rated load at 1.0 PF/0.8 PF : 85%


(%)

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name

6.0 Miscellaneous

6.1 Inverter provided with following features

a. Automatic voltage regulation : Provided

b. Current limiting circuitry : Provided

c. Wave shaping circuit : Provided

d. Transient recovery circuit : Provided

e. Automatic synchronising circuit : Provided

f. Soft-start feature : Provided

g. Smoothing filter circuit : Provided

6.2 SCR elements provided with

a. Surge protection : Provided

b. Fast acting HRC fuse : Provided

6.3 Fuse type size and characteristics.

a. Inverter input : Not envisaged as output is


current limited
b. Inverter output : Not envisaged as output is
current limited
6.4 Inverter auxiliary equipment along with : Yes
necessary alarms furnished as per
specification (Yes/No)

6.5 Cooling

a. Type : Forced air cooled

b. Number of fans : Six

c. Operating time at full load without : 30 mins


forced air cooling

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
6.6 Technical literature for inverter and : Provided with O&M manual
auxiliary equipment furnished? (Yes/No)

C. STATIC TRANSFER SWITCH

1.0 General

1.1 Make : HI-REL ELECTRONICS PVT


LTD
1.2 Cat. No : ---

1.3 Type : Bi-Directional Thyristorized

1.4 Reference Standard : IEC 62040 – 3

2.0 Ratings : 21.74 Amp

2.1 Rated voltage (Volt) : 230 VAC

2.2 Rated current : 21.74 Amp

2.3 Transfer time (ms) : < 4 msec in sync mode &


< 20 msec in Async mode
3.0 Performance :

3.1 Overload capacity

a. For 100 milliseconds (%) : 750%

b. For 60 seconds (%) : 150%

c. For indefinite period (%) : 100%

4.0 Miscellaneous

4.1 Oscillographic records for transfer : During the Factory Test


operation furnished? (Yes/No)

4.2 Static transfer switch auxiliary equipment : Yes


along with necessary alarm furnished as
per specification? (Yes/No)

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
4.3 Technical literature for static transfer : Provided with O&M manual
switch and auxiliary equipment
furnished? (Yes/No

D MANUAL BY-PASS SWITCH

1.0 General

1.1 Make : Kaycee / Switch-On

1.2 Cat. No : --

1.3 Type : Make before break

1.4 Reference Standard : ---

2.0 Ratings :

2.1 Rated voltage (Volt) : 230 VAC

2.2 Rated current (Amp) : 40 Amp

3.0 Miscellaneous

3.1 Contact configuration and type of switch : Yes


as per specification furnished? (Yes/No)

3.2 Technical literature on manual by-pass : Provided with O&M manual


switch furnished? (Yes/No)

E. BATTERY CHARGER

1.0 General

1.1 Make : HI – REL ELECTRONICS PVT LTD

1.2 Cat. No. : I4

1.3 Type : 6 pulse full wave

1.4 Reference Standard : IEC 62040 – 3

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
2.0 A.C. Input

2.1 Voltage ±% variation (Volt) : 415 VAC +10%, -15%

2.2 Phase (No) : Three

2.3 Frequency ± % variation (Hz) : 50 Hz + 6%

2.4 Input amps at the following loads in


addition to supply the battery charging
current.

a. 50% rated load (Amp) : 14 Amp

b. 100% rated load (Amp) : 18 Amp

c. 110% rated load (Amp) : 19 Amp

2.5 Charger maximum inrush current: :

3.0 D.C. Output

a. Voltage (Volt/Cell) : 2 V/ Cell

b. Current (Amp) : 38 Amp

4.0 Performance :

4.1 Regulation for 0-100% rated load with : +/- 1%


±10% Input voltage and ±5% input
frequency variation (%)

4.2 Ripple content in D.C. output:

a. With battery (%) : + 1% RMS

b. Without battery (%) : + 2% RMS

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
4.3 Efficiency at

a. 50% rated load (%) : 93%

b. 100% rated load (%) : 89%

4.4 Power Factor at rated load (%) : 0.8

4.5 Maximum fault current for the short


circuit at output terminals.

a. With current limiting device : 10 KA


operative (KA)

b. With current limiting device in : 10 KA


operative (KA):

5.0 Miscellaneous

5.1 Charger provided with following features

a. Automatic voltage regulation : Provided

b. Current limiting circuitry : Provided

c. Smoothing filter circuit : Provided

d. Soft-start feature : Provided

e. Automatic load sharing during : NA for Stand Alone UPS


parallel operation

5.2 SCR elements provided with

a. Surge protection : Provided

b. Fast acting HRC fuse : Provided

5.3 Maximum temp. within cubicle above


50oC ambient

a. Rectifier transformer ( oC) : 85 Deg C

b. SCR (oC) : 35 Deg C

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
5.4 Charger auxiliary equipment along with : Yes
necessary alarms furnished as per
specification (Yes/No)

5.5 Cooling

a. Type : Forced

b. Number of fans : Common panel for Inverter &


charger
c. Operating time at full load without : 30 mins
forced air cooling

5.6 Technical literature for charger and : Provided in O&M manual


auxiliary equipment furnished?

F. STEP DOWN TRANSFORMER

1.0 General

1.1 Make : HI-REL ELECTRONICS PVT


LTD
1.2 Type : Open – Delta (3Ph to 1 Ph)

1.3 Number of phase : 3 Phase in primary & 1 Phase


in secondary
1.4 Frequency (Hz) : 50 Hz

1.5 Type of cooling : Natural

1.6 Class of insulation : F

2.0 Rating :

2.1 Capacity (KVA): : 5 KVA

2.2 Rated voltage

a. H.V. (KV) : 0.415 KV

b. L.V. (KV) : 0.230 KV

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
2.3 Rated current

a. H.V. (Amp) : 13 Amp

b. L.V. (Amp) : 21.74 Amp

3.0 Performance :

3.1 Guaranteed loss at 100% rated voltage : 0.35 KW


and rated frequency (KW)

3.2 No load loss (KW) : 0.14 KW

3.3 Copper loss at full load at 75oC (KW) : 0.21 KW

3.4 Efficiency at 75oC at unity power factor

a. at full load (%) : 94%

b. at 3/4th. load (%) : 92.7%

c. at ½ load (%) : 91%

G. VOLTAGE STABILIZER

1.0 General

1.1 Make : HI-REL ELECTRONICS PVT


LTD
1.2 Type : Servo controlled

1.3 Number of phase : 1 Phase

1.4 Frequency (Hz) : 50 Hz

1.5 Type of cooling : Natural

1.6 Class of insulation : F

2.0 Rating

2.1 Capacity (KVA) : 5 KVA

2.2 Rated voltage : 230 VAC

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name

3.0 Performance

3.1 Guaranteed loss at 100% rated voltage 0.06 KW


and rated frequency KW

3.2 No load loss (KW) : 0.02 KW

3.3 Copper loss at full load at 75oC (KW) : 0.04 KW

3.4 Efficiency at 75oC at unity power factor

a. at full load (%) : 98.5%

b. at 3/4th. load (%) : 97.8%

c. at ½ load (%) : 97.2%

H. DISTRIBUTION BOARD

1.0 General

1.1 Make & Type : HI-REL ELECTRONICS PVT


LIMITED
Non-compartmentalized
1.2 Degree of protection : IP-52

1.3 Sheet steel thickness : 2 mm for load bearing & 1.6


mm for non-load bearing
1.4 Mounting : Floor mounted

1.5 Dimension (W x H x D) (mm) : 700 x 1500 x 750

1.6 Weight (Kg) : 150 kG (approx)

1.7 Fuse

a. Make : For Fuse = GE / Bussman /


Ferraz
For MCB = Scheider / GE /
L&T
b. Type & characteristic for branch : HRC type fuses
circuit protection

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
SCHEDULE – II : TECHNICAL PARTICULARS

HI REL ELECTRONICS PVT LTD


Bidder's Name
1.8 Terminals

a. Make & Type : Elemax

b. 20% spare terminals furnished? : NO


(Yes/No)

1.9 Technical literature/curves for fuse, : Provided with O&M Manual


circuit breakers switches furnished?
(Yes/No)

---------------------------------------------------------------------------------------------------------------------

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RIIFRA DOC NO : REL-BGCPP-VEN-405-S-000052
HI-REL DOC NO : 105TS12341
Rev : B
/0" . %#" ! %#"
! " ! # ! " ! # " "!$"$ %#" & '"
" ! # 0" "!1 2

! - ! # #
" #
$ ! #
& # &- ! # #
% " #
' #

14.06.11
() *++) , +)) -
%#" ! B.B.N.
! "! # . "" ! " ! # " ! # /0" " "!$"$ %#" & '"
0"
( " !
( ( #
" !
% ( " !
(
( + " ! V6/1142 14.06.11
$ ( " !
#( ( &
" !
'
( ) " !
% ! (! #(
" !
( " !
#(* %
" !
( " !
! #(* $
" !
&

( * ( # + ( ! (* (
# # #
*+ ( # + ! % )
" # *+ ( # % !, ,
+ (
Alarms, Indications: for UPS(i4 series)

ALARMS Hi-Rel’s Reply at In drawing (drwg


prebid stage no: REL-
BGCPP-405-
D-000041)
AC input under voltage Input UV alarm provided Under voltage
through LCD. through LCD.
DC output over voltage DC over voltage alarm DC over voltage text
provided through LCD. readout through LCD.
DC output under voltage Low Batt trip alarm Low Batt through
provided through LCD. LCD
DC output circuit breaker fuse Visual Indication Batt iso. LA LED
trip provided. indication on MIMIC.
Common trouble alarm for Common alarm indication Common alarm
switchboard bus under voltage provided. through LED
indication on MIMIC.
Battery ground detection DC ground LED indication DC ground Alarm
provided through LCD. through LCD.
Switch board breaker / Fuse Not Envisaged. ----
open
Static switch transferred to other Transfer to ALT alarm Transfer to ALT alarm
source shall be provided through shall be provided
LCD. through LCD.
Manual Bypass transfer to Transfer to ALT alarm Transfer to ALT alarm
alternate source shall be provided through shall be provided
LCD. through LCD.
Bypass source fail ALT OV & UV alarm ALT OV & UV alarm
provided through LCD. provided through
LCD.
AC input fail Input UV & OV alarm Input UV & OV alarm
provided through LCD. provided through
LCD.
AC output fail Inverter UV & OV alarm Inverter UV & OV
provided through LCD. alarm provided
through LCD.
UPS battery fail Battery LOW alarm LOW BATT through
provided through LCD. LCD
DC Ground fault DC ground indication DC Ground through
provided. LCD.
Load on Battery LED indication provided Load on Battery
on Mimic. indication on MIMIC
through LED.

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-VEN-405-K-0000 53
HI-REL DOC NO : 105CL12341
Rev : A DATE:26.5.11 PAGE1 OF 2
---------------------------------------------------------------------------------------------------------------------
Alarms, Indications: for UPS(i4 series)

Load on Bypass LED indication provided BYP/ALT ON led


on Mimic. indication on MIMIC.
UPS failure (Common Alarm) Common Alarm Common alarm
through LED
indication on MIMIC.
Charger / Inverter Trip Charger /Inverter UV & Charger /Inverter UV
OV alarm provided & OV alarm provided
through LCD. through LCD.
Charger / Bypass AC mains fail Charger /ALT UV & OV Charger /ALT UV &
alarm provided through OV alarm provided
LCD. through LCD.
Charger / Battery output hi DC over voltage alarm DC over voltage text
provided through LCD. readout through LCD.
Charger output voltage low Not provided. ----
Fan failure or Temperature Hi LED indication, OT alarm INV OVER LD TRIP
provided through LCD. through LCD.
Charger / Inverter fuse failure LED indication LED indication
provided.
UPS overload Inverter Overload alarm Overload through
provided through LCD. LCD.
Battery disconnected LED indication Batt iso. LA LED
indication on MIMIC.
Inverter and bypass not Frequency out of limit Frequency out of
synchronized alarm provided through limit alarm provided
LCD. through LCD.
Earth output (if floating) No alarm. ----

M/s HI-REL confirms that common alarm(PF contact) will be generated when any
of the alarms indicated in above mention list appears on the LCD screen of UPS
Panel.

Project : 2 x 300 MW Coal based group captive power project


Client : Reliance Infrastructure Limited
RINFRA DWG. NO. :-REL-BGCPP-VEN-405-K-0000 53
HI-REL DOC NO : 105CL12341
Rev : A DATE:26.5.11 PAGE2 OF 2
---------------------------------------------------------------------------------------------------------------------
12.05.11
B.B.N
V6/1087 12.05.11
Sheet3

ACDB FEEDER LIST FOR 5 KVA UPS

Cable in Recommende
Sr. No Feeder No From Location From Terminal Terminal type MCB FUSE
Scope d Cable size
TA-2 - 1 (L) 2C x 6 Sq mm
1 FEEDER -1 32A 32A RINFRA
TA-2 - 2 (N) AYFY
TA-2 - 3 (L) 2C x 6 Sq mm
2 FEEDER -2 32A 32A RINFRA
TA-2 - 4 (N) AYFY
TA-2 - 5 (L) 2C x 6 Sq mm
3 FEEDER -3 32A 32A RINFRA
TA-2 - 6 (N) AYFY
TA-2 - 7 (L) 2C x 6 Sq mm
4 FEEDER -4 16A 16A RINFRA
TA-2 - 8 (N) AYFY
TA-2 - 9 (L) 2C x 6 Sq mm
5 FEEDER -5 16A 16A RINFRA
TA-2 - 10 (N) AYFY
TA-2 - 11 (L) 2C x 6 Sq mm
6 FEEDER -6 16A 16A RINFRA
TA-2 - 12 (N) AYFY
TA-2 - 13 (L) 2C x 6 Sq mm
7 FEEDER -7 16A 16A RINFRA
TA-2 - 14 (N) AYFY
ACDB TA-2 - 15 (L) KUT 10 2C x 6 Sq mm
8 FEEDER -8 16A 16A RINFRA
TA-2 - 16 (N) AYFY
TA-2 – 17 (L) 2C x 6 Sq mm
9 FEEDER-9 16A 16A RINFRA
TA-2 – 18 (N) AYFY
TA-2 – 19 (L) 2C x 6 Sq mm
10 FEEDER -10 16A 16A RINFRA
TA-2 – 20 (N) AYFY
TA-2 – 21 (L) 2C x 6 Sq mm
10A 10A RINFRA
11 FEEDER -11 TA-2 – 22 (N) AYFY
TA-2 – 23 (L) 2C x 6 Sq mm
12 FEEDER -12 10A 10A RINFRA
TA-2 – 24 (N) AYFY
TA-2 – 25 (L) 2C x 6 Sq mm
FEEDER -13 10A 10A RINFRA
13 TA-2 – 26 (N) AYFY
TA-2 – 27 (L) 2C x 6 Sq mm
14 FEEDER -14 10A 10A RINFRA
TA-2 – 28 (N) AYFY

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-K-0000 55
HIREL DWG NO. 105CL12341 REV:A
PAGE 1 OF 1

12.05.11
B.B.N.

V6/1087 12.05.11

Page 2
12.05.11
B.B.N
V6/1087 12.05.11
12.05.11
B.B.N
V6/1087 12.05.11
12.05.11
B.B.N
V6/1087 12.05.11
12.05.11
B.B.N.
V6/1087 12.05.11
SCOPE

SCOPE OF SUPPLY FOR 5KVA UPS

Sr.
No. MARERIAL HEAD Qty (n) REMARKS

1 5 KVA UPS SYSTEM 1 NO. UPS


2 AUXILLARY 1 NO. I/P ISOLATION X'MER + SCVS
3 BATTERY JN. BOX 1 NO. WALL MOUNTED
4 ACDB 1 NO. FLOOR MOUNTED NON-COMPARTMENTALIZED
5 MODBUS CONNECTIVITY ----- IN BUILT IN UPS
6 UPS TO BATTERY CABLE 2 X 20 METERS 1C,UN-10 UNINYVIN Flexible cu cable
7 UPS TO ACDB CABLE 2 X 20 METERS 1C, UN-8 UNINYVIN. Flexible cu cable
Quantity : 2Sets

Sr. 12.05.11
No. MARERIAL HEAD Qty (n) REMARKS
1 Mandatroy Spares 1 SET ----- B.B.N.

V6/1087 12.05.11
PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT
CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-Q-000060
HIREL DWG NO. 105GB12341 REV:0
PAGE 1 OF 1

Page 8
STAND ALONE UPS SYSTEM-I4 SERIES

An uninterrupted Power Supply is employed for critical loads which cannot be


powered by utility supply (mains) directly.

OPERATION MODES

1. NORMAL MODE: 12.05.11


B.B.N.

V6/1087 12.05.11

When the utility is normal , the UPS powers the load through the rectifier and
inverter and charging the batteries at the same time, as shown in above figure. This is
called Normal Mode.

2. BATTERY MODE:
Failure of the Utility supply or fault in the rectifier/charger section. Inverter will
feed load from the Battery.
After resumption of the Utility supply, battery will undergo chargering & inverter
will feed load from the rectifier/charger.

3. Maintenance Mode
Should the UPS module need to be taken out of service for limited maintenance or
repair, manual activation of the bypass shall cause an immediate transfer of the
connected a.c. load from the inverter to the bypass source. Full electrical isolation of
the UPS system shall therefore be obtained, without disruption to the critical load, by
operation of an integral wrap-around maintenance bypass switch.

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-W-000061
HIREL DWG NO. 105WR12341 REV:0
HI - REL ELECTROINCS LIMITED
SUB VENDOR LIST FOR 5KVA

Sr. No. Description Name


1 AC CAPACITORS M/S EPCOS
M/S SYSTEC
M/S ALCON
2 DC CAPACITORS M/S EPCOS
M/S PHILLIPS
M/S ALCON
3 COOLING FANS M/S NADI
M/S REXNORD
M/S NISHIKI
4 FUSES M/S GE
M/S FERRAZ
M/S BUSMANN
5 THYRISTORS M/S SEMIKRON
6 IGBT M/S SEMIKRON
7 MCCB M/S L&T
8 ISOLATOR M/S L&T
9 SWITCH KAYCEE / SWITCH-ON
10 CHOKE M/S HI-REL
11 ELECTRONICS CARDS M/S HI-REL
12 METERS M/S MECO
M/S RISHABH
13 TRANSFORMER M/S HI-REL
14 STATIC SWITCH (THY.) M/S SEMIKRON
15 TERMINALS M/S ELMAX
M/S CONNECTWELL
16 SCVS M/S HI-REL
17 MCB M/S L&T
18 POWER CABLE M/S INDUSTRIAL GLASS
19 CONTROL CABLE M/S INDUSTRIAL GLASS
M/S LAPP

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-U-000064

PAGE 1 OF 1

12.05.11
B.B.N.

V6/1087 12.05.11
CABLE SIZING CALCULATION

• INPUT CABLE FOR AUX: -


SELECTED TRANSFORMER IS : 5kVA
PRIMARY RATED CURRENT : 6.96 AMPS. 6.96X1.732A = 12.05
(DUE TO OPEN DELTA CONNECTION)
SELECTED CABLE IS 10sqmm 3C AYFY CABLE.
CURRENT HANDLING CAPACITY IS 40 AMPS @ 50 Deg.C AMBIENT.

• INPUT CABLE FOR UPS : -


SELECTED TRANSFORMER IS : 13kVA
PRIMARY RATED CURRENT : 18.09 AMPS.
SELECTED CABLE IS 10sqmm 3C AYFY ,CABLE.
CURRENT HANDLING CAPACITY IS 40 AMPS @ 50 Deg.C AMBIENT.

17.06.11
B.B.N.

V6/1152 17.06.11

PROJECT 2X300MW COAL BASED GROUP CAPTIVE POWER PROJECT


CLIENT RELIANCE INFRASTRUCTURE LTD.
RINFRA DWG NO. REL-BGCPP-VEN-405-S-000065
Page : 01 OF 01