You are on page 1of 9

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/224232433

Electrical Safety of Street Light Systems

Article  in  IEEE Transactions on Power Delivery · August 2011


DOI: 10.1109/TPWRD.2011.2131690 · Source: IEEE Xplore

CITATIONS READS
10 14,898

3 authors, including:

Giuseppe Parise Massimo Mitolo


Sapienza University of Rome Irvine Valley College
221 PUBLICATIONS   1,789 CITATIONS    149 PUBLICATIONS   580 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

METERGLOB View project

Electrical Safety in Arc Welding Processes View project

All content following this page was uploaded by Massimo Mitolo on 10 March 2015.

The user has requested enhancement of the downloaded file.


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

IEEE TRANSACTIONS ON POWER DELIVERY 1

Electrical Safety of Street Light Systems


Giuseppe Parise, Fellow, IEEE, Luigi Martirano, Senior Member, IEEE, and Massimo Mitolo, Senior Member, IEEE

Abstract—Street light systems are publicly accessible electrical the risk of breakdown of both layers of insulation is deemed
pieces of equipment out of the physical control of who operates/ extremely low.
owns them. Street lighting systems typically include low-voltage However, double insulation of Class II components of street
loads, distributed in a large area, and are collectively protected
by the same device. Under fault conditions, hazardous potentials lighting systems may actually fail during their life-cycle. This
may appear on the metal enclosures of these systems, and expose may be caused by lack of maintenance due to their possible large
people to shock hazards. To reduce the risk to an acceptable level, extension, as well as by their critical operating conditions, such
different solutions for the bonding and grounding are available. as, for example, car impacts or animal intrusions into poles. As
The Standard IEC 60364 and a current worldwide tendency seem a consequence, the loss of the double insulation of components
to encourage the use of Class II equipment for the street light sys-
tems. Class II components, such as the wiring systems, the light within metal poles, which may go undetected if the leakage cur-
fixtures, etc., have double or reinforced insulation. In this paper, rent is below the trip setting of protective overcurrent devices,
these authors analyze technical alternatives to protect against in- exposes people to the risk of electric shock.
direct contact in light of the IEC standards. In order to elevate the In this paper, the authors discuss possible alternatives for the
level of safety offered by Class II metal poles, the adoption of spe- protection against indirect contact in light of the aforementioned
cial circuitry and bonding connections to continuously monitor the
double insulation of metal poles is proposed. IEC standards. In addition, to increase the level of safety offered
by Class II metal poles in different grounding systems, the au-
Index Terms—Earth, exposed-conductive-parts, extra-
thors propose the adoption of special circuitry and bonding con-
neous-conductive-part, grounding electrode, light pole, neutral
residual current device, street lighting system, TI system, TN nections to monitor continuously the status of their double in-
system, TT system. sulation. Throughout the entire paper, the terms “ground” and
“earth” are used as synonyms.

I. INTRODUCTION
II. PROTECTION AGAINST INDIRECT CONTACT
TREET lighting systems are a typical case of distributed
S low-voltage loads located in large areas, and collectively
protected by the same device. In most cases, lighting systems of
AND TYPES OF GROUNDING SYSTEMS

In low-voltage (LV) systems, the protection against indirect


streets, parkways, and other public areas are under the respon- contact may be achieved by automatic disconnection of the
sibility of electrical utilities. Utilities maintain and operate the supply. This measure calls for the grounding of the neutral of
system and ensure safe illumination during the hours of dark- the LV supply, as well as of the enclosures of equipment, also
ness (approximately 4000 h/yr). referred to as exposed conductive parts (ECPs). This grounding
Luminaries may be mounted on steel or wooden poles, fed is preferably carried out through an earthing electrode common
with underground cables, originating from the nearest avail- to source and loads (i.e., the TN system), but can also be
able distribution line. Typically in the U.S., the single-phase, achieved through two independent grounding systems (i.e.,
three-wire, 120/240 V, or the three-phase, four-wire, 277/480 V the TT system). To further clarify the differences among the
are adopted; in Europe, the single-phase, two-wire, 230 V, or TT, TN, and IT grounding systems, explanatory figures are
the three-phase, four-wire, 400/230 V distribution systems are provided in the Appendix.
typical. The different types of grounding systems are codified by IEC
Technical standards of the International Electrotechnical 60364 through the XY-Z acronyms (Table I). This codification
Commission (IEC) specify the use of Class II equipment for the allows the introduction of the TI grounding system, which is not
street light systems as the protection against indirect contact. formally defined in IEC standards.
Class II components, such as the wiring systems, the light In the XY-Z acronym:
fixtures, etc., have a double or reinforced insulation. In normal • the X-letter describes the condition of the neutral point of
operating conditions and for properly maintained systems, the grounding of power-supply global positioning system
(GPS) with respect to ground:
Manuscript received October 21, 2010; revised February 16, 2011; accepted
March 15, 2011. Paper no. TPWRD-00806-2010 direct connection of source neutral to earth;
G. Parise and L. Martirano are with the Department of Electrical Engineering,
University “La Sapienza,” Rome 00184, Italy (e-mail: parise@ieee.org; arti- neutral is ungrounded, or grounded through an
rano@ieee.org).
M. Mitolo is with the Electrical Department of Chu and Gassman, New York, impedance.
NY 08846 USA (e-mail: mmitolo@chugassman.com). • The Y-letter describes the condition of the exposed con-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. ductive parts (ECPs) with respect to ground:
Digital Object Identifier 10.1109/TPWRD.2011.2131690 •
0885-8977/$26.00 © 2011 IEEE
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

2 IEEE TRANSACTIONS ON POWER DELIVERY

TABLE I MV/LV substation. In this case, the service entrance is supplied


GROUNDING SYSTEMS ACRONYMS DEFINED BY IEC. by the utility at medium-voltage. Consequently, in residential
or small commercial applications, powered by utility-owned
transformers, only the TT system can be implemented.
Where street lighting systems are in areas where it may not
be possible, or practical, to implement either the TT or the TN
system, the adoption of Class II components for all the elements
of the lighting system (e.g., poles, light fixtures, cables, splices,
terminal strips, etc.) is an alternative approach. Class II compo-
nents have double, or reinforced, insulation: protections against
direct contact (also referred to as basic protection) and against
indirect contact (also referred to as fault protection) are, respec-
tively, provided by the basic and the supplementary insulations.
Reference [1] defines as Class II, the metal poles whose hand-
hole cover on the lighting column is separated from wires by
insulating material (e.g., sleeves or tubes).
In this case, [1] does not require the intentional earthing of the
conductive parts of the lighting column; thus, protective conduc-
tors are not provided in the electrical distribution system.1

III. TT STREET LIGHTING SYSTEM


In low-voltage TT systems (generally used in Europe) the
Fig. 1. TN-S system: protective conductors (PE) are connected to the power- distribution line is carried out through four-wire (H-H-H-N)
supply ground electrode. or two-wire (H-N for single-phase loads) systems, generally at
400/230 V (or 380/220 V), and at 50 Hz.
At the service panel, a protective conductor (PE) is locally
connection of the ECPs to ground, independent earthed, and kept separate from the neutral wire. Downstream
of the GPS; the service panel, the local distribution system consists of a five-
connection of the ECPs to GPS; wire system (H-H-H-N-PE for three-phase loads) or a three-
wire system (H-N-PE for single-phase loads).
ECPs are not connected to GPS. For TT systems, all ECPs collectively protected by the same
• The Z-letter (if any) describes the arrangement of neutral feeder protective device (FPD) must be connected to a common
and protective conductors (PE): earth electrode [3]. However, if in addition to the FPD, local
protective devices (LPDs) are used for each pole or group of
neutral wire and PE are separated; poles, independent grounding systems may be allowed (Fig. 2).
neutral wire and PE are combined in a single
conductor (PEN). In the TT system, ground-fault currents are greatly limited by
the earth resistance of the earth electrodes; the fault loop also
Based on the previous text, the TI grounding system is charac- includes the earth resistance of the utility substation. Thus, a
terized by grounded power supplies and by ungrounded metal protective overcurrent device may not trip within the maximum
enclosures of equipment. permissible times [5], since the magnitude of the ground-fault
Low-voltage loads are usually supplied by radial distribu- current might be below the threshold of its long time pickup.
tion systems. A basic solution is the TN system, where all of Thus, in TT systems, residual current devices (RCD) must nec-
the simultaneously accessible ECPs must be connected to the essarily be employed. In the TT system of Fig. 2, protection
grounding of the power supply via protective conductors. The against indirect contact is achieved by using RCD at a level of:
TN-S is a practical solution when the LV loads are concentrated • FPD in case of a common earth electrode [Fig. 2(a)];
in the same area as the MV/LV substation (Fig. 1). • LPD in case of independent earth electrodes; in this case,
In TN-S systems, the three-phase distribution line consists of FPD may have a delayed instantaneous tripping time (no
five-wire (H-H-H-N-PE), whereas the single-phase distribution higher than 1 s) [Fig. 2(b)].
line consists of three-wire (H-N-PE). In both cases, the protec-
tive conductor and neutral wire are distinct conductors (Fig. 1).
Extraneous-conductive-parts (EXCPs) must also be bonded IV. TN-C-S STREET LIGHTING SYSTEM
to the main earthing terminal of the building, as close as possible In low-voltage TN-C-S systems (generally used in North
to their point of entry within it. EXCPs may include metallic America), the distribution line is carried out through a four-wire
parts of the building structure, metal pipe systems for gas, water, (H-H-H-PEN) three-phase, or three-wire (H-H-PEN), double
heating, and noninsulating floors and walls [8]. 1The absence of equipment grounding conductors in particular cases, such as
Note that in the IEC approach for LV power systems, the double-insulated appliances, is a concept also present in [2] (Art. 250.114 Ex),
use of the TN system is possible only if the user owns the adopted in the U.S.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

PARISE et al.: ELECTRICAL SAFETY OF STREET LIGHT SYSTEMS 3

Fig. 4. In TI systems, the neutral point is grounded and the poles (potential
ECPs) are Class II.

Fig. 2. (a) TT system with light poles collectively protected by the same FPD
and (b) independently protected by local protective devices LPD.

Fig. 5. Cast polyurethane resin (90 C) splice for Class II, multicore plastic
insulated cables.

guarantee double insulation characteristics (Class II), both


by construction, as shown in datasheets, and by installation
(adopting special requirements).
Fig. 3. TN-C-S systems: the PEN conductor acts as a grounded conductor and
as an equipment grounding conductor. It is, in fact, important that the installation of Class II equip-
ment (especially branch joints and connections) should not
compromise the protection prescribed in the specifications for
single phase. In these systems, the PEN conductor acts as a double insulated equipment.
grounded conductor and a PE (Fig. 3). For example, the installation of Class II, multicore, plastic
The system becomes a TN-S system downstream the user insulated cable splices, used to derive the branch circuit in the
panel, where a separate protective conductor PE originates. At- handhole at the pole, requires special materials and techniques
tention is drawn to the fact that in the TN-S portion of TN-C-S (Fig. 5).
systems, the PE must not pass through the RCD’s toroid, so that For the street light electric distribution systems, IEC stan-
fault currents will not circulate through it and possibly desensi- dards promote the TI system, which does not call for the RCDs;
tize it, invalidating its protection. this solution avoids nuisance tripping that could determine un-
safe conditions especially in areas at high vehicular traffic.
V. TI STREET LIGHTING SYSTEM INTEGRATED WITH A The disadvantage of this arrangement is that if the double
RESPONSIBLE MAINTENANCE insulation fails, the TI system degrades to a TT system; there-
In TI systems (generally used for street lighting system in fore, overcurrent protective devices may not clear the fault for
Italy), the electrical distribution line consists of a four-wire the reasons examined in Section III. Thus, in this case, mainte-
(H-H-H-N) three-phase, or two-wire (H-N) single-phase nance implies a higher responsibility for the owner of the street
system. The neutral point of the source is grounded, whereas all lighting system.
of the electrical components are Class II, and are ungrounded If, for instance, the double insulation of the luminaire termi-
(Fig. 4). In this case, the FPD may be an overcurrent protec- nals fails due to, for example, an incorrect lamp replacement
tive device. Each electrical component of the TI system must (Fig. 6), the surface of the metal pole may become permanently
guarantee the double insulation, not only by construction, energized, exposing people to the risk of electric shock, until a
but also by installation. Steel poles supported by concrete maintenance crew detects the failure.
plinths have an optimal mechanical resistance against natural Actual earth measurements carried out in TI systems show
events (e.g., high winds, thunderstorms, ice accumulation, etc.) that a 10 m steel pole, whose foundation plinth is embedded in
and accidental events (e.g., car impacts). Let us note that in the ground for 0.8 m (Fig. 7), offers relatively high values of
a TI system, each component, such as switchgears, cables, resistance-to-ground. If, for example the pole earth resistance
luminaries, terminations, joints (straights and 90 ), etc, must assumes a value of , in TI street lighting systems supplied
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

4 IEEE TRANSACTIONS ON POWER DELIVERY

Fig. 6. Luminaire terminations with faulty double insulation.

Fig. 8. Conceptual representation of the ground insulation test for single-phase


circuits supplying poles.

Fig. 7. Typical street light pole.

at 400/230 V, the earth fault current caused by the faulty double Fig. 9. Feeder within the panelboard is disconnected from the CB for the insu-
insulation will not exceed 11 A. lation-to-ground test.
The metal pole can assume almost the whole supply value of
230 V, which is permitted for no more than 0.2 s. The ground
current may be even lower, if we consider the limitation effect the line, with a minimum of 1 km, and N is the number of
caused by the arc impedance. Arc faults to ground, in fact, are luminaries.
more likely to occur than bolted faults in ac low-voltage sys- For example, for a system with an extension not exceeding 1
tems. km, which supplies 30 luminaries, the minimum value of the in-
Consequently, it would be advisable to implement a mainte- sulation resistance is about ; a leakage current of about 3.5
nance program to: mA at 230 V corresponds to this value of insulation resistance.
• periodically inspect the publicly exposed lighting system Although conceptually simple, the aforementioned procedure
to confirm the absence of damages to the structures; is rather complex to perform, because the personnel must tem-
• periodically test the insulation between live conductors and porarily drive an auxiliary ground rod, not always an easy task
earth, as per the conceptual diagram presented in Fig. 8. in urban areas, and disconnect the feeder within the panelboard
The insulation-to-ground of the system will pass the test if (Fig. 9).
upon the application of a voltage of 500 V for 60 s, the resistance Attention is drawn on the fact that [1] states that metal struc-
measured is greater than: tures (such as fences, grids, etc.), which are in the proximity
• , if the test is conducted with all the luminaries of the street lighting system, but do not form part of it, need
disconnected (very unpractical); not be connected to the earth terminal of the installation. This
• , if the test is arranged with all the lumi- requirement applies to any outdoor lighting installation, regard-
naries connected; where L is the length in kilometers of less of the type of grounding system adopted. Reference [1] does
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

PARISE et al.: ELECTRICAL SAFETY OF STREET LIGHT SYSTEMS 5

not clarify whther the aforementioned metal structures that are VII. PROPOSED SOLUTIONS
EXCPs constitute an exception and should be earthed.
The authors suggest two types of solutions, applicable in al-
ternative or combined, to improve the TI system:
1) an additional level of protection extended to all the com-
ponents of the street light system;
VI. PRACTICE IN THE U.S
2) a smart solution localized within the panelboard.

Reference [2], adopted in the U.S., prescribes that conduc- A. TI System With an Additional Level of Protection
tive enclosures of light poles be connected to the facility ground
system through an equipment ground conductor in the same Considering the basic benefits for safety of the double insula-
raceway as the line wires. However, not all light street systems tion, but also the difficulties in detecting its failure, the authors
are installed per [2]. suggest, as extra levels of protection (Fig. 10), the addition of
Outdoor lighting installations mounted by utilities are, in a residual current relay within the protective device and, one or
fact, in compliance with [9], which does not require protective both, of the following:
conductors to bond the conductive poles. In some systems, • employment of multiconductor cables with an integral pro-
the safety of steel, or aluminum, poles is exclusively entrusted tective conductor to reduce the risk of its accidental discon-
upon local ground rods connected to each pole, without any nection;
bonding connection to the source or to the other poles. • addition of a buried bare grounding wire to be connected
The resulting system is a TT, which may not necessarily have to each metal pole in TI systems.
its characteristic safety requirements, such as a very low earth The bare grounding wire will have a minimum cross-sectional
resistance for the single electrodes and/or the RCDs. Thus, low- area of and be buried at a minimum depth of 0.50 m
intensity ground faults might not be cleared at all, causing the below grade. This additional earth electrode will integrate the
permanent presence of stray voltages on publicly exposed en- natural electrode constituted by the plinth.
closures. In this arrangement, the protection against indirect contact is
This earthing arrangement is unsafe and, in fact, is not guaranteed by two levels:
permitted by [1], as mentioned in Section III. Details on the • a first level consisting of double insulated components;
safety reasons behind this prohibition have been discussed in • a second level consisting of the disconnection of the supply,
[5]. Modern systems use a three-wire, or four-wire distribution or the activation of an alarm, in the case of failure of the
line, which does include a ground wire. The ground conductor double insulation.
is bonded to the metal pole. The earth electrode system is
B. “Smartpanel” with an Insulation Monitoring Device
usually a ground rod, or a concrete-encased electrode obtained
by using the re-bars of the plinth of the pole, connected at the As explained in Section V, although conceptually simple, the
service point. maintenance in the TI system is rather complex, due to the prac-
The City of Los Angeles Street Lighting Guide, for example, tical difficulties setting up the insulation test circuit.
states that overcurrent devices (i.e., fuses or circuit breakers) To facilitate the testing procedure, and drastically reduce
without ground-fault protection shall protect all street lighting its costs, the authors propose the adoption of a “smartpanel”
systems. When circuit breakers are used, the neutral wire shall equipped with a special insulation monitoring device (IMD).
only be grounded at the service point, and an additional equip- The special IMD is composed of:
ment ground conductor shall be employed to bond together all 1) a permanent testing circuitry consisting of a double-insu-
steel components of the lighting system [7]. The aforementioned lated test switch and a ground test electrode permanently
arrangement constitutes a TN-S system. installed in an inspection well (Fig. 11).
As a further example of good practice, we can consider the re- The test switch has two positions: “power” and “test,” sep-
quirements of the Louisiana Highways Lighting Systems, which arated by an “open” status. The “power” position allows
prescribes that: “an equipment grounding conductor shall be in- the normal supply of the light fixtures. The “test” position
stalled with each new circuit and shall be connected to each new shorts together the live conductors, allowing the insulation
light pole and fixture.” test.
In New York City, the chronic problem of stray voltages ap- When the switch is in test position, the insulation tester
pearing on metal poles is being mitigated by installing noncon- (indicated as Mohm in Fig. 10) is connected to the live
ductive composite covers on utility service boxes, and intro- conductors and to the test electrode. Two connection ter-
ducing isolation transformers [5] within the poles. minals are available at the smartpanel to accept the insula-
These transformers allow the galvanic separation of the tion tester leads.
lighting circuit from the earth, thereby preventing the circula- 2) The insulation tester can be either enclosed in the panel
tion of currents, if the basic insulation of the circuit, or of other or external and portable. If the Mohm is enclosed in the
components within the pole, fails. panel, the insulation test can be performed on a daily basis
In addition, the utility has also developed a mobile detection without personnel involvement, thanks to a contactor that
vehicle (MDV) that can survey for stray voltages on metal poles automatically turns the test switch in the “test” position. If
while driving down the streets. MDVs are used to conduct an- the Mohm is portable, the insulation test is manual and has
nual surveys and prior to public events to enhance public safety. to be performed by maintenance personnel.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

6 IEEE TRANSACTIONS ON POWER DELIVERY

Fig. 10. The grounding electrode only operates upon failure of the double insulation (TT system).

TABLE II
COMPARISON AMONG THE DIFFERENT SMART SOLUTIONS

Note that the new generation of lighting smartpanels is al-


ready equipped with transmitter interfaces, so that the addi-
tional cost reduces to the test switch and the test electrode.
C. “Smartpanel” with Residual Current Monitoring Device
To further increase the public safety, the smartpanel could be
equipped with a residual current monitoring device (RCMD).
The RCMD consists in a residual current relay that can initiate
Fig. 11. Panelboard equipped with the test switch and accessible ground test a local alarm and send an automatic notification to the mainte-
electrode. nance center, without disconnecting the supply to the lighting
system. The RCMD should be protected against surges, and
have a residual threshold of not less than 500 mA, to prevent
3) A transmitter system (e.g., GSM, GPRS, or power-line nuisance trippings.
communication (PLC)), capable of sending the testing data Table II shows a comparison among the different proposed
to the maintenance center, allowing a continuous and cost- solutions by assuming the TI system as the reference.
effective maintenance activity.
The aforementioned solution adds extra cost to the utility, VIII. CONCLUSION
which is estimated in an additional expense not exceeding It has been substantiated that fault loops in streetlight sys-
50% of the panelboard cost. However, this extra expendi- tems depend on the grounding system employed. The strategy
ture would drastically reduce maintenance activities and for the protection against indirect contact must therefore be ac-
greatly increases public safety. cordingly studied.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

PARISE et al.: ELECTRICAL SAFETY OF STREET LIGHT SYSTEMS 7

Fig. 12. TT grounding system. Fig. 13. TN grounding system.

TT, TI, and TN systems have fault loops of a different nature,


the first two comprise the actual earth, which makes the pro-
tection against indirect contact by disconnection of the supply
based on overcurrent devices difficult.
The TI system is an efficient solution to protect people from
electric shocks and to preserve the continuity of the service, es-
pecially in areas at high pedestrian and/or vehicular circulation.
In fact, the probability that the basic and the supplementary in-
sulations are both punctured is very low, but not zero, if we con-
sider the hundreds of thousands of metal poles present in large
cities. However, forensic cases have been documented (Fig. 6),
proving that this event has occurred.
To reduce this risk, the authors propose testing circuitry to be
implemented within the lighting system panelboard. This cir-
cuitry, thanks to a test electrode, can check the leakage to ground
Fig. 14. IT grounding system.
of the double insulation and alert the maintenance personnel
well before the complete failure of the Class II pole. In addition,
these authors also propose the adoption of grounding electrodes
for Class II light pole systems, beneficial in the case of the un- REFERENCES
detected failure of the double insulation.
[1] 1996-04, 1st Ed., Electrical Installations of Buildings, Part 7. Require-
Studies to generalize the proposed solutions in the case of ments for Special Installations or Locations—Section714: External
concrete or wooden poles as well as in the case of light systems Lighting Installations, IEC 60364-7-714, 1996.
in high-resistivity soils will be carried out in the future. [2] ANSI/NFPA 70, National Electrical Code 2008.. Quincy, MA, Na-
tional Fire Protection Assoc.
[3] G. Parise, “A summary on the IEC protection against electric shock,”
IEEE Trans. Ind. Appl., vol. 34, no. 5, pp. 911–922, Sep./Oct. 1998.
[4] M. Mitolo, “Is it possible to calculate safety?,” IEEE Ind. Appl. Mag.,
vol. 15, no. 3, pp. 31–35, May/Jun. 2009.
APPENDIX [5] Low-Voltage Electrical Installations—Part 4-41: Protection
for Safety–Protection Against Electric Shock, 2005, Ed.5, IEC
60364-4-41, 2005.
In TT grounding systems, two independent earthing systems [6] M. Mitolo, “On outdoor lighting installations grounding systems,” in
Proc. IEEE Ind. Appl. Soc. 41st Annu. Meeting, Conf. Rec., Tampa, Fl,
are called for: one for the source and one for the equipment Oct. 2006, vol. 5, pp. 2224–2229.
(Fig. 12). [7] Bureau of Street Lighting City of Los Angeles, Design Standard and
In TN grounding systems, the earthing electrode is common Guidelines, May 2007.
[8] M. Mitolo, M. Tartaglia, and F. Freschi, “To bond or not to bond: That
to the source and the equipment (Fig. 13). is the question,” IEEE Trans. Ind. Appl., vol. 47, no. 2, pp. 989–995,
In IT grounding systems, the source is not earthed, or is Mar./Apr. 2011.
earthed through a high impedance; the equipment is grounded [9] Standard ANSI/IEEE C2-2007, National Safety Electrical Code,
C2-2007, 2008.
(Fig. 14). [10] M. Mitolo, Electrical Safety of Low-Voltage Systems. New York: Mc-
For further details, see [3] and [10, ch. 6, 7, and 9]. Graw-Hill, 2009.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

8 IEEE TRANSACTIONS ON POWER DELIVERY

Giuseppe Parise (M’82-SM’03–F’10) was born in Massimo Mitolo (SM’03) received the Ph.D. degree
Luzzi (Cosenza), Italy. He received the Electrical in electrical engineering from University of Naples
Engineering degree from the University of Rome, “Federico II, ” Naples, Itraly, in 1990.
Rome, Italy, in 1972. His field of research is in analysis and grounding
He has been with the Department of Electrical En- of power systems. He is currently the Assistant
gineering, University of Rome “La Sapienza” since Electrical Department Head at Chu & Gassman,
1973 and is currently a Full Professor of Electrical New York. He has authored many journal papers,
Power Systems. He has authored about 190 papers and the textbook Electrical Safety of Low-Voltage
and two patents. Since 1975, he has been a Designer Systems.
of Power Electrical Systems in Buildings Complexes, Dr. Mitolo is very active within the IEEE IAS In-
such as in Roma Sapienza University City and Engi- dustrial & Commercial Power Systems Department,
neering Faculty, Polyclinic Umberto I, Italian Parliament, Campus Biomedical where he currently is the Chair of the Power Systems Engineering (PSE) Com-
Research Center. mittee, the Chair of the Power Systems Analysis Subcommittee, and the Chair
Prof. Parise received three Prize Paper Awards from the IEEE/IAS Power of the Power Systems Grounding Subcommittee. He is also an Associate Editor
Systems Department. Since 1983, he has been a member of Superior Council of of the PSE and ES Scholarone Manuscript. He is also the recipient of the Lu-
Ministry of Public Works. He is active in IEEE\IAS, Chair of IA Italy Section cani Insigni Award in 2009, for merits achieved in the scientific field. He is a
Chapter, Member at Large of Executive Board 2007-2010, and is past President registered Professional Engineer in Italy.
of AEIT Rome’s Section. He is Chair of Electrical Power Systems Researchers
of Sapienza University. He has been a Registered Professional Engineer since
1975.

Luigi Martirano (S’98–M’02–SM’11) received the


M.S. and Ph.D. degrees in electrical engineering
from the University of Rome, Italy, in 1998 and
2002, respectively.
In 2000, he joined the Department of Electrical
Engineering, University of Rome “La Sapienza.”
Currently, he is an Assistant Professor of Building
Automation and Energy Management at the En-
gineering Faculty and of Lighting Systems at the
Architecture Faculty. He is the author or coauthor of
more than 60 papers and a co-inventor of one inter-
national patent. His research activities cover power systems design, planning,
safety, lightings, home and building automation, and energy management. He
is a senior member of the IEEE Industry Applications Society, of the Italian
Association of Electrical and Electronics Engineers (AEIT), and of the Italian
Electrical Commission (CEI) Technical Committees CT205 and SC311B. He
is a Registered Professional Engineer.

View publication stats

You might also like