Professional Documents
Culture Documents
net/publication/4078321
CITATIONS READS
10 1,374
3 authors:
Mansueto Rossi
Università degli Studi di Genova
81 PUBLICATIONS 919 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Federico Delfino on 04 September 2014.
5
20
15
Voltage [kV]
Voltage [kV]
10
2
5
1
0 0
0,0 0,5 1,0 1,5 2,0 0,0 0,5 1,0 1,5 2,0
Time (ms) Time (ms)
Fig. 3 – Voltage at the terminal of the ESS cable (contact line side) for the Fig. 6 – Voltage at the nearest ESS for the overvoltage applied at point A and
overvoltage applied at point A and arresters at the ESSs. arresters (earth resistance 1 Ω) at the ESSs.
12 10
10
8
6
6 Voltage [kV]
4
4
2
0
-2 0
0,0 0,5 1,0 1,5 2,0 0,0 0,5 1,0 1,5 2,0
Time (ms) Time (ms)
Fig. 4 – Voltage at the terminal of the parallel feeder cable (contact line side) Fig. 7 – Voltage at the nearest ESS for the overvoltage applied at point A and
for the overvoltage applied at point A and arresters at the ESSs. arresters (earth resistance 5 Ω) at the ESSs.
5 0,0
4
-0,5
3
Voltage [kV]
Voltage [kV]
-1,0
-1,5
1
0 -2,0
0,0 0,5 1,0 1,5 2,0 0,0 0,5 1,0 1,5 2,0
Time (ms) Time (ms)
Fig. 5 – Voltage at the nearest ESS for the overvoltage applied at point A and Fig. 8 – Voltage on the most stressed diode for the overvoltage applied at
arresters (earth resistance 0 Ω) at the ESSs. point A and arresters (earth resistance 0 Ω) at the ESSs.
-0,5 10
Voltage [kV]
Voltage [kV]
-1,0 5
-1,5
0
-2,0
-5
0,0 0,5 1,0 1,5 2,0
Time (ms) 0,0 0,5 1,0 1,5 2,0
Time (ms)
Fig. 9 – Voltage on the most stressed diode for the overvoltage applied at Fig. 11 – Voltage at the terminal of the ESS cable (contact line side) for the
point A and arresters (earth resistance 1 Ω) at the ESSs. overvoltage applied at point B and arresters at the ESSs.
20
0,0
-0,5 15
-1,0
10
Voltage [kV]
Voltage [kV]
-1,5
-2,0
0
-2,5
-3,0 -5
0,0 0,5 1,0 1,5 2,0 0,0 0,5 1,0 1,5 2,0
Time (ms) Time (ms)
Fig. 10 – Voltage on the most stressed diode for the overvoltage applied at Fig. 12 – Voltage at the terminal of the parallel feeder cable (contact line side)
point A and arresters (earth resistance 5 Ω) at the ESSs. for the overvoltage applied at point B and arresters at the ESSs.
are concerned, they are higher than the rated impulse voltage
UNI = 8 kV [4].
1
The voltages at the ESSs and on the diodes are limited by
the surge arresters to values slightly lower than the
corresponding ones of the case of voltage surge applied at 0
point A. Anyway; in both cases the presence of the arresters 0,0 0,5 1,0
Time (ms)
1,5 2,0
prevents the ESS voltage from reaching values that could Fig. 13 – Voltage at the ESSs for the overvoltage applied at point B and
result dangerous for its devices. arresters at the ESSs.
0,0 15
-0,5
10
Voltage [kV]
Voltage [kV]
-1,0
-1,5
-2,0 0
0,0 0,5 1,0 1,5 2,0 0,0 0,5 1,0 1,5 2,0
Time (ms) Time (ms)
Fig. 14 – Voltage on the most stressed diode for the overvoltage applied at Fig. 16 – Voltage at the terminal of the ESS cable (contact line side) for the
point B and arresters at the ESSs. overvoltage applied at point A and arresters (earth resistance 1 Ω) at the
interface OCS/cables.
3
Voltage [kV]
-1
0,0 0,5 1,0 1,5 2,0
Time (ms)
Fig. 17 – Voltage at the terminal of the parallel feeder cable (contact line side)
for the overvoltage applied at point A and arresters (earth resistance 1 Ω) at
the interface OCS/cables.
The results of this test are reported in Figs. 16, 17, 18 and 19
and are relevant to 1 Ω surge arresters earth resistance. These 8
As can be seen from Fig. 16, the voltage at the ESS cable
terminal (contact line side), although lower than that of Fig. 3, 4
Voltage [kV]
shown in Fig. 19. 5
0
0
-1
-5
0,0 0,5 1,0 1,5 2,0
Time (ms)
Voltage [kV]
-2
Fig. 21 – Voltage at the terminal of the parallel feeder cable (contact line side)
for the overvoltage applied at point B and arresters (earth resistance 1 Ω) at
the interface OCS/cables.
-3
-4
0,0 0,5 1,0 1,5 2,0
Time (ms) 6
Fig. 19 – Voltage on the most stressed diode for the overvoltage applied at
point A and arresters (earth resistance 1 Ω) at the interface OCS/cables.
gVoltage( [kV]g)
5 0,0
4 -0,5
3 -1,0
Voltage [kV]
Voltage [kV]
2 -1,5
1 -2,0
0 -2,5
-1 -3,0
0,0 0,5 1,0 1,5 2,0 0,0 0,5 1,0 1,5 2,0
Time (ms) Time (ms)
Fig. 20 – Voltage at the terminal of the ESS cable (contact line side) for the Fig. 23 – Voltage on the most stressed diode for the overvoltage applied at
overvoltage applied at point B and arresters (earth resistance 1 Ω) at the point B and arresters (earth resistance 1 Ω) at the interface OCS/cables.
interface OCS/cables.
6
As a general comment, one can conclude that this
configuration does not seem to be effective, since the presence
of the arresters at the interface between contact line and cables
could not be sufficient to limit the cable voltages. Moreover 4
Voltage [kV]
2
C. Configuration 3: surge arresters located both at the
interface between contact line and feeder cables and at the
DC busbars of each electrical substation
0
The location of the arresters is depicted in Fig. 24. In all these
cases the earth resistance of the OCS arresters is 5 Ω, (since it
is highly impractical to obtain a lower value) while the earth
resistance of the ESSs ones is assumed to be 1 Ω. -2
0,0 0,5 1,0 1,5 2,0
Time (ms)
Fig. 26 - Voltage at the terminal of the parallel feeder cable (contact line side)
for the overvoltage applied at point A and arresters located both at the
interface OCS/cables (earth resistance 5 Ω) and at the ESSs (earth resistance 1
Ω).
4
Voltage [kV]
1
Figs. 25 and 26 show the voltage at the terminal both of the
ESS cable and of the parallel feeder cable (contact line side),
0
respectively as a consequence of the application of the voltage 0,0 0,5 1,0 1,5 2,0
surge at point A. The benefits deriving from the connection of Time (ms)
the surge arresters to the ESS busbars are highlighted in Fig. Fig. 27 - Voltage at the nearest ESS for the overvoltage applied at point A and
arresters located both at the interface OCS/cables (earth resistance 5 Ω) and at
27 that shows the voltage at the nearest substation. the ESSs (earth resistance 1 Ω).
In order to investigate the dependence of the voltage peaks on
the earth resistance, the analysis has been repeated with OCS
arresters earth resistance of 1 Ω. In Table I the values of the TABLE I
VOLTAGE PEAKS ON THE DIFFERENT DEVICES WITH OCS ARRESTERS EARTH
peaks in both cases are compared, highlighting that there is a
RESISTANCE OF 1 AND 5 Ω AND VOLTAGE SURGE APPLIED AT POINT A.
not negligible difference of such peaks in the two cases.
20
15
Parallel feeder voltage peak (kV) 4.2 5.6
10
Nearest ESS voltage peak (kV) 4.8 5
2
The comparative study has pointed out that the solution
where the arresters are only at the ESSs is the best one, since
it represents a good compromise between a sufficiently safe
0
configuration and a cheap one.
Of course, the study has been carried out developing a tool
whose aim is not to describe in detail the field-to-line coupling
-2
0,0 0,5 1,0 1,5 2,0 due to a lightning event, but to give useful guidelines to a
Time (ms)
Fig. 28 - Voltage at the terminal of the ESS cable (contact line side) for the
designer with low computational costs.
overvoltage applied at point B and arresters located both at the interface
V. REFERENCES
OCS/cables (earth resistance 5 Ω) and at the ESSs (earth resistance 1 Ω).
15 [1] Light Rail Transit Association, UK Development Group, Fact Sheet N.
102, July 2000.
[2] R. Buckley, Tramways and Light Railways of Switzerland and Austria,
National Atlases from LRTA, London, 2000.
10 [3] EN 50124-1 (March 2001): Railway applications – Insulation
coordination. Part I: Basic requirements. Clearances and creepage
distances for all electrical and electronic equipment.
[4] EN 50124-2 (March 2001): Railway applications – Insulation
Voltage [kV]