You are on page 1of 39

SUPPLY, ERECT AND COMMISSIONING OF 275KV GIS, 132KV AIS, 2 X 240MVA

AUTOTRANSFORMER AND ANCILLARY EQUIPMENT COMPLETE WITH


ASSOCIATED CIVIL WORKS FOR PMU 275/132KV KANGKAR TEBRAU, JOHOR
Contract No: TNB 99/2015

METHOD STATEMENT ( NON OUTAGE REQUIRED):


Defect rectification at PMU 275/132kV kangkar tebrau

A. To replace faulty indication /pilot lamp H4 at panel


=D00+RBB1&RBB2
B. To retrieve actual setting from AVR both RTC1 and RTC2 panel

Main Contractor:

TENAGA SWITCHGEAR SDN BHD – TOSHIBA TRANSMISSION & DISTRIBUTION SYSTEMS ASIA SDN BHD JV
Lot 3, Jalan Teknologi 3/6, Taman Sains Selangor 1, Kota Damansara, 47810 Petaling Jaya,
Selangor Darul Ehsan
Tel: 03-6140 6520 Fax: 03-6140 6530

Prepared by Review by Review by Approved by

TNB TNB TNB


TSG – TTDA JV
Grid Development Grid Maintenance Grid Maintenance
South 1 Southern Southern
TABLE OF CONTENT

No. Description

1. Background information & Introduction


2. Scope of Work

3. Method of Statement (Details Step)

4. Safety work at site & HIRACD

5. List of Equipment / Machineries

6. List of Manpower & ntsp/cidb

7. Contingency Plan

8. Propose Work Program

9. List of Appendix
1. Company background information
COMPANY DETAILS TENAGA SWITCHGEAR SDN BHD – TOSHIBA
TRANSMISSION & DISTRIBUTION SYSTEMS ASIA SDN
BHD JV
Lot 3, Jalan Teknologi 3/6, Taman Sains Selangor 1,
Kota Damansara, 47810 Petaling Jaya
No. Tel : 03-6140 6520
No. Fax : 03-6140 6530
SITE ADDRESS PMU 275/132KV Kangkar Tebrau GIS, Johor

OVERVIEW OF PROJECT SUPPLY, ERECT AND COMMISSIONING OF 275KV


GIS, 132KV AIS,
2X240MVA AUTOTRANSFORMER AND ANCILLARY
EQUIPMENT COMPLETE WITH CIVIL WORKS
FOR PMU 275/132KV KANGKAR TEBRAU, JOHOR
Contract No: TNBT 99/2015
PROJECT TEAM (CLIENT & MAIN CONTRACTOR) TNB-GD South-I Project Director
Ir. Goh Yin Seng
TNB-GD South-I Project Engineer (Electrical)
Muhamad Safuan Bin Ishak
TNB-GD South-I Project Engineer (Civil)
Norasyikin Binti Nasarudin

TSG & TTDA-JV Project Director


Ir. Hj. Mazelan Bin Abdul Samad (TSG)
TSG & TTDA-JV Project Manager (Electrical)
Mohd Akramin Bin Ayob (TSG)
Lidya Ahmad (TTDA)
TSG & TTDA - JV Project Manager (Civil)
Saiful Azwan Bin Rasidi
TSG & TTDA-JV Project Engineer (Electrical)
Nizam & Kamil
TSG Supervisor:
Zahir
TSG CQP:
Zahir
INTRODUCTION

OBJECTIVE: To provide a guideline on safe working practice on completing the activity


on live switchyard and around control building in TNB substation. The
procedure is to establish safe, efficient and quick normalization of the
substation
SITE:
PMU 275/132KV Kangkar Tebrau, PMU PMJY 275KV, PMU SKDI 275KV. Johor
MANPOWER:
All workers should wear PPE at all times
TOOLS:
All tools should be in proper working conditions
MACHINARIES:
Minimum safe working clearance from any adjacent live point should be
maintained at 3.5m at all time during operations (for outdoor switchyard)

• PRELIMINARY:

• Before any works start, TNB Permit to Work (PTW) must be obtained for the bays involved.
TNB shall also have their own authorized personnel to supervise the works throughout the
jobs at site. Any necessary clearance from NLDC must be arranged through TNB internal
procedure and area of work should be barricade.

• No work shall be done without the presence of TNB site supervisor.

• Before climbing on any equipment he has to ensure that the bay is completely isolated. If
he has any doubts he has to get clarified from the competent engineer and also the TNB
site supervisor.

• The works specified in the scope of works has to complete as per the given schedule with
full safety compliance.

• CONSTRAINTS:

• Work duration shall be extended due to bad weather i.e heavy rain, thunderstorm, etc
• There must be sufficient work space and /or clearance as directed by Superintending
Officer, No work shall be allowed to continue if contractor fail to provide adequate safe
working space and/or clearance on existing LIVE switchyard area.
• No work shall be done without the personnel of TNB or Competent Engineer
• Work area shall be barricaded with plastic chain (yellow)
• Proper signage indication the working area shall be made visible
• All work will do in “LIVE CONDITION” so please make sure all tools used must be fully
insulated and insulation glove must be worn during the work
2. SCOPE OF WORK / JOB SCOPE

A. Defect rectification -To replace faulty indication /pilot lamp H4 at panel


=D00+RBB1&RBB2
B. To retrieve actual setting from AVR both RTC1 and RTC2 panel

3. METHOD OF STATEMENT.

No Work Description PMU/Location Step / procedure

1. Identify the faulty indication lamp location.


2. Test the lamp by push the test button lamp SLT,
Remove cable L27 from H4: X1, and tape properly
To replace the lamp PMU KTBR
with PVC tape.
indication-H4 as per 275/132kV
3. Replace with new lamp, Rewired cable L27 to H4:
1 TNB MDL Panel
X1, carefully without touching other cable/ terminal.
(=D00+RBB1&R
4. Test again -SLT for the confirmation healthy lamp
BB2)
indication.
5. Verification and Sign off the MDL with TNB site
6. Refer for appendix A1.
To retrieve actual
PMU KTBR
setting from AVR both 275/132kV 1. To refer the attached appendix A2. (detail MOS by
2 RTC1 and RTC2 panel Panel (=RTC1)& siemens)
(=RTC2)
4. SAFETY AT WORK SITE

The person in charge of a working party shall ensure that at all times the members of his party
thoroughly understand the work they have to do and the safety precautions required.

Safety Equipment
Safety equipment such as safety helmets, safety belts and harnesses, safety ropes must be
checked that it is in good condition before and after use

Objections
A person receiving an instruction regarding work on or the operation of High Voltage equipment
shall be report any objection he may have to carrying out instruction to the person issuing them

Dangerous Occurrences and Accidents


All dangerous occurrences and accidents shall be reported in accordance with TNB’s standing
instruction and statutory requirements

Safety Equipment
1. All apparatus, equipment and conductors shall be regarded as being LIVE until isolated and
proven DEAD; a DEAD apparatus is NOT SAFE until it is isolated and earthed

2. Earthed means connected to the general mass of earth in such manner as will ensure at all
time immediate discharge of electrical energy without danger, when applied to apparatus,
equipment, and conductors. All phase short circuited and efficiently connected to earth

3. Earthing bond for use at generating station and transmission substation shall have a cross
section of not less than 65sqmm

4. Earthing rod shall be insulated suitable for the system voltage which it is used

Access to High Voltage Apparatus / Zone


1. All High Voltage Apparatus shall be regarded as LIVE until it has been isolated, earthed and
made subject of a Permit to Work

2. Barricade (including rates on access ladders) cutting of access to enclosures, chambers,


cubicles or cell containing exposed High Voltage conductors shall be kept locked and shall not
be opened except by an Authorized Person (AP)

3. All spout shutters other than those made subject of a Permit to Work shall be locked shut

4. A High Voltage Zone under Permit to Work (PTW) shall be barricaded and all work by
contractors and their employees shall be confined within the zone and be in immediate
charge of a qualified person provided for under the Electricity Regulations 1994

5. Portable ladders (except of an approved typed) and tong objects are not allowed with the
High Voltage Zone. The use of such objects shall be under the direct supervision of the person in
charge of the work and when moved at ground level they shall be carried only in a horizontal
position as near to the ground as practicable

6. No person shall climb any structure in a High Voltage Zone unless the safe nature of the climb is
checked by a second person in the immediate vicinity. In every case one of the above two
person must be a competent engineer / person

7. No vehicle is allowed to move about, load or unload in a High Voltage Zone except as
approved by this person in charge

8. Cranes or other equipment shall be taken into or out of a substation via predetermined route
approved by the Authorized Person
General Precautions

Before carrying out any work on any part of High Voltage Apparatus / Zone made subject of a
Permit to Work it is good practice to verify that:-

A. The apparatus dead – check for physical breaks

B. All possible sources of supply are isolated and looked

C. All point of isolation earthed and Caution Notices Fixed

D. Zone on with work may be carried out is properly barricaded and Danger Notices are
attached on or an adjacent to live apparatus at the limits of the zone

E. Caution Notices is fixed on all switchgears or apparatus which had been dead and on
which work is to proceed

F. All circuit main earth and additional earth are properly installed

G. Necessary working clearances are maintained (Refer – example sketch of electrical


clearance)

Electrical Parameters and Clearances (Substation)

Standard Electrical Parameters and Clearance as per table below to be followed:

Nominal Systems Voltage K Vrms 275 132 33 11


(Phase to Phase)
Rated Voltage K Vrms 300 145 36 12
Power Frequency Withstand Voltage K Vrms 380 275 70 28
(1 minutes)
Lightning Impulse Withstand K Vpeak 1050 650 170 75
Switching Impulse Withstand K Vpeak 850 - - -
Minimum clearance between Live mm 2082 1270 381 203
metal and earth
Minimum clearance between Live mm 2515 1473 432 254
metal of different phase
Minimum safety clearance between mm 2440 2440 2440 2440
ground to nearest point not at earth
potential of an insulator
Minimum safety clearance between mm 4570 3500 2740 2590
ground or a working platform and
the nearest Live unscreened
conductor

Table: For 275KV, 132KV and 275/132KV Substation


HIRADC
Doc. No.: TTDA-HIRADC-ASTR-ELECT
Rev. No.: 1 (DATE: 10/10/20)
Page: 1 of 1, prepared by NIZAM, verified by LYDIA

HAZARD IDENTFICATION, RISK ASSESSMENT AND DETERMINING CONTROL FORM

Likelihood 1 2 3 4 5

Severity

5 5 10 15 20 25
4 4 8 12 16 20
3 3 6 9 12 15
2 2 4 6 8 10
1 1 2 3 4 5

JOB TITLE : replacement of the indication lamp and to retrieved AVR setting
works

Activities R/NR IDENTIFY Name ASSESSMENT CONTROL


Hazard Consequences Current Risk Ctrl f L/Hood Severity R/Level Type Futher PIC (DUE
of Action / DATE/STATUS)
Ct l C t l
rework due to Barricade work
wrong area and ensure
wrong panel and part. panel location is
Replacement
R location and Tripping operated. confirm with TNB 2 2 4 (L) NIL - TNB supervisor
led pilot lamp AP. Carried out
panel.
with TNB
supervision.

OEM to follow
tripping and
guideline with
Download Software crash software failed to TNB AP
R operate. System 4 1 4 (L) NIL - TNB supervisor
software supervision. OEM
Shutdown &
personal
failure.

likehood SEVERITY RISK = LIKELIHOOD X


SEVERITY
Numerous fatalities, 1-4 : LOW RISK
Most Likely (5) The most likely result of the hazard / event being Catastropic (5) irrecoverable property
realised damage and productivity
5 - 12 : MEDIUM RISK
Possible (4) Fatal (4)
Approximately one single
Has a good chance of occuring and is not unusual
Serious/Major (3) fatality and major property
Conceivable (3) (within 5 years) 15 - 25 : HIGH RISK
Minor (2) damage if hazards is
Remote (2) Might be Negligible (1) realized
occur at R = Routine NR = Non-Routine
Inconceivable (1) Non fatal injury, permanent disability
sometime in
future Disabling but not permanent injury
(within 5-10
years) Has Minor abrasions, bruises, cut, first aid
not been type injury
5. LIST OF EQUIPMENT / MACHINARIES

No. Equipment / Machinery remarks


1 Digital Multimeter Serial no: 35470272WS
Calibrated: yes
2 Laptop, OEM software and communication cable By Siemens

6. LIST OF MANPOWER

No. Name Position CIDB No. Expiry NTSP No. Expiry date
date
1 Lidya Ahmad Project W511B042012001 07/2025 TNB020083N 30.05.2022
manager
2 Muhammad engineer J91270120060001 28.12.2021 TNB000360N 25.07.2022
Nizam
3 Khairul Fatah engineer D81080420090023 23.10.2022 TNB034335N 30/05/2022
4 Ahmad Syazwan engineer T11280920030055 13.09.2021 TNB003413N 14/03/2022
5 Abu Bakar manager W21231120010020 12.06.2022 TNB001570N 30/05/2022
6 Mohd saiful tech 1870925KN1800246116 RENEW TNB034508N 25.07.2022
7 WAN SIEMENS tbc 28.07.2021 TNB002362896 14.10.2022
ZAINORHAZWAN SPECIALIST
7. CONTIGENCY PLAN

Immediate action will be taken if any unwanted situation happens as below:-

A. Action taken if any accidents happen during unloading equipment etc.


• Make sure the victim still conscious
• Victim unconscious immediately send to hospital
• TSG-TTDA JV supervisor above will report to TNB personnel at site.
• Situations become worse stop all work

B. Action taken when non tripping fault or hazard occurs during does any unloading equipment
• TSG-TTDA JV supervisor will investigated location of fault happen
• Asked all workers who at fault location
• Discuss the outcome with the TNB personnel at site
• Any conclusion TNB personnel at site will decide
8. Propose Work Program

Period
Description
9am 10am 11am 12am 1pm 2pm 3pm
Safety Briefing and PTW issuance by GM
Barricade the working area.

1. replace faulty indication /pilot lamp H4 at panel


=D00+RBB1&RBB2
2. retrieve actual setting from AVR both RTC1 and RTC2
panel by siemens

Housekeeping and PTW cancellation


9. List of Appendix

A1. Pilot lamp catalogue and manual


A2. Detail step procedure AVR setting retrieving by OEM Siemens
A3. Location faulty indication lamp H4 panel drawings
EP1140-0_YW Page 1 Tuesday, August 8, 2006 9:40 AM

Appendx A1. Pilot lamp catalogue and manual

ø22mm
YW Series Control Units
EP1140-0_YW Page 2 Tuesday, August 8, 2006 9:40 AM

Innovative Design Enables


Save
Space-Saving and Safety YW
seri

With Reliable Self-Cleaning Contacts Relia

Save A new contact block design reduces the


depth of pushbuttons, illuminated pushbut-
tons, and selector switches behind the
New Contact Blocks panel. The new contact blocks are only 10
YW series mm thick, so three contact blocks can mount
in one deck. The full-voltage adapter for illu-
minated pushbuttons is also only 10 mm
thick, so it can be mounted along with two
contact blocks on the same deck.

CB: Contact block


FA CB CB FA CB FA: Full-voltage adapter

10 10 10
CB

Reliable
30

15 15

30
Heavy-Duty Rugged Construction
Retained Locking Lever The YW series control units are designed to withstand
harsh operating conditions in factory environments. The
Lock Unlock rugged mechanical design provides reliability in critical

➂ ➁ switching applications.

Self-Cleaning Wiping-Action Contacts


with Scored Contact Surface Eme
The YW contact blocks feature a Scored Surface
wiping action on the movable contact
and scored contact surfaces for higher
contact reliability. The contacts can
switch a wide range of loads from 5
mA at 3V DC up to 10A at 120V AC.
The innovative plastic locking lever is
retained and eliminates the need for a sepa-
rate lever lock.
Wiping Action
After touching the stationary contact, the movable
To lock the locking lever with an operator contact starts to wipe and cleans the contact surfaces.
installed, simply turn the locking lever to the
right as viewed from the back. The latch Spring
inside the locking lever firmly retains the
locking lever and withstands vibrations.
To unlock the locking lever, pull out the latch Movable
Contact
inside the locking lever and turn the locking
lever to the left, then the operator can be Stationary
removed from the contact blocks. Contact

(1) Normal State (2) Wiping (3) Fully Depressed


EP1140-0_YW Page 3 Tuesday, August 8, 2006 9:40 AM

Save Safety
YW
series

ontacts Reliable

replace item,

Safety
Integrated Finger-safe
Terminal Cover

le
uction
Degree of Protection: IP20
The new YW contact blocks, full-voltage
adapter, and pilot light terminals feature
integrated finger-safe terminal covers to
prevent electrical shocks and ensure a
to withstand high degree of safety during wiring and
ronments. The maintenance.
bility in critical

n Contacts
e Emergency Stop Switches
Scored Surface
Satisfy International Standards
• Safety Lock Mechanism
If any part of the body inadvertently touches the
pushbutton, the contacts will not open until the operator
mechanism is locked. This feature prevents unintentional
operation of the emergency switch (compliant to EN418).
movable • Direct Opening Function
tact surfaces. Even if the contacts become welded together, an
operating force applied to the pushbutton forces the NC
contacts to open and ensures a break in the circuit
(compliant to IEC 60947-5-1, Annex K).
• Safe Pushbutton Design
The mushroom pushbutton is designed to ensure that an
object cannot become trapped between the mushroom
button and the panel, disabling the button operation. In
addition, the pushbutton is designed to prevent any
(3) Fully Depressed tampering from the front of the panel.
EP1140-0_YW Page 4 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units


Space-saving, 10-mm-thick contact blocks
Removable operator
• Compact and light-weight
• IP20 finger-safe screw terminals (IEC 60529)
• Separate contact block makes installation
and removal easy.
• Pilot lights feature a large lens for a wide
viewing angle.
• Matted surfaces on the buttons, lenses, and
bezels reduce reflection of ambient light.
• UL, c-UL listed, EN compliant, and CCC
approved (except for emergency stop
switches).

• UL508, CSA C22.2 No. 14,


EN 60947-1, EN 60947-5-1
GB 14048. 5

Contact Ratings (Contact Block) Specifications


Rated Insulation Voltage 600V Operating temperature: –20 to +55°C (no freezing)
Operating humidity: 45 to 85% RH (no condensa-
Rated Thermal Current 10A Operating
tion)
Operating Voltage 24V 120V 240V 380V Conditions
Storage temperature: –45 to +80°C
Resistive Load (AC-12) 10A 10A 6A 2A Storage humidity: 95% RH maximum
AC
50/60 Hz Inductive Load (AC-15) 10A 6A 3A 1.9A Degree of From panel front: IP65 (IEC 60529)
Protection Terminal: IP20 (IEC 60529)
Resistive Load (DC-12) 8A 2.2A 1.1A –
DC Insulation
Inductive Load (DC-13) 4A 1.1A 0.55A – 100 MΩ
Resistance
Contact block: 2,500V, 1 minute
Dielectric Strength
LED Lamp Ratings Pilot light: 2,000V, 1 minute
<Emergency stop switch>
Type No. Rated Voltage Rated Current Color Code
Operating extremes / Damage limits:
LSED-6➁ 6V AC/DC
10 mA (A, R, Y) 10 to 500Hz, amplitude 0.35 mm, acceleration 50 m/s2
7 mA (G, PW, S) Vibration
<Pushbutton, pilot light, illuminated pushbutton, and
A (amber) Resistance selector switch>
14 mA (A, R, Y) G (green)
LSED-1➁ 12V AC/DC Operating extremes: 5 to 55 Hz, amplitude 0.5 mm
13 mA (G, PW, S) PW (pure white)
Damage limits: 30 Hz, amplitude 1.5 mm
14 mA (A, R,Y) R (red)
LSED-2➁ 24V AC/DC <Emergency stop switch>
13 mA (G, PW, S) S (blue)
Y (yellow) Operating extremes: 150 m/s2 (15G)
LSED-H➁ 110V AC/DC 5.5 mA
Damage limits: 1,000 m/s2 (100G)
LSED-M3➁ 230/240V AC/DC 2.7 mA Shock
<Pushbutton, pilot light, illuminated pushbutton, and
Resistance
selector switch>
Note: Specify a color code in place of ➁ in the Type No.
Operating extremes: 100 m/s2 (10G)
Yellow LED lamps are used for white illumination of pilot lights and illu-
Damage limits: 1,000 m/s2 (100G)
minated pushbuttons.
<Emergency stop switch>
250,000 (single contact block)
Incandescent Lamp Ratings <Pushbutton and illuminated pushbutton>
Mechanical Life Momentary: 5,000,000 (single contact block)
Type No. Rated Voltage Ratings
(minimum 1,000,000 (double contact block)
LS-T6 6V AC/DC 6.3V 1W operations) Maintained: 250,000 (single contact block)
LS-T8 12V AC/DC 18V 1W 100,000 (double contact block)
<Selector switch> 250,000 (single contact block)
LS-T3 24V AC/DC 30V 1W 100,000 (double contact block)
<Emergency stop switch>
Electrical Life 100,000 (single contact block)
Mounting Hole Layout (minimum <Pushbutton and selector switch>
R0.8 max. operations) 100,000 (single contact block)
50,000 (double contact block)
3.2 +0.2
0 The 3.2-mm-wide key recess
ø22
.3 +0.4 is necessary when the anti-
0
24.1 +0.4

rotation ring is used.


0

Unit A (mm) B (mm)


Emergency stop switch 50 min. 50 min.
A B Pushbutton 50 min. 30 min.
Selector switch
Mushroom pushbutton 50 min. 40 min.
Pilot light 30 min.∗ 30 min.
∗ Keep a minimum spacing of 50 mm when using a lamp of over 1W.

4
EP1140-0_YW Page 5 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22

Emergency Stop Switches

Style Operation Contact Type No. Button Color Code


Mushroom ø40mm 1NC YW1B-V4E01R

2NC YW1B-V4E02R

3NC YW1B-V4E03R
Pushlock
Red only
Pull/Turn Reset
1NO-1NC YW1B-V4E11R

1NO-2NC YW1B-V4E12R

2NO-1NC YW1B-V4E21R

Dimensions
Panel Thickness 0.8 to 6
Note: When pressed, the button is locked in
the depressed position, and is reset
10 10 10

when either pulled or turned clockwise.

M3.5 Terminal Screw


Contact Block Locking Ring Gasket
28.6

41.4

0
ø4
45.8 32.5 30

Illuminated Emergency Stop Switches

Illumination ➂ Operating Lens Color


Style Operation Contacts Type No.
Type Voltage Code Code
Mushroom ø40mm 1NC YW1L-V4E01Q0R
Without 0 (without lamp)
2NC YW1L-V4E02Q0R
Lamp 250V AC/DC max.
1NO-1NC YW1L-V4E11Q0R
1NC YW1L-V4E01Q➂R 2 (6V AC/DC)
3 (12V AC/DC)
Pushlock
LED 2NC YW1L-V4E02Q➂R 4 (24V AC/DC) Red only
Pull/Turn Reset
H (110V AC/DC)
1NO-1NC YW1L-V4E11Q➂R M3 (230/240V AC/DC)
1NC YW1L-V4E01Q➂R 5 (6V AC/DC)
Incandescent 2NC YW1L-V4E02Q➂R 6 (12V AC/DC)
1NO-1NC YW1L-V4E11Q➂R 7 (24V AC/DC)
Note: Specify an operating voltage code in place of ➂ in the Type No.

Dimensions
M3.5 Terminal Screw Panel Thickness 0.8 to 6 Note: When pressed, the button is locked in
Full-Voltage Adapter
the depressed position, and is reset
when either pulled or turned clockwise.
10 10
10

M3.5 Terminal Screw


Contact Block Locking Ring Gasket
28.6

41.4

0
ø4
45.8 32.5 30 All dimensions in mm.

5
EP1140-0_YW Page 6 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units

Pushbuttons

Style Operation Contact Type No. ➀ Button Color Code


Flush 1NO YW1B-M1E10➀

1NC YW1B-M1E01➀

2NO YW1B-M1E20➀

2NC YW1B-M1E02➀

Momentary 1NO-1NC YW1B-M1E11➀

3NO YW1B-M1E30➀ B (black)


G (green)
3NC YW1B-M1E03➀ R (red)
2NO-1NC YW1B-M1E21➀ S (blue)
W (white)
1NO-2NC YW1B-M1E12➀ Y (yellow)

1NO YW1B-A1E10➀

1NC YW1B-A1E01➀

Maintained 2NO YW1B-A1E20➀

2NC YW1B-A1E02➀

1NO-1NC YW1B-A1E11➀
Extended 1NO YW1B-M2E10➀

1NC YW1B-M2E01➀

Momentary 2NO YW1B-M2E20➀

2NC YW1B-M2E02➀ B (black)


G (green)
1NO-1NC YW1B-M2E11➀ R (red)
1NO YW1B-A2E10➀ S (blue)
W (white)
1NC YW1B-A2E01➀ Y (yellow)

Maintained 2NO YW1B-A2E20➀

2NC YW1B-A2E02➀

1NO-1NC YW1B-A2E11➀
Mushroom ø40mm 1NO YW1B-M4E10➀

1NC YW1B-M4E01➀

Momentary 2NO YW1B-M4E20➀

2NC YW1B-M4E02➀ B (black)


G (green)
1NO-1NC YW1B-M4E11➀ R (red)
1NO YW1B-A4E10➀ S (blue)
W (white)
1NC YW1B-A4E01➀ Y (yellow)

Maintained 2NO YW1B-A4E20➀

2NC YW1B-A4E02➀

1NO-1NC YW1B-A4E11➀

Note: Specify a button color code in place of ➀ in the Type No.

6
EP1140-0_YW Page 7 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22


Dimensions (Pushbuttons)
Panel Thickness: 0.8 to 6
Gasket
10
10

0.5
M3.5 Terminal Screw
Contact Block Lock

Locking Ring
• Flush
(Button Diameter)

28.6
ø23.6

41.4
9
ø2

45.8 11 30

• Extended
(Button Diameter)

28.6
ø23.6

41.4

9
ø2
11
45.8 19 30

• Mushroom
(Button Diameter)

28.6

41.4
ø40

11
45.8 20.5 30

All dimensions in mm.

7
EP1140-0_YW Page 8 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units

Pilot Lights

Style Illumination Type Operating Voltage Type No. ➁ Lens Color Code
Flush A (amber), C (clear),
Full Voltage Without Lamp 250V AC/DC max. YW1P-1EQ0➁ G (green), R (red), S (blue),
W (white), Y (yellow)
6V AC/DC YW1P-1EQ2➁
12V AC/DC YW1P-1EQ3➁ A (amber), G (green),
PW (pure white), R (red),
LED 24V AC/DC YW1P-1EQ4➁
S (blue), W (white), Y (yellow)
110V AC/DC YW1P-1EQH➁ Built-in LED lamp: LSED-➂➁

230/240V AC/DC YW1P-1EQM3➁

6V AC/DC YW1P-1EQ5➁ A (amber), C (clear),


G (green), R (red), S (blue),
Incandescent 12V AC/DC YW1P-1EQ6➁ W (white), Y (yellow)
24V AC/DC YW1P-1EQ7➁ Built-in incandescent lamp: LS-T➂

Flush 100/110V AC YW1P-1EH2➁


Transformer Type
A (amber), G (green),
200/220V AC YW1P-1EM2➁ PW (pure white), R (red),
LED S (blue), W (white), Y (yellow)
115/120V AC YW1P-1EH22➁
Built-in LED lamp: LSED-6➁
230/240V AC YW1P-1EM42➁

100/110V AC YW1P-1EH5➁
A (amber), C (clear),
200/220V AC YW1P-1EM5➁ G (green), R (red), S (blue),
Incandescent W (white), Y (yellow)
115/120V AC YW1P-1EH25➁
Built-in incandescent lamp: LS-T6
230/240V AC YW1P-1EM45➁
Flush Marking Type A (amber), G (green), R (red),
Without Lamp 250V AC/DC max. YW1P-1BEQ0➁
Full Voltage S (blue), W (white), Y (yellow)
6V AC/DC YW1P-1BEQ2➁
12V AC/DC YW1P-1BEQ3➁ A (amber), G (green),
PW (pure white), R (red),
LED 24V AC/DC YW1P-1BEQ4➁ S (blue), W (white), Y (yellow)
Built-in LED lamp:
110V AC/DC YW1P-1BEQH➁ LSED-➂➁
230/240V AC/DC YW1P-1BEQM3➁

6V AC/DC YW1P-1BEQ5➁
A (amber), G (green), R (red),
Incandescent 12V AC/DC YW1P-1BEQ6➁ S (blue), W (white), Y (yellow)
Built-in incandescent lamp: LS-T➂
24V AC/DC YW1P-1BEQ7➁
Flush Marking Type 100/110V AC YW1P-1BEH2➁
Transformer Type A (amber), G (green),
200/220V AC YW1P-1BEM2➁ PW (pure white), R (red),
LED S (blue), W (white), Y (yellow)
115/120V AC YW1P-1BEH22➁ Built-in LED lamp:
LSED-6➁
230/240V AC YW1P-1BEM42➁

100/110V AC YW1P-1BEH5➁

200/220V AC YW1P-1BEM5➁ A (amber), G (green), R (red),


Incandescent S (blue), W (white), Y (yellow)
115/120V AC YW1P-1BEH25➁ Built-in incandescent lamp: LS-T6
230/240V AC YW1P-1BEM45➁

Note: Specify a lens color code in place of ➁ in the Type No.


Clear lenses are used for PW (pure white) illumination of pilot lights.

8
EP1140-0_YW Page 9 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22

Style Illumination Type Operating Voltage Type No. ➁ Lens Color Code
Extended A (amber), C (clear),
Full Voltage Without Lamp 250V AC/DC max. YW1P-2TEQ0➁ G (green), R (red), S (blue),
W (white), Y (yellow)
6V AC/DC YW1P-2TEQ2➁
12V AC/DC YW1P-2TEQ3➁ A (amber), G (green),
PW (pure white), R (red),
LED 24V AC/DC YW1P-2TEQ4➁
S (blue), W (white), Y (yellow)
110V AC/DC YW1P-2TEQH➁ Built-in LED lamp: LSED-➂➁

230/240V AC/DC YW1P-2TEQM3➁

6V AC/DC YW1P-2TEQ5➁ A (amber), C (clear),


G (green), R (red), S (blue),
Incandescent 12V AC/DC YW1P-2TEQ6➁ W (white), Y (yellow)
24V AC/DC YW1P-2TEQ7➁ Built-in incandescent lamp: LS-T➂

Extended 100/110V AC YW1P-2TEH2➁


Transformer Type
A (amber), G (green),
200/220V AC YW1P-2TEM2➁ PW (pure white), R (red),
LED S (blue), W (white), Y (yellow)
115/120V AC YW1P-2TEH22➁
Built-in LED lamp: LSED-6➁
230/240V AC YW1P-2TEM42➁

100/110V AC YW1P-2TEH5➁
A (amber), C (clear),
200/220V AC YW1P-2TEM5➁ G (green), R (red), S (blue),
Incandescent W (white), Y (yellow)
115/120V AC YW1P-2TEH25➁
Built-in incandescent lamp: LS-T6
230/240V AC YW1P-2TEM45➁
Dome A (amber), C (clear),
Full Voltage Without Lamp 250V AC/DC max. YW1P-2EQ0➁ G (green), R (red), S (blue),
W (white), Y (yellow)
6V AC/DC YW1P-2EQ2➁
12V AC/DC YW1P-2EQ3➁ A (amber), G (green),
PW (pure white), R (red),
LED 24V AC/DC YW1P-2EQ4➁
S (blue), W (white), Y (yellow)
110V AC/DC YW1P-2EQH➁ Built-in LED lamp: LSED-➂➁

230/240V AC/DC YW1P-2EQM3➁


lamp to replaced
6V AC/DC YW1P-2EQ5➁ A (amber), C (clear),
G (green), R (red), S (blue),
Incandescent 12V AC/DC YW1P-2EQ6➁ W (white), Y (yellow)
24V AC/DC YW1P-2EQ7➁ Built-in incandescent lamp: LS-T➂

Dome 100/110V AC YW1P-2EH2➁


Transformer Type
A (amber), G (green),
200/220V AC YW1P-2EM2➁ PW (pure white), R (red),
LED S (blue), W (white), Y (yellow)
115/120V AC YW1P-2EH22➁
Built-in LED lamp: LSED-6➁
230/240V AC YW1P-2EM42➁

100/110V AC YW1P-2EH5➁
A (amber), C (clear),
200/220V AC YW1P-2EM5➁ G (green), R (red), S (blue),
Incandescent W (white), Y (yellow)
115/120V AC YW1P-2EH25➁
Built-in incandescent lamp: LS-T6
230/240V AC YW1P-2EM45➁

Note: Specify a lens color code in place of ➁ in the Type No.


Clear lenses are used for PW (pure white) illumination of pilot lights.

9
EP1140-0_YW Page 10 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units


Dimensions (Pilot Lights)
• Flush • Flush Marking Type
Full Voltage Full Voltage
Panel Thickness 0.8 to 6 Panel Thickness 0.8 to 6

M3.5 Terminal Screw Gasket Gasket


M3.5 Terminal Screw
Locking Ring Locking Ring

8
9.

9.
ø2

ø2
24

24
46.2 9.5 29.6 46.2 10 29.6

Transformer Type Transformer Type


Panel Thickness 0.8 to 6 Panel Thickness 0.8 to 6

Gasket Gasket
M3.5 Terminal Screw M3.5 Terminal Screw
Locking Ring Locking Ring
8

8
9.

9.
ø2

ø2
24

24
63.3 9.5 29.6 63.3 10 29.6

• Extended • Dome
Full Voltage Panel Thickness 0.8 to 6 Full Voltage Panel Thickness 0.8 to 6

Gasket Gasket
M3.5 Terminal Screw M3.5 Terminal Screw
Locking Ring Locking Ring
8

8
9.

9.
ø2

ø2
24

24

46.2 15.5 29.6 46.2 15.5 29.6

Transformer Type Transformer Type


Panel Thickness 0.8 to 6 Panel Thickness 0.8 to 6

Gasket Gasket
M3.5 Terminal Screw M3.5 Terminal Screw
Locking Ring Locking Ring
8
8

9.
9.

ø2
ø2

24
24

63.3 15.5 29.6 63.3 15.5 29.6

All dimensions in mm.

10
EP1140-0_YW Page 11 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22

Illuminated Pushbuttons

Illumination ➂ Operating
Style Operation Contacts Type No. ➁ Lens Color Code
Type Voltage Code
Extended 1NO YW1L-M2E10Q0➁
1NC YW1L-M2E01Q0➁
Momentary 2NO YW1L-M2E20Q0➁
A (amber)
2NC YW1L-M2E02Q0➁
G (green)
1NO-1NC YW1L-M2E11Q0➁ 0 (without lamp) R (red)
Without Lamp
1NO YW1L-A2E10Q0➁ 250V AC/DC max. S (blue)
W (white)
1NC YW1L-A2E01Q0➁
Y (yellow)
Maintained 2NO YW1L-A2E20Q0➁
2NC YW1L-A2E02Q0➁
1NO-1NC YW1L-A2E11Q0➁
1NO YW1L-M2E10Q➂➁
1NC YW1L-M2E01Q➂➁
A (amber)
Momentary 2NO YW1L-M2E20Q➂➁ G (green)
2NC YW1L-M2E02Q➂➁ 2 (6V AC/DC) PW (pure white)
3 (12V AC/DC) R (red)
1NO-1NC YW1L-M2E11Q➂➁
LED 4 (24V AC/DC) S (blue)
1NO YW1L-A2E10Q➂➁ H (110V AC/DC) W (white)
1NC YW1L-A2E01Q➂➁ M3 (230/240V AC/DC) Y (yellow)
Maintained 2NO YW1L-A2E20Q➂➁ Built-in LED lamp:
LSED-➂➁
2NC YW1L-A2E02Q➂➁
1NO-1NC YW1L-A2E11Q➂➁
1NO YW1L-M2E10Q➂➁
1NC YW1L-M2E01Q➂➁
Momentary 2NO YW1L-M2E20Q➂➁ A (amber)
G (green)
2NC YW1L-M2E02Q➂➁ R (red)
1NO-1NC YW1L-M2E11Q➂➁ 5 (6V AC/DC) S (blue)
Incandescent 6 (12V AC/DC) W (white)
1NO YW1L-A2E10Q➂➁ 7 (24V AC/DC) Y (yellow)
1NC YW1L-A2E01Q➂➁
Built-in incandescent lamp:
Maintained 2NO YW1L-A2E20Q➂➁ LS-T➂
2NC YW1L-A2E02Q➂➁
1NO-1NC YW1L-A2E11Q➂➁
Extended with 1NO YW1L-MF2E10Q0➁
Full Shroud 1NC YW1L-MF2E01Q0➁
Momentary 2NO YW1L-MF2E20Q0➁
A (amber)
2NC YW1L-MF2E02Q0➁
G (green)
1NO-1NC YW1L-MF2E11Q0➁ 0 (without lamp) R (red)
Without Lamp
1NO YW1L-AF2E10Q0➁ 250V AC/DC max. S (blue)
W (white)
1NC YW1L-AF2E01Q0➁
Y (yellow)
Maintained 2NO YW1L-AF2E20Q0➁
2NC YW1L-AF2E02Q0➁
1NO-1NC YW1L-AF2E11Q0➁
1NO YW1L-MF2E10Q➂➁
1NC YW1L-MF2E01Q➂➁
A (amber)
Momentary 2NO YW1L-MF2E20Q➂➁ G (green)
2NC YW1L-MF2E02Q➂➁ 2 (6V AC/DC) PW (pure white)
3 (12V AC/DC) R (red)
1NO-1NC YW1L-MF2E11Q➂➁
LED 4 (24V AC/DC) S (blue)
1NO YW1L-AF2E10Q➂➁ H (110V AC/DC) W (white)
1NC YW1L-AF2E01Q➂➁ M3 (230/240V AC/DC) Y (yellow)
Maintained 2NO YW1L-AF2E20Q➂➁ Built-in LED lamp:
LSED-➂➁
2NC YW1L-AF2E02Q➂➁
1NO-1NC YW1L-AF2E11Q➂➁
1NO YW1L-MF2E10Q➂➁
1NC YW1L-MF2E01Q➂➁
Momentary 2NO YW1L-MF2E20Q➂➁ A (amber)
G (green)
2NC YW1L-MF2E02Q➂➁ R (red)
1NO-1NC YW1L-MF2E11Q➂➁ 5 (6V AC/DC) S (blue)
Incandescent 6 (12V AC/DC) W (white)
1NO YW1L-AF2E10Q➂➁ 7 (24V AC/DC) Y (yellow)
1NC YW1L-AF2E01Q➂➁
Built-in incandescent lamp:
Maintained 2NO YW1L-AF2E20Q➂➁ LS-T➂
2NC YW1L-AF2E02Q➂➁
1NO-1NC YW1L-AF2E11Q➂➁
Note: Specify a lens color code in place of ➁ in the Type No.
Specify an operating voltage code in place of ➂ in the Type No.

11
EP1140-0_YW Page 12 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units

Illumination ➂ Operating
Style Operation Contacts Type No. ➁ Lens Color Code
Type Voltage Code
Mushroom ø40mm 1NO YW1L-M4E10Q0➁
1NC YW1L-M4E01Q0➁
Momentary 2NO YW1L-M4E20Q0➁
A (amber)
2NC YW1L-M4E02Q0➁
G (green)
1NO-1NC YW1L-M4E11Q0➁ 0 (without lamp) R (red)
Without Lamp
1NO YW1L-A4E10Q0➁ 250V AC/DC max. S (blue)
W (white)
1NC YW1L-A4E01Q0➁
Y (yellow)
Maintained 2NO YW1L-A4E20Q0➁
2NC YW1L-A4E02Q0➁
1NO-1NC YW1L-A4E11Q0➁
1NO YW1L-M4E10Q➂➁
1NC YW1L-M4E01Q➂➁
A (amber)
Momentary 2NO YW1L-M4E20Q➂➁ G (green)
2NC YW1L-M4E02Q➂➁ 2 (6V AC/DC) PW (pure white)
3 (12V AC/DC) R (red)
1NO-1NC YW1L-M4E11Q➂➁
LED 4 (24V AC/DC) S (blue)
1NO YW1L-A4E10Q➂➁ H (110V AC/DC) W (white)
1NC YW1L-A4E01Q➂➁ M3 (230/240V AC/DC) Y (yellow)
Maintained 2NO YW1L-A4E20Q➂➁ Built-in LED lamp:
LSED-➂➁
2NC YW1L-A4E02Q➂➁
1NO-1NC YW1L-A4E11Q➂➁
1NO YW1L-M4E10Q➂➁
1NC YW1L-M4E01Q➂➁
Momentary 2NO YW1L-M4E20Q➂➁ A (amber)
2NC YW1L-M4E02Q➂➁ G (green)
5 (6V AC/DC) R (red)
1NO-1NC YW1L-M4E11Q➂➁
Incandescent 6 (12V AC/DC) S (blue)
1NO YW1L-A4E10Q➂➁ 7 (24V AC/DC) W (white)
1NC YW1L-A4E01Q➂➁ Built-in incandescent lamp:
Maintained 2NO YW1L-A4E20Q➂➁ LS-T➂
2NC YW1L-A4E02Q➂➁
1NO-1NC YW1L-A4E11Q➂➁
Note: Specify a lens color code in place of ➁ in the Type No.
Specify an operating voltage code in place of ➂ in the Type No.

Dimensions (Illuminated Pushbuttons)


Panel Thickness: 0.8 to 6
M3.5 Terminal Screw
Full-voltage Adapter Gasket
10 10 10

0.5
M3.5 Terminal Screw
Contact Block
• Extended • Extended with Full Shroud
28.6
(Button Diameter)

28.6
ø23.6

41.4

41.4

9
ø2 8.2
ø2
11 30 45.8 19 30
45.8 19

• Mushroom
(Button Diameter)

28.6

41.4
ø40

11
45.8 20.5 30 All dimensions in mm.

12
EP1140-0_YW Page 13 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22

Selector Switches

Knob Type

Style

No. of Contact Contact Block Operator Position Spring Return


Configuration Mounting Position
Maintained — —
Positions L R – from Right
1 NO
1NO
2 YW1S-2E10 YW1S-21E10 — —
(10)
3
1
1NC
2 YW1S-2E01 YW1S-21E01 — —
(01)
3 NC
1 NO
2NO
2 YW1S-2E20 YW1S-21E20 — —
(20)
3 NO
1 NC
2NC
2 YW1S-2E02 YW1S-21E02 — —
90° (02)
3 NC
2-Position
1 NO
1NO-1NC
L R 2 YW1S-2E11 YW1S-21E11 — —
(11)
3 NC
1 NO
3NO
2 NO YW1S-2E30 YW1S-21E30 — —
(30)
3 NO
1 NC
3NC
2 NC YW1S-2E03 YW1S-21E03 — —
(03)
3 NC
1 NO
2NO-1NC
2 NO YW1S-2E21 YW1S-21E21 — —
(21)
3 NC
1 NO
1NO-2NC
2 NC YW1S-2E12 YW1S-21E12 — —
(12)
3 NC
No. of Contact Contact Block Operator Position Spring Return Spring Return Spring Return
Maintained
Positions Configuration Mounting Position L C R from Right from Left Two-Way
1 NO
2NO
2 YW1S-3E20 YW1S-31E20 YW1S-32E20 YW1S-33E20
(20)
3 NO
1
2NO
2 NO YW1S-3E20N1 YW1S-31E20N1 YW1S-32E20N1 YW1S-33E20N1
(20N1)
3 NO
1 NC
2NC
2 YW1S-3E02 YW1S-31E02 YW1S-32E02 YW1S-33E02
(02)
3 NC
1
2NC
2 NC YW1S-3E02N1 YW1S-31E02N1 YW1S-32E02N1 YW1S-33E02N1
(02N1)
3 NC
1 NO
1NO-1NC
2 YW1S-3E11 YW1S-31E11 YW1S-32E11 YW1S-33E11
(11)
3 NC
1 NC
1NO-1NC
2 YW1S-3E11N1 YW1S-31E11N1 YW1S-32E11N1 YW1S-33E11N1
45° (11N1)
3 NO
3-Position
1 NO
1NO-1NC
C 2 NC YW1S-3E11N2 YW1S-31E11N2 YW1S-32E11N2 YW1S-33E11N2
L R (11N2)
3
1
1NO-1NC
2 NC YW1S-3E11N3 YW1S-31E11N3 YW1S-32E11N3 YW1S-33E11N3
(11N3)
3 NO
1
1NO-1NC
2 NO YW1S-3E11N4 YW1S-31E11N4 YW1S-32E11N4 YW1S-33E11N4
(11N4)
3 NC
1 NO
3NO
2 NO YW1S-3E30 YW1S-31E30 YW1S-32E30 YW1S-33E30
(30)
3 NO
1 NC
3NC
2 NC YW1S-3E03 YW1S-31E03 YW1S-32E03 YW1S-33E03
(03)
3 NC
1 NO
2NO-1NC
2 NC YW1S-3E21 YW1S-31E21 YW1S-32E21 YW1S-33E21
(21)
3 NO
1 NC
1NO-2NC
2 NO YW1S-3E12 YW1S-31E12 YW1S-32E12 YW1S-33E12
(12)
3 NC

13
EP1140-0_YW Page 14 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units


Contact Block Mounting Position Dimensions (Selector Switch)
Contact Block Mounting Position Panel Thickness: 0.8 to 6
2 3 Gasket
1

10
10
0.5
C M3.5 Terminal Screw
L R Contact Block 45°
Locking Ring 45°
LOCK
Operator Position

28.6

41.4
3-Position
9
ø2
ø2
11 Kn 7.6
45.8 24 30 Di ob
am
ete
r

90°

2-Position

All dimensions in mm.

Accessories

Package
Name & Shape Type No. Description & Dimensions (mm)
Quantity
Locking Ring Wrench Metallic tool used to tighten the
110
plastic locking ring when installing 8
ø2
the YW series control unit on a
MW9Z-T1 panel. 1

Lamp Holder Tool Made of rubber.


Used for replacing lamps.
ø14

OR-55 1
ø11.6

59

Rubber Mounting Hole Plug Used for plugging unused mounting holes in the panel. ø29
Color: Black
OB-31PN05 5
3.5

ø25
3.5

Metallic Mounting Hole Plug Used for plugging unused mounting holes in the ø25.8
panel.
3

LW9Z-BM Weight: Approx. 18g 1


12

Locking Ring

Anti-Rotation Ring Prevents rotation of switches in panel. 1.5 TOP


Mainly used with selector switches when no 9
ø2
nameplate is used.
HW9Z-RLPN10 ø22 10
With waterproof gasket (IP65).
Made of plastic (black).
Applicable panel thickness: 1.2 to 4.5 mm

14
EP1140-0_YW Page 15 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22


Package
Name & Shape Type No. Description & Dimensions (mm)
Quantity
Padlock Cover Plastic hinged cover to protect pushbuttons, 82.5
illuminated pushbuttons, or selector switches. Panel Thickness 0.8-3.2
Degree of protection: IP65.
Applicable panel thickness: 0.8 to 3.2 mm

R6
6.5

93
HW9Z-KL1 1

30
70
24
0
ø5

ø2
2
.2
Waterproof Gasket
29.5 Thickness 0.5
Pad Lock Hole ø8
30

LED Lamp Specify a color code in place of ➁ in the Type No.


LSED-6➁ 6V AC/DC
Base BA9S/14 A (amber), G (green), PW (pure white), R (red),
S (blue), Y (yellow)
LSED-1➁ 12V AC/DC Applicable units:
ø10.6

• LED illuminated pilot lights


LSED-2➁ 24V AC/DC • LED illuminated pushbuttons
For the rated current, see page 4. 1
LED Lamp Note: Yellow LED lamps are used for white illumination
Base BA9S/14 LSED-H➁ 110V AC/DC of pilot lights and illuminated pushbuttons.
ø10

LSED-M3➁ 230/240V AC/DC


25.3

Incandescent Lamp One pack contains 100 incandescent lamps.


LS-T6P 6.3V, 1W
Base BA9S/13

LS-T8P 18V, 1W 100


ø11 ±1

23 ±1 LS-T3P 30V, 1W

Single Contact Block


YW-E10P Contact: 1NO
5
22.3

10
M3.5 Terminal Screw
YW-E01P Contact: 1NC 41.4

Double Contact Block


YW-EW20P Contact: 2NO
5

M3.5 Terminal Screw


42.3

YW-EW11P Contact: 1NO-1NC 10

41.4

YW-EW01P Contact: 2NC


Note: Double contact blocks cannot be used on emer-
gency stop switches.

15
EP1140-0_YW Page 16 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units


Buttons, Lenses, and Marking Plates
➀➁ Package
Name Style Type No. Dimensions (mm)
Color Code Quantity
Button 6
3.
(for pushbuttons) ø2
Extended YW9Z-B12➀PN10
B (black)
G (green) 9.3
R (red) 0
ø4
10
S (blue)
W (white)

ø23.6
Mushroom Y (yellow)
YW9Z-B14➀PN10
ø40mm

6
10.8

Lens A (amber)
8
(for pilot lights) C (clear) 9.
ø2
G (green)
Flush YW9Z-PL11➁PN10 R (red) 10
S (blue)
W (white) 8.5
Y (yellow)
A (amber) 8
9.
C (clear) ø2
Flush G (green)
YW9Z-PL11B➁PN10 10
Marking R (red)
S (blue)
Y (yellow) 9

8
9.
ø2

Extended YW9Z-PL12T➁PN10 A (amber) 10


C (clear)
G (green) 14.5
R (red)
S (blue) 8
9.
ø2
W (white)
Dome YW9Z-PL12➁PN10 Y (yellow) 10

14.5

Lens 6
3.
(for illuminated pushbuttons) ø2
Extended YW9Z-L12➁PN10
A (amber)
C (clear) 9.3
G (green) 0
ø4
10
R (red)
S (blue)
ø23.6

Mushroom Y (yellow)
YW9Z-L14➁PN10
ø40mm

6
10.8

Marking Plate
7
2.
ø2

(for pilot lights)


ø21.8

— YW9Z-PP12PN10 — 10

21 2
4.4

Marking Plate
2
7.

(for illuminated pushbuttons)


ø1

ø16

— YW9Z-P12PN10 — 10

15.2 1.4
5

16
EP1140-0_YW Page 17 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22


Nameplate
Ordering Package
Description Legend Material Type No. Dimensions (mm)
Type No. Quantity

ERGENCY 0
EM ø6
Blank HWAV-0 HWAV-0 1

Plastic (yellow)
HWAV ø2
2
1.5 mm thick
STOP

1.6 0.9
EMERGENCY STOP HWAV-27 HWAV-27 1
• Legend “Emergency Stop”
is indicated outside a ø44mm circle.

EMO Switch Guards


Type No. & Appearance Dimensions (mm) Type No. & Appearance Dimensions (mm)
HW9Z-KG1 HW9Z-KG3
64 38 35
ø2

25
2

47 22
ø2
2

ø66

ø74
52
ø66.8

ø80
32

42
EMO Switch Guard EMO Switch Guard
SEMI S2 compliant (Note 1) SEMI S2 compliant
HW9Z-KG2 HW9Z-KG4
35
36.5 25
ø2
2.
2

ø2
2

ø75

ø90
67
ø76.1

ø90

50
EMO Switch Guard EMO Switch Guard
SEMI S2 compliant (Note 1) SEMI S2 compliant
SEMATECH compliant (Note 2) SEMATECH compliant (Note 2)
Material: Polyamide (PA6) • Degree of protection IP65 applies to the combination of an emergency stop
Color: Yellow, Munsell 2.5Y 8/10 equivalent switch and an EMO switch guard.
Degree of protection: IP65

Separate DIN Rail Mounting Type Transformer


• Dimensions (mm)

Secondary Terminal Primary Terminal


Screws M3.5 Screws M3.5
22
30

2-ø3.5 40
. Mounting Holes 48
Primary Voltage
Type No. Applicable Lamp Rating
(50/60 Hz)
52
110V AC TWR516 One full voltage type illuminated
115V AC TWR5116 unit containing LED lamp LSED-6
120V AC TWR5126 (6V AC/DC) or incandescent lamp
LS-T6 (6.3V)
220V AC TWR526
41
40

230V AC TWR5236
240V AC TWR5246
380V AC TWR5386
440V AC TWR546
480V AC TWR5486 Note: Finger-safe terminal cover is supplied with the transformer.

17
EP1140-0_YW Page 18 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units

Safety Precautions
• Turn off the power to the YW series control units before starting in- ing lamps.
stallation, removal, wiring, maintenance, and inspection of the • For wiring, use wires of a proper size to meet the voltage and cur-
products. Failure to turn power off may cause electrical shocks or rent requirements. Tighten the M3.5 terminal screws to a tighten-
fire hazard. ing torque of 1.0 to 1.3 N·m. Failure to tighten the terminal screws
• To avoid burning your hand, use the lamp holder tool when replac- may cause overheating and fire.

Instructions
Panel Mounting 1. To remove the full voltage unit, squeeze the full voltage unit from
both sides to disengage the latch as shown, and pull it out. Like
• Remove the contact block from the operator (for pilot lights, re- the transformer unit, the full voltage unit can also be pulled out by
move the transformer or full voltage unit from the pilot light). Re- inserting a flat screwdriver into the latch hole as shown.
move the locking ring from the operator. Insert the operator into the
panel cut-out from the front, tighten the locking ring from the back, 2. To reinstall, place the TOP markings on the operator and the latch
then install the contact block to the operator. on the full voltage unit in the same direction, and insert the oper-
ator into the full voltage unit.
• Removing and Installing the Contact Block
• Notes for Panel Mounting

1. Use the optional locking ring wrench (MW9Z-T1) to mount the op-

erator onto a panel. Tightening torque must not exceed 2.0 N · m.
Do not use pliers. Excessive tightening will damage the locking
ring.

2. For the contact blocks and transformers housing LED and incan-
descent lamps, make sure not to press the lamps too hard, other-
wise the lamp socket may be impaired.

Insertion Order of Lens and Marking Plate


➀ Pull up the locking lever. ➂ Pull out the contact block.
➁ Turn the lever to the left. • Illuminated Pushbutton • Pilot Light
1. To remove the operator from the contact block, pull up the locking Extended Flush
lever and turn it to the left. Then the operator can be pulled out. Extended
Dome
2. To reinstall, place the TOP marking on the operator and the idec
marking on the contact block mounting adapter in the same direc-
tion, and insert the operator into the contact block mounting Lens
Marking Plate
adapter. Then turn the locking lever to the right.
Lens
Flush Marking

With Full Shroud

Marking Plate
Marking Plate
Lens
Lens

Full Shroud
• Removing and Installing the Transformer Unit
1. Insert a flat screwdriver (5 mm wide at maximum) into the latch
hole on the transformer unit as shown in the photo below, and dis- Mushroom
engage the latch. Then pull out the operator.
2. To reinstall, place the TOP marking on the operator and the latch
in the same direction, and push the operator into the transformer
unit.
Marking Plate

Lens

Marking
For YW series pilot lights and illuminated pushbuttons, legends and
➁ symbols can be engraved on the built-in marking plates, or printed
mylar film can be inserted under the lens for labeling purposes.
Mylar film is not supplied with the control units and must be sup-
• Removing the Full Voltage Unit plied by the end user.

18
EP1140-0_YW Page 19 Tuesday, August 8, 2006 9:40 AM

YW Series Control Units ø22


• Built-in Marking Plate and Marking Film Size
Make sure to remove the lamp and contact blocks before removing
Unit Pilot Light Illuminated Pushbutton the full voltage adapter.
0
1.
ø2 5.2 Lamp
Built-in Marking Plate

ø1


Engraving Area Engraving Area

Full Voltage Adapter

1.2
1.0

Engraving depth: 0.5 mm maximum Contact Block


Marking plate material: White acrylic

Applicable Marking Film

-0.2
ø22.7 -0.2

0
0

ø17.2

➁ ➁

0
20.8 -0.2
0
15.0 -0.2 Tightening Torque for Terminal Screws
Tighten terminal screws to a torque between 1.0 and 1.3 N·m.
0.1-mm-thick × 2 sheets or 0.2-mm-thick × 1 sheet
Film material: Mylar (recommended) Anti-rotation Ring and Mounting Panel
Note: Marking film is not supplied with the pilot light or illu- Turn the TOP marking on the operator and the ▲ mark on the anti-
minated pushbutton. rotation ring to the recess on the mounting panel.
• Replacement (LED and incandescent lamps) Projections (▲ mark)

Lamps can be replaced using the lamp holder tool (OR-55) from the
front of the panel, or by removing the contact block from the opera-
tor unit.
• Removing the Lamp from the Front of the Panel
To remove, gently insert the lamp holder tool onto the lamp head.
Then push slightly, and turn the lamp holder tool to the left.
Anti-rotation Ring Locking Ring

Panel Thickness 1.2 to 4.5 mm

Mounting Panel Thickness


The mounting panel must be 0.8 to 6.0 mm in thickness. When
optional accessories are added, the applicable panel thickness
changes as shown below.
Padlock Cover
HW9Z-KL1P
• Installing the Lamp from the Front of the Panel
1. To install, insert the lamp head into the lamp holder tool, and hold
the lamp as shown in the figure below.

Lamp Lamp Removal Tool

Panel Thickness Panel Thickness


2. Place the pins on the lamp base to the grooves in the lamp socket. 0.8 to 6 mm 0.8 to 3.2 mm
Insert the lamp and turn it to the right.

Contact Bounce
When the button is reset by pulling or turning, the NC main contacts
will bounce. When pressing the button, the NO monitor contacts will
bounce.
When designing a control circuit, take the contact bounce time into
consideration (reference value: 20 ms).
Projection
Pilot Light Illuminated Pushbutton
Nameplate
When anti-rotation is not required, remove
Removing Contact Blocks the projection from the nameplate using
pliers.
and Full Voltage Adapter Nameplate
Insert a flat screwdriver between the Handling
latch and contact block mounting
Do not expose the switch to excessive
adapter, and disengage the latch.
shock and vibration, otherwise the switch
may be deformed or damaged, causing
malfunction or operation failure.

19
EP1140-0_YW Page 20 Tuesday, August 8, 2006 9:40 AM

ø22 YW Series Control Units

Instructions
LED Illumination [Protection Example 1] For AC circuit
LED lamps consist of semiconductors. If the applied voltage
exceeds the rated voltage, LED elements deteriorate due to over- LED with
heat, resulting in significant decrease in luminance, hue change, or transformer

failure of lighting. Also, if extraneous noise, transient voltage, or


C C
transient current is applied to the circuit, similar effects will be
LED with Relay Ry
caused. When using LED lamps, observe the following instructions. transformer LED R coil or
LED
R
solenoid
• Rated Voltage
(Reference values) R: 120Ω
The LED illuminated units are rated at 6V, 12V, 24V, 110V, or 230/ C: 0.1 µF
240V AC/DC, and can be used within ±10% the rated voltage of
either AC or DC, except the 230/240V AC/DC types can be used on
250V AC/DC maximum. [Protection Example 2] For DC circuit
• DC Power +

1. Switching power supply


Regulated voltage from switching power supply is best suited.
Make sure to use within the rated voltage of the LED lamp.
2. Rechargeable battery Relay Ry LED Diode
Note that the battery voltage may exceed the rated voltage of the coil or
solenoid
LED lamp while the battery is being charged and immediately af- –
ter the charging is complete. Be sure to use the LED lamp on a
voltage of ±10% the rated voltage, except the 230/240V AC/DC
types on 250V AC/DC maximum. • Countermeasures against Dim Lighting
3. Full-wave rectification 1. Leakage currents through the transistors or a contact protection
Since the LED lamp is AC/DC compatible, a diode bridge for rec- circuit may cause the LED lamp to illuminate dimly even when the
tification is not necessary. If the LED lamp is used on a full-wave output is off.
rectification current through a diode bridge, the rectifier diodes will 2. When the LED lamp is illuminated by a transistor output, take the
reduce the voltage, resulting in lower luminance. following measure.
4. Single-phase half-wave rectification
[Circuit Example]
This is not suitable for the power source of LED lamps. Use con-
stant-voltage DC power. Connect shunt resistor R in parallel with the LED lamp.
• Noise
LED elements deteriorate due to extraneous noise, resulting in sig-
nificant decrease in luminance, hue change, or failure of lighting.
R LED
When such effects are anticipated, take a protection measure
shown below, such as RC elements or a surge absorber.
Io

Io: Leakage current when the output is off


R: Shunt resistor

Ordering Information
• When ordering, specify the Type No. and quantity. • Replacement contact blocks are supplied in a package containing
10 pieces.

Specifications and other descriptions in this catalog are subject to change without notice.
7-31, Nishi-Miyahara 1-Chome, Yodogawa-ku, Osaka 532-8550, Japan
Tel: +81-6-6398-2571, Fax: +81-6-6392-9731
E-mail: products@idec.co.jp

IDEC CORPORATION (USA) IDEC ELEKTROTECHNIK GmbH IDEC IZUMI (H.K.) CO., LTD.
1175 Elko Drive, Sunnyvale, CA 94089-2209, USA Wendenstrasse 331, 20537 Hamburg, Germany Unit 1505-07, DCH Commercial Centre No. 25,
Tel: +1-408-747-0550 / (800) 262-IDEC (4332)
T Tel: +49-40-25 30 54 - 0, Fax: +49-40-25 30 54 - 24 Westlands Road, Quarry Bay, Hong Kong
Fax: +1-408-744-9055 / (800) 635-6246 E-mail: service@idec.de Tel: +852-2803-8989, Fax: +852-2565-0171
E-mail: opencontact@idec.com IDEC (SHANGHAI) CORPORATION E-mail: info@hk.idec.com
IDEC CANADA LIMITED Room 608-609, 6F, Gangtai Plaza, No. 700, IDEC TAIWAN CORPORATION
Unit 22-151, Brunel Road, Mississauga, Ontario, Yan'an East Road, Shanghai 200001, P.R.C. 8F-1, No. 79, Hsin Tai Wu Road, Sec. 1,
L4Z 1X3, Canada Tel: +86-21-5353-1000, Fax: +86-21-5353-1263 Hsi-Chih, Taipei County, Taiwan
Tel: +1-905-890-8561, Toll Free: (888) 317-4332 E-mail: idec@cn.idec.com Tel: +886-2-2698-3929, Fax: +886-2-2698-3931
Fax: +1-905-890-8562 IDEC (SHANGHAI) CORPORATION E-mail: service@idectwn.com.tw
E-mail: sales@ca.idec.com Beijing Office IDEC IZUMI ASIA PTE. LTD.
IDEC AUSTRALIA PTY. LTD. Unit 1002, No. 10 Kuntai Building, Zhaowai Dajie, No. 31, Tannery Lane #05-01, Dragon Land
2/3 Macro Court, Rowville, Victoria 3178, Australia Zhao Yang District, Beijing, 100020, P.R.C. Building, Singapore 347788
Tel: +61-3-9763-3244, Toll Free: 1800-68-4332 Tel: +86-10-6599-5541, Fax: +86-10-6599-5540 Tel: +65-6746-1155, Fax: +65-6844-5995
Fax: +61-3-9763-3255 E-mail: info@sg.idec.com
IDEC (SHENZHEN) CORPORATION
E-mail: sales@au.idec.com Unit AB-3B2, Tian Xiang Building, Tian’an Cyber Park,
IDEC ELECTRONICS LIMITED Fu Tian District, Shenzhen, Guang Dong 518040, P.R.C.
Unit 2, Beechwood, Chineham Business Park, Tel: +86-755-8356-2977, Fax: +86-755-8356-2944
Basingstoke, Hampshire RG24 8WA, UK
Tel: +44-1256-321000, Fax: +44-1256-327755
www.idec.com E-mail: sales@uk.idec.com

Cat. No. EP1140-0 AUGUST 2006 13.7DNP PRINTED IN JAPAN


APPENDIX A2. Detail step procedure AVR setting retrieving by OEM Siemens
WORK PROCEDURE

RETRIEVED SETTING FROM AVR

1. Open Reydisp Evolution software.


2. Open setting menu.

3. Click Get Setting.

4. Read one group of settings from the device into a Settings Editor Window
The user will be prompted to enter the group required.

PREPARED BY: WAN ZAINOORHAZWAN BIN CHECK BY: SUKHDEV SINGH


HAMID
WORK PROCEDURE

5. Save Settings.
6. Click file > save

7. A dialog box is displayed for the user to choose a directory to save the files.
The current path is shown at the top of the box. Underneath is a control to
select the target disk drive, then a list of the directories available on that
drive. Double click on a name in the list to enter a sub-directory. If
necessary you can create a directory by typing a name into the control in
the Create Directory area and pressing Create.

PREPARED BY: WAN ZAINOORHAZWAN BIN CHECK BY: SUKHDEV SINGH


HAMID
WORK PROCEDURE

8. Click ‘Save’

9. The Setting will saved in the folder as type .RSF2

PREPARED BY: WAN ZAINOORHAZWAN BIN CHECK BY: SUKHDEV SINGH


HAMID
APPENDIX A3. Location faulty indication lamp H4 panel drawings
1 2 3 4 5 6 7 8

800

A 275kV MAIN/RESERVE ZONE FRONT VIEW & PART LIST A


HIGH IMPEDANCE BUSBAR
PROTECTION PANEL NO.1 ITEM DESIGNATION DESCRIPTION
-F52/1 MINIATURE CIRCUIT BREAKER - AC SUPPLY (HEATER & LIGHTING)
-F52/2 MINIATURE CIRCUIT BREAKER - AC SUPPLY (SOCKET)
-F72/1 MINIATURE CIRCUIT BREAKER - PROTECTION DC SUPPLY
-F72/2 MINIATURE CIRCUIT BREAKER - INDICATION DC SUPPLY
-H1 INDICATING LAMP FOR HEATER
-SH HEATER ON/OFF SWITCH
-XPS POWER SOCKET
-X87BBHI/M1

B B
-F87BBHI/M1 -F96BBHI/M1 -X87BBHI/M1 TEST TERMINAL BLOCK
-F87BBHI/M1 MAIN 1 ZONE HIGH IMPEDANCE DIFFERENTIAL RELAY
-F96BBHI/M1 MAIN 1 ZONE BBP CT SUPERVISION RELAY
-X87BBHI/M2 TEST TERMINAL BLOCK
-F87BBHI/M2 MAIN 2 ZONE HIGH IMPEDANCE DIFFERENTIAL RELAY
-X87BBHI/M2

-F87BBHI/M2 -F96BBHI/M2 -F96BBHI/M2 MAIN 2 ZONE BBP CT SUPERVISION RELAY


-X87BBHI/R TEST TERMINAL BLOCK
-F87BBHI/R RESERVE ZONE HIGH IMPEDANCE DIFFERENTIAL RELAY
C -F96BBHI/R RESERVE ZONE BBP CT SUPERVISION RELAY C
-H2 MAIN 1 ZONE BBP IN SERVICE INDICATION
2275
-X87BBHI/R

-H3 MAIN 1 ZONE BBP OUT OF SERVICE INDICATION


-F87BBHI/R -F96BBHI/R
-S87M1 MAIN 1 ZONE BBP IN/OUT SELECTOR SWITCH (PADLOCKABLE)
-H4 MAIN 2 ZONE BBP IN SERVICE INDICATION
-H5 MAIN 2 ZONE BBP OUT OF SERVICE INDICATION
-H2 -H3 -H4 -H5 -H6 -H7 -SLT
to replace
-S87M2 MAIN 2 ZONE BBP IN/OUT SELECTOR SWITCH (PADLOCKABLE)
-H6 RESERVE ZONE BBP IN SERVICE INDICATION
-H7 RESERVE ZONE BBP OUT OF SERVICE INDICATION
D -S87M1 -S87M2 -S87R D
-S87R RESERVE ZONE BBP IN/OUT SELECTOR SWITCH (PADLOCKABLE)
-SLT LAMP TEST PUSH BUTTON
1
-K96DCS/1 1 DC SUPPLY SUPERVISION FLAG RELAY PROTECTION DC SUPPLY
-K96DCS/2 DC SUPPLY SUPERVISION FLAG RELAY INDICATION DC SUPPLY
- TERMINAL BLOCK (SPRING LOADED CLAMP TYPE)
PANEL DIMENSION 800(W) x 800(D) x 2275(H) mm
-F72/2
-F52/2

-F72/1
-F52/1

-H1
-XPS
E -SH E

=D00+RBB1
75
275-BBH/RP

F CLIENT: CONTRACTOR: TENAGA SWITCHGEAR SDN. BHD.- TITLE: = D00 + RBB1 / A11 F
DATE 17.11.15 TENAGA TOSHIBA TRANSMISSION & 275kV SCHEMATIC DRAWING
DRAWN MAR NASIONAL BERHAD (200866-W) DISTRIBUTION SYSTEM ASIA SDN. BHD. JV 275kVHIGH IMPEDANCE BUSBAR PROTECTION
SUPPLIER: DRAWING NO.: REV.: THIS SHEET: 13
AS-BUILT 11.03.20 MAR/FAUZI/EHSAN/ABU CHECKED FAUZI/EHSAN CONTRACT NO.: TNB 99/2015 TOSHIBA TRANSMISSION & PANEL NO.1 FRONT VIEW & PART LIST
REV. DATE DRN/CHK/REVIEWED REVIEWED ABU TENDER NO.: TNBT 808814 DISTRIBUTION SYSTEM ASIA SDN. BHD. SUBSTATION: PMU KANGKAR TEBRAU 275/132kV GIS TTDA KTRU 808814 275 S 11-BBHI AS-BUILT NEXT SHEET: 14
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

MAIN 1 ZONE MAIN 1 ZONE MAIN 2 ZONE MAIN 2 ZONE RESERVE ZONE RESERVE ZONE
LAMP TEST IN SERVICE OUT SERVICE IN SERVICE OUT SERVICE IN SERVICE OUT SERVICE

A A

L101 L101
SH.31/D7

13 6 8 6 8 6 8
-SLT -S87M1 IN -S87M2 IN -S87R IN
SH.84 OUT SH.84 OUT SH.84 OUT
SH.84
14 5 7 5 7 5 7
B B

L21

A A A A A A
-D1 -D2 -D3 -D4 -D5 -D6
SH.84 K SH.84 K SH.84 K SH.84 K SH.84 K SH.84 K

C C

L23 L25 L27 L29 L33 L35

D X1 X1 X1 X1 X1 X1 D
-H2 -H3 -H4 -H5 -H6 -H7
SH.84 SH.84 SH.84 SH.84 SH.84 SH.84
X2 X2 X2 X2 X2 X2

L102 L102
SH.31/D7

E E

:to replace

UNLESS OTHERWISE SPECIFIED, WIRES ARE 1.5 GREY (1000V)


F CLIENT: CONTRACTOR: TENAGA SWITCHGEAR SDN. BHD.- TITLE: = D00 + RBB1 /Q F
DATE 17.11.15 TENAGA TOSHIBA TRANSMISSION & 275kV SCHEMATIC DRAWING
DRAWN MAR NASIONAL BERHAD (200866-W) DISTRIBUTION SYSTEM ASIA SDN. BHD. JV 275kV HIGH IMPEDANCE BUSBAR PROTECTION
SUPPLIER: DRAWING NO.: REV.: THIS SHEET: 56
AS-BUILT 11.03.20 MAR/FAUZI/EHSAN/ABU CHECKED FAUZI/EHSAN CONTRACT NO.: TNB 99/2015 TOSHIBA TRANSMISSION & INDICATION CIRCUIT
REV. DATE DRN/CHK/REVIEWED REVIEWED ABU TENDER NO.: TNBT 808814 DISTRIBUTION SYSTEM ASIA SDN. BHD. SUBSTATION: PMU KANGKAR TEBRAU 275/132kV GIS TTDA KTRU 808814 275 S 11-BBHI AS-BUILT NEXT SHEET: 61
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ITEM DETAILS PANEL DEVICE TERMINAL FUNCTION DETAILS

PUSH BUTTON 13 23
A MANUFACTURER : IDEC IZUMI A
TYPE : YW1B-M1E20B
COLOR : BLACK 14 24
CONTACT : 2 N/O

+RBB1 -SLT SH.56/B2


SELECTOR SWITCH 2 4 6 8 10 12 14 16
SERVICE (IN/OUT)
MANUFACTURER : KRAUS & NAIMER IN
TYPE : CA10-A723MYC743 OUT
NO OF POLE : 4 POLE
NO OF POSITION : 2 POSITION 1 3 5 7 9 11 13 15
B SELECTION TYPE : STAYPUT + PAD LOCKABLE B
+RBB1 -S87M1 SH.51/A1 SH.56/B2 SH.56/B3 SH.77/C2 SH.75/C4
+RBB1 -S87M2 SH.51/A2 SH.56/B4 SH.56/B5 SH.77/C4 SH.75/C5
+RBB1 -S87R SH.51/A3 SH.56/B6 SH.56/B6 SH.77/C5 SH.75/C5

DIODE A
MANUFACTURER : PHOENIX
TYPE : UT4-MTD
RATING : 1300V, 0.5A K

+RBB1 -D1 SH.56/C2


C +RBB1 -D2 SH.56/C3 C
+RBB1 -D3 SH.56/C4
+RBB1 -D4 SH.56/C4
+RBB1 -D5 SH.56/C5
+RBB1 -D6 SH.56/C6
X1
INDICATION LAMP
MANUFACTURER : IDEC IZUMI : to replace lamp indicaton
TYPE : YW1P-2EQHA X2
COLOUR : WHITE
RATED VOLTAGE : 110V DC
+RBB1 -H2 SH.56/D2
D D
+RBB1 -H3 SH.56/D3
+RBB1 -H4 SH.56/D4
+RBB1 -H5 SH.56/D5
+RBB1 -H6 SH.56/D6
+RBB1 -H7 SH.56/D6

AUXILIARY RELAY
c/w FRONT CONNECTED BASE 2 4 5 6 7 9 8
MANUFACTURER : OMRON
TYPE : MKS3P c/w BASE PF113A-E 10
ORDERING CODE : MKS3P-I 110 VDC 1 3 11
E E
RATED VOLTAGE : 110V DC
POWER CONSUMPTION : 2.7 VA +RBB1 -K52/X1 SH.49/D2 SH.77/C7 SH.75/C3
TYPICAL PICK-UP TIME VALUE : 30ms
+RBB1 -K87BBHI/M1X SH.47/D3 SH.77/C2 SH.75/C2
(MAKE/BREAK CONTACTS)
TYPICAL DROP-OUT TIME : 20ms +RBB1 -K87BBHI/M2X SH.47/D5 SH.77/C3 SH.75/C2
(MAKE/BREAK CONTACTS) +RBB1 -K87BBHI/RX SH.47/D7 SH.77/C4 SH.75/C3
+RBB2 -K87BBHI/CX SH.48/D3 SH.77/C8 SH.75/C8

F CLIENT: CONTRACTOR: TENAGA SWITCHGEAR SDN. BHD.- TITLE: = D00 + RBB1 & RBB2 / X4 F
DATE 17.11.15 TENAGA TOSHIBA TRANSMISSION & 275kV SCHEMATIC DRAWING
DRAWN MAR NASIONAL BERHAD (200866-W) DISTRIBUTION SYSTEM ASIA SDN. BHD. JV 275kV HIGH IMPEDANCE BUSBAR PROTECTION
SUPPLIER: DRAWING NO.: REV.: THIS SHEET: 84
AS-BUILT 11.03.20 MAR/FAUZI/EHSAN/ABU CHECKED FAUZI/EHSAN CONTRACT NO.: TNB 99/2015 TOSHIBA TRANSMISSION & APPARATUS LIST
REV. DATE DRN/CHK/REVIEWED REVIEWED ABU TENDER NO.: TNBT 808814 DISTRIBUTION SYSTEM ASIA SDN. BHD. SUBSTATION: PMU KANGKAR TEBRAU 275/132kV GIS TTDA KTRU 808814 275 S 11-BBHI AS-BUILT NEXT SHEET: 85
1 2 3 4 5 6 7 8