You are on page 1of 2

Subject 603

March 2, 2012

SUMMARY OF TOPICS

The following change in requirements to the Standard for Power Supplies for Use with Burglar-
Alarm Systems, UL 603, is being proposed:

1. Modification of Table 26.1 to add Access Control System Units

STP BALLOTS AND COMMENTS DUE: April 2, 2012

UL’s goal is to have no interest category comprise more than one-third of the STP membership
balance. To improve the current balance for STP 205A, UL is looking for participants in the Testing and
Standards Organizations, Supply Chain, AHJ, Government, Consumer, Commercial/Industrial Users,
and International Delegate interest categories. Definitions for these interest categories are available on
the Standards STP Internet site:

http://ul.com/global/eng/pages/solutions/standards/developstandards/participation/
interestcategories/index.jsp

If you are interested in applying for STP 205A membership or are aware of potential candidates for this
STP, please contact the STP Project Manager, Megan.M.Sepper@ul.com.

For your convenience in review, proposed additions to existing requirements are shown underlined and
proposed deletions are shown lined-out.

1. Modification of Table 26.1 to add Access Control System Units

RATIONALE

Proposal submitted by: Lou Chavez, UL

This proposal adds details relative to battery standby requirements for Access Control System Units, UL
294, which is not presently specified on the table.
SUBJECT 603 -2- MARCH 2, 2012

PROPOSAL

Table 26.1
Battery standby times for alarm systems

UL standard covering equipment


Type of alarm system used in alarm system [see 1.1(b)] Standby time required

Bank Vault or Safe Alarma,d UL 365, UL 609, UL 827c,


UL 639, UL 72 hours
1076c, UL 1610c, UL 1635c
Mercantile Alarma UL 365, UL 609, UL 827, UL 639, UL 4 hours
1076, UL 1610, UL 1635
Alarm Receiving Equipment at a Police UL 365 4 hours – Mercantile
Department or a Central Station
8 hours – Bank
Holdup Alarm UL 636 8 hours
Household Alarmb UL 1023 4 hours or as marked
Electric Locking Mechanisms UL 1034 Not specified
Antitheft Alarm UL 1037 Not specified
Proprietary Alarm UL 1076 24 hours
Alarm Sounding Device UL 365, UL 609 15 minutes
Alarm Sounding Device UL 1023 4 minutes
Access Control Systems UL 294 4 hours or as marked
a If the power supply is also to provide power for an alarm sounding device, it shall provide an additional 15 minutes of

such power.
b If the power supply is also to provide power for an alarm sounding device, it shall provide an additional 4 minutes of such

power.
c Combination system only.
d Applies only to a power supply that will be located inside of the bank vault or safe.

Copyright © 2012 Underwriters Laboratories Inc.