You are on page 1of 13

Electric Power Systems Research 121 (2015) 1–13

Contents lists available at ScienceDirect

Electric Power Systems Research


journal homepage: www.elsevier.com/locate/epsr

Analysis of fault signatures for the diagnosis of induction motors fed


by voltage source inverters using ANOVA and additive models
Oscar Duque-Perez a,∗ , Luis-Angel Garcia-Escudero b , Daniel Morinigo-Sotelo a ,
Pedro-Esteban Gardel c , Marcelo Perez-Alonso d,e
a
Department of Electrical Engineering, University of Valladolid – UVA, 47011 Valladolid, Spain
b
Department of Statistics and Operational Research, University of Valladolid, 47011 Valladolid, Spain
c
National University of Asuncion, UNA, Paraguay
d
Renfe Fabricación y Mantenimiento SA, 28036 Madrid, Spain
e
Antonio de Nebrija University, 28040 Madrid, Spain

a r t i c l e i n f o a b s t r a c t

Article history: Condition monitoring of voltage source inverters-fed induction motors is challenging since the influence
Received 12 June 2014 of the supply complicates the use of methods valid for utility fed motors. Analysis of variance is performed
Received in revised form over data obtained in a controlled laboratory experiment where a hole was progressively drilled into a
20 November 2014
rotor bar. Additive models are obtained to stand out the influence of the operating conditions and the
Accepted 21 November 2014
supply on the amplitude of the fault signatures. Useful conclusions for the design of diagnosis systems
for the detection of broken bars in induction motors are drawn from the analysis.
Keywords:
© 2014 Elsevier B.V. All rights reserved.
Additive models
Condition monitoring
Fault diagnosis
Induction motors
Spectral analysis
Statistical analysis

1. Introduction Motor current signature analysis (MCSA) is currently consid-


ered as a standard in preventive maintenance basically due to
Induction motors are essential in many industries. Their sim- the advantages of using non-invasive sensors [8,9]. Nevertheless,
plicity and ruggedness are outstanding advantages and make them the introduction of VSI-fed (voltage source inverters) motors in
by far the most commonly used type of motor in sizes ranging applications where variable speed and torque are needed has pro-
from fractional horsepower to grades of industrial applications [1]. duced significant changes in the field of diagnostics needing further
However, owing to the thermal, electrical and mechanical stresses, research in order to overcome various challenges such as higher
industry is confronted with unexpected faults and lifetime reduc- noise level (inherent floor noise reduces the possibility of true
tion of these motors [2]. fault signature recognition using line current spectrum) [10,11],
The need to increase reliability against possible faults has dynamically changing excitation frequency and the fact that fault
attracted considerable interest in fault diagnosis of induction signatures can significantly change from open-loop to closed-loop
motors in recent years [3–7]. The main aim of a condition monitor- VSI operation. All these effects complicate the utilization of fre-
ing system is to detect incipient faults before a potentially harmful quency analysis methods [12]. VSI-fed motor faults have been
machine failure occurs with low missed and false alarms rates, in analyzed and initial results are given in literature [13–19] but fur-
order to discriminate among various machine conditions, classify- ther investigation is still required [20].
ing faulty modes from normal modes. The amplitude of fault harmonics is also affected by the sup-
ply voltage, making any of these anomalies more noticeable as the
supply voltage increases, provided that the machine is not working
under saturation condition. This is very important, and it must be
∗ Corresponding author at: Paseo del Cauce 59, 47011 Valladolid, Spain.
taken into account, particularly, with controlled-speed induction
Tel.: +34 983184533.
motors, when this control is based on voltage regulation, keep-
E-mail addresses: oscar.duque@eii.uva.es (O. Duque-Perez), lagarcia@eio.uva.es
(L.-A. Garcia-Escudero), daniel.morinigo@eii.uva.es (D. Morinigo-Sotelo),
ing constant the voltage/frequency ratio. Therefore, to develop a
pgardel@pol.una.py (P.-E. Gardel), marcelop@renfe.es (M. Perez-Alonso). generic condition monitoring method valid for any supply and

http://dx.doi.org/10.1016/j.epsr.2014.11.021
0378-7796/© 2014 Elsevier B.V. All rights reserved.
2 O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13

Table 1
Specifications of the tested motors.

Motor Rated power (kW) Rated voltage (V) Rated current (A) Rated speed (rpm) Pole pairs

M1 0.75 3 × 230/400 1.9 1395 2


M2 1.1 3 × 230/400 2.6 1415 2

at different operating conditions, further considerations must be rotating field at slip frequency with respect to the rotor. If a rotor
taken into account. asymmetry occurs, there will be a resultant backward rotating field
Considering this goal, in this paper it is analyzed the suitability at slip frequency with respect to the forward rotating rotor. This
of a number of fault signatures obtained from the stator current backward rotating field induces a voltage and a current in the
to diagnose rotor faults in induction motors fed by different sup- stator winding at (1 − 2s)f1 frequency (known as lower-sideband
plies. First, statistical tools such as boxplots and analysis of variance harmonic, LSH), where s is the motor slip and f1 is the funda-
(ANOVA) are used to analyze the data obtained from a case study mental frequency. This induced current is the cause of torque and
in which a cage fault condition has been produced by drilling speed pulsations, which at the same time, induce new electromo-
a hole in one of the bars of an induction motor. Different fault tive forces in the stator, and as a result, new counter currents are
conditions have been obtained by progressively making the hole produced at frequency (1 + 2s)f1 (known as upper-sideband har-
deeper. monic, USH). This process goes on indefinitely, until it is damped
Secondly, additive models are obtained, which are easy to inter- and a pair of new sidebands appears around the main frequency f1
pret but are more powerful analysis tools than linear models, as [26].
it is shown in Section 5. The aim of this analysis is to evaluate In VSI-driven induction motors, the line current will contain
the potential and suitability of the data, composed by the afore- additional time harmonics whose number, frequency and ampli-
mentioned fault signatures, to be used in a condition monitoring tude will depend on the switching strategy of the semiconductors.
task and to study the influence on the diagnosis of the type of These time harmonics will generate new air gap spatial harmonics
motor (two motors of different rated powers have been tested), or will modify the amplitude of the existing ones. That is, in addi-
the motor supply (five supplies have been used, utility supply and tion to the characteristic motor spectrum, new harmonics will be
four different frequency inverters with different types of control) introduced, related to the fault condition, to the driven load or to the
and the motor load level (the motors have been tested from low system performance. Therefore, the current spectrum is affected
load to full load). It is also evaluated the capability to distinguish by many factors, including the motor characteristics (stator con-
among four different rotor bar states: healthy, incipient fault (cor- nection, design and application), the power supply and the fault
responding to a 6 mm depth hole), half-broken bar and full broken condition.
bar. When a motor with a cage asymmetry is fed by a non-sinusoidal
The results show that the same fault severity produces differ- voltage supply, the process is very similar to a motor fed by a bal-
ent fault signature amplitudes depending on the type of the motor, anced and sinusoidal one [27]. A pair of sidebands around the time
supply and load level. This is critical in the construction of a uni- harmonics of the line current will appear at frequencies (k ± 2 ns)f1 ,
versal diagnosis procedure. Another significant contribution of this where k is the order of the line current time harmonic and n is
paper is the use of the additive models to quantify the influence of any positive integer. The number of sidebands will increase pro-
each of these influential variables in the amplitude of the fault sig- gressively, but their amplitude will decrease as they move away
natures, allowing the subtraction of the contribution of a variable in from the main frequency, although the magnitude of this amplitude
the fault signature value. This way, when constructing a universal attenuation will depend on the machine and driven load inertia and
diagnosis procedure, the bias produced by any of these variables the building characteristics of the motor, which, in turn, depend on
can be avoided. its purpose or application.

2. Detection of broken rotor bars in VSI-fed induction


motors 3. Case study

Induction motor failure through broken rotor bars (where crack- In this work, stator current is the signal measured and processed
ing is experienced in the rotor conductors) is common in many to determine the condition of the induction motor. Two different
industrial applications. One of the reasons for this type of failures motors, star connected, were tested. Each motor was fed from a
is that large starting currents occur when cooling is at minimum, set of three different sources. The first motor, named M1, was fed
resulting in thermal and mechanical stresses being at maximum. from the utility supply (UT), an inverter by Telemecanique (TE)
The incidence of this failure mode is greatest when the start-up and a laboratory inverter by Lucas Nülle (LN). The second motor,
time is relatively long and when frequent starts are required as named M2, was also fed from three sources: utility supply (UT)
part of a heavy-duty cycle [21]. Initially, they start as high resis- and two frequency inverters by Allen Bradley (AB) and by Siemens
tance, causing high temperature, and then progress as cracking or (SM). Table 1 shows the specifications of both motors. The control
small holes in the rotor bars [22]; healthy bars in imminent vicin- of the TE and SM inverters was of V/f linear type, the AB inverter
ity must conduct extra current, thus increasing the possibility of had sensorless vector control, while the control of the LN inverter
cracking due to increased stresses [23]. To prevent such cumula- permits an independent adjustment of voltage and frequency. All
tive destructive process, the problem should be detected as early as four inverters operated with the slip compensation option off and
possible [24]. Recently, improvements in machine design and man- with an assigned frequency of 50 Hz. In each test, the stator cur-
ufacturing have been very important in diminishing the occurrence rent was measured using a Hall effect current probe by Fluke (i30s)
of other types of faults in induction motors but squirrel cage design and a DAQ board by National Instruments (PCI-6250M) as data
has only changed slightly [25]. acquisition equipment. The software used was Labview DLLs for
When the cage winding is symmetrical and assuming a purely data acquisition, Matlab for signal processing and R as statistical
and balanced sinusoidal voltage supply, there is only a forward software for data analysis.
O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13 3

Table 2 Table 3
Description of the tests performed. Analysis of variance. Motors M1 and M2. LSH.

Condition state Description Hole depth M1 Hole depth M2 Estimate Std. error t p-value
(mm) (mm)
Intercept 11.9338 0.3336 35.768 <2e−16***
1 Healthy motor 0 0 Motor M2 −3.8749 0.3446 −11.244 <2e−16***
2 Incipient fault 6.4 5.7 Condition 2 1.8392 0.4683 3.928 9.06e−05***
3 Semi-broken bar 11.7 12.1 Condition 3 9.8605 0.4687 21.038 <2e−16***
4 Full-broken bar 17 18 Condition 4 14.7252 0.4742 31.050 <2e−16***

Signif. codes: 0 ‘***’ 0.001 ‘**’ 0.01 ‘*’ 0.05 ‘.’ 0.1 ‘ ’ 1.
Residual standard error: 5.984 on 1214 degrees of freedom.
Multiple R-squared: 0.5314, adjusted R-squared: 0.5298.
F-statistic: 344.1 on 4 and 1214 DF, p-value: <2.2e−16.
Four rotor conditions, corresponding to different fault severities,
were studied. The four fault severities were obtained by drilling a
hole of different depths (Table 2) into one of the rotor bars. As the 4. Statistical analysis of the results
goal was to perform a statistical analysis, 200 tests were performed
for each motor and voltage supply, covering a broad range of load In this section, the results of statistical analysis are shown with
conditions. the aim of drawing relevant conclusions for diagnosing rotor faults
Power spectral density (PSD) using the fast Fourier transform induction motors with different types of power supply.
(FFT) was used to extract fault features. This choice determines
the parameters of the data acquisition process. To avoid frequency 4.1. General analysis
aliasing, a high sampling frequency of 80 kHz was used. One of
the drawbacks of this signal processing technique is the spectral First, boxplots are used to analyze and compare the collected
leakage due to the use of a finite dataset to perform the spectrum data. Boxplots are a useful visual tool to compare means and vari-
calculation. This is solved by the use of an appropriate window ability between different datasets. In these boxplots, the legend in
function. In this work, the Hann window was applied to every full the x-axis is as follows: the first numeric value stands for the fault
measure since it decreases the spectral leakage with a good com- severity or condition state (1 for a healthy motor; 2 for an incipient
promise between resolution and amplitude accuracy. In order to fault; 3 for a half-broken bar; 4 for a full broken bar); next, it is
have a reasonable frequency resolution (0.1 Hz), the time acquisi- denoted the motor by M1 or M2; the additional letters are to indi-
tion period was 10 s, and this gives a measurement with 800,000 cate the type of supply using the acronyms previously mentioned
samples. in Section 3.
The amplitude of the LSH and USH harmonics are normally used Fig. 2 shows the boxplots of the amplitude of the fault signatures
as fault features for condition monitoring purposes. Instead of using around the main harmonic (Fig. 2a and b) for both tested motors, the
directly the FFT of each stator current, the PSD of the signal spec- four condition states including the three different supplies for each
trum is calculated because it allows a much better identification motor and all motor operating conditions. Motor M1 data are more
of the fault harmonics compared to the main component. Further- spread out indicating a larger variance and causing an overlapping
more, the PSDs were normalized so that the fundamental harmonic of the boxes.
frequency was always 0 dB. The graphic information given by the boxplots is completed with
As mentioned in the introduction, condition monitoring of VSI- some ANOVA models. In this analysis, the LSH and USH features are
driven induction motors is more challenging than for the utility taken as continuous response variables and “the type motor” and
supply case. For example, the stator current spectrum is highly “fault condition” as categorical explanatory variables. This analysis
affected in a different way by the specific VSI used as motor sup- demonstrated that the two categorical variables, “motor” and “con-
ply. To illustrate this, the PSD of the line current consumed by dition”, had a clear statistical significance in each ANOVA model
motor M1 with a full broken bar in the rotor under two differ- adjusted.
ent supplies is shown in Fig. 1. In Fig. 1a (UT supply), the fault Table 3 shows the associated estimated coefficients resulting
sidebands around the main harmonic are clearly seen and the from the ANOVA where the LSH feature was considered as response
noise level is very low. The current PSD of the same motor fed variable and motor M1 and Condition 1 (healthy motor) as the ref-
by TE supply is represented in Fig. 1b. Although operating con- erence levels. Since the associated p-values are much smaller than
ditions in both tests are similar (slip: 4.6%), it is very remarkable 0.01 and 0.001 (the standard cut-off values normally accepted), we
that the noise level is very high when the motor is fed with conclude that the following differences detected are statistically
the TE inverter. Additionally, an interharmonic appears between significant: means of the LSH measures between motors M1 and
the lower sideband and the main harmonic and this makes more M2, and means corresponding to the conditions 2, 3 and 4 (repre-
difficult to identify this fault signature in the current spectrum senting different fault severity degrees) with respect to condition
[28,29]. 1 (healthy motor).
For condition monitoring purposes, instead of the peak absolute Tukey’s honest significant differences method was also applied
value in dBs, as fault signature is considered the difference between as post hoc testing procedure to make a statistical comparison of the
the peak amplitude and the noise floor in the PSD of the stator cur- means of the 4 condition states for the LSH and USH response vari-
rent calculated by means of a wavelet function (the Daubechies ables. Tukey’s method provides a multiple testing correction when
orthonormal wavelet of length equal to 8, which is the least asym- comparing all these mean values (see [31] as reference for ANOVA
metric family, has been used [30]). The reason of choosing this testing and post hoc multiple comparisons). Although the results of
measurement, instead of the peak absolute value in dBs, is because applying this multiple comparison technique are not reported here,
it is considered essential to take into account the different level all differences observed between pairs of means were statistically
of noise introduced by the power supply. For example, in Fig. 1, significant in the analysis of the fault signatures. The p-values again
the first band of fault signatures has similar amplitudes for both were very close to 0 and thus statistical significant differences were
motor supplies. However, while they are clearly observed for UT detected among these 4 mean values.
supply, in the inverter-fed motor case they are almost hidden by The boxplots, ANOVA models and post hoc comparisons suggest
the noise. that these fault signatures may be adequate to discriminate among
4 O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13

Fig. 1. Normalized PSD around main harmonic. Motor M1 with a full-broken bar. Supplies UT and TE.

the four condition states. Fig. 2 shows overlapping among the boxes, allow us to be more conclusive, the analysis has to consider the
which indicates that in some operating conditions it could be dif- influence of the different operating conditions. In Section 4.2, it
ficult to distinguish between adjacent fault severity conditions: will be analyzed the influence of the supply and in Section 4.3 the
a healthy state and an incipient fault, between an incipient fault influence of the load.
and a semi broken bar, and between the semi broken and the full
broken bar. The use of additive models will allow us to overcome 4.2. Influence of the supply on the signature faults
some of these difficulties as it will be shown in Section 5.
Fig. 2 shows too, the boxplots corresponding to the sidebands In this section, data are segregated according to motor and sup-
around the fifth (Fig. 2c and d) and seventh harmonic (Fig. 2e and f), ply with the aim to point out the diagnostic differences due to the
respectively. It can be inferred from these plots that the LSH around supply. The boxplots of the amplitude of the LSH and USH fault
the fifth harmonic is a useful fault signature to complement the signatures are shown in Fig. 3. Tables 4 and 5 present the results
information provided by the signatures around the main harmonic. of the ANOVA models adjusted for both motors. Now, the type of
However, this is not the case for the rest of fault signatures, at least, power supply is included in the analysis as a variable. Several inter-
when the data obtained in all the different operating conditions are esting conclusions can be drawn from the analysis of these figure
analyzed together. and tables. The most obvious one is that results are not similar for
It must be pointed out that this analysis used mixed data from all combinations of motors and supplies. Each case studied will be
two different motors, six supplies and different load conditions. To analyzed separately next.
O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13 5

Fig. 2. Boxplots of the amplitude of the broken bar signature faults LSH (left) and USH (right) around the main harmonic (top figure), fifth harmonic (middle figure) and
seventh harmonic, for motors M1 and M2, all types of supply and four condition states (denoted as 1 to 4, from healthy to full broken bar).

First, we focus on motor M1 and UT supply analysis results. It UT supply. It is remarkable that, when only the LSH is considered,
is observed that the evolution of the fault severity can be clearly the ANOVA models of Table 6 show that the differences between
traced by extracting the LSH and UHS fault signatures from the cur- both supplies are not significant. But, this is not the case when the
rent spectrum. An incipient fault is even easily observable because USH is studied. In the case of the LSH study, there is an overlapping
there is no overlapping between the boxes of healthy motor and between boxes corresponding to the condition states 1 and 2. But,
incipient fault conditions. Nevertheless, this is not the case when on the other hand, half-broken and complete broken bar condition
it comes to distinguish between half-broken bar and full broken states can be clearly observed and distinguished. On the contrary,
bar conditions. The peak amplitudes characterizing a half-broken if only the USH is considered, there is no overlapping between the
bar condition are so high (and therefore, so easily observable) that boxes of conditions states 1 and 2.
they produce an overlapping with the box corresponding with a full The condition monitoring is more challenging when the motor
broken bar, making very difficult to distinguish these two condition M1 is fed by the TE inverter. This supply is characterized by a
states. high noise level in the current spectrum. While an incipient fault
When the motor is fed by the LN frequency inverter, the ampli- is hardly distinguishable from a healthy motor condition, a half-
tude of the fault peaks shows a behavior somehow similar to the broken bar condition is observable but not as easily as for UT or
6 O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13

a)

40

30
dB

20

10

1 .M 1 _ U T

2 .M 1 _ U T

3 .M 1 _ U T

4 .M 1 _ U T

1 .M 2 _ U T

2 .M 2 _ U T

3 .M 2 _ U T

4 .M 2 _ U T
1 .M 1 _ T E

2 .M 1 _ T E

3 .M 1 _ T E

4 .M 1 _ T E

1 .M 2 _ A B

2 .M 2 _ A B

3 .M 2 _ A B

4 .M 2 _ A B

1 .M 2 _ S M

2 .M 2 _ S M

3 .M 2 _ S M

4 .M 2 _ S M
1 .M 1 _ L N

2 .M 1 _ L N

3 .M 1 _ L N

4 .M 1 _ L N

b)
40

30
dB

20

10
1 .M 1 _ U T

2 .M 1 _ U T

3 .M 1 _ U T

4 .M 1 _ U T

1 .M 2 _ U T

2 .M 2 _ U T

3 .M 2 _ U T

4 .M 2 _ U T
1 .M 2 _ A B

2 .M 2 _ A B

3 .M 2 _ A B

4 .M 2 _ A B
1 .M 1 _ T E

2 .M 1 _ T E

3 .M 1 _ T E

4 .M 1 _ T E

1 .M 2 _ S M

2 .M 2 _ S M

3 .M 2 _ S M

4 .M 2 _ S M
1 .M 1 _ L N

2 .M 1 _ L N

3 .M 1 _ L N

4 .M 1 _ L N

Fig. 3. Boxplots of the amplitude of the broken bar signature fault (LSH: top figure, USH, bottom figure) around the main harmonic, for motors M1 and M2, six different
supplies and four condition states (denoted as 1 to 4, from healthy to full broken bar).

LN supplies. Furthermore, all condition states show lower fault sig- state 1 as reference, there is not significant evidence of interaction
nature amplitudes, and consequently, the fault detection is not as between the four condition states. Therefore, the two fault signa-
straightforward as it was with the other supplies. Therefore, fault tures are useful for condition monitoring purposes. In Table 5, the
detection is more difficulty when the motor is fed by this inverter. p-value for the condition state 2 is much bigger than for the other
Next, the results corresponding to the motor M2 analysis are condition states. This result means that it could be difficult to dis-
shown. The ANOVA models of Table 5 indicate that, taking condition tinguish between condition states 1 and 2. This is also observed
O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13 7

Table 4
Analysis of variance. Motor M1. LSH and USH.

LSH USH

Estimate Std. error t p-value Estimate Std. error t p-value

Intercept 10.2955 0.7514 13.701 <2e−16*** 12.5562 0.7720 16.265 <2e−16***


typeM1 LN 0.3798 0.5503 0.690 0.49 −2.6006 0.5654 −4.600 5.16e−06***
typeM1 TE −10.0824 0.4108 −24.541 <2e−16*** −10.3997 −0.4221 24.639 <2e−16***
Slip 114.9593 13.7517 8.360 4.33e−16*** 89.6634 14.1280 6.346 4.32e−10***
Condition 2 3.2075 0.4953 6.477 1.94e−10*** 4.5680 0.5088 8.978 <2e−16***
Condition 3 10.2642 0.4855 21.142 <2e−16*** 9.8418 0.4988 19.732 <2e−16***
Condition 4 15.8637 0.5193 30.547 <2e−16*** 15.0091 0.5335 28.132 <2e−16***

Signif. codes: 0 ‘***’ 0.001 ‘**’ 0.01 ‘*’ 0.05 ‘.’ 0.1 ‘ ’ 1.
Residual standard error: 4.461 on 605 degrees of freedom.
Multiple R-squared: 0.7985, adjusted R-squared: 0.7965.
F-statistic: 399.5 on 6 and 605 DF, p-value: <2.2e−16.
Residual standard error: 4.584 on 605 degrees of freedom.
Multiple R-squared: 0.7579, adjusted R-squared: 0.7555.
F-statistic: 315.7 on 6 and 605 DF, p-value: <2.2e−16.

Table 5
Analysis of variance. Motor M2. LSH and USH.

LSH USH

Estimate Std. error t p-value Estimate Std. error t p-value

Intercept 6.6327 0.5401 12.280 <2e−16*** 5.8980 0.5724 10.304 <2e−16***


typeM2 AB −2.2867 0.3808 −6.005 3.32e−09*** −1.6869 0.4036 −4.180 3.35e−05***
typeM2 SM −0.1410 0.3882 −0.363 0.7166 0.3993 0.4114 0.971 0.332
Slip 101.6038 15.2920 6.644 6.85e−11*** 112.7421 16.2057 6.957 9.13e−12***
Condition 2 1.1622 0.4287 2.711 0.0069** 2.9176 0.4543 6.422 2.73e−10***
Condition 3 9.5110 0.4410 21.566 <2e−16*** 10.5088 0.4674 22.485 <2e−16***
Condition 4 11.9837 0.4300 27.871 <2e−16*** 13.1294 0.4557 28.814 <2e−16***

Signif. codes: 0 ‘***’ 0.001 ‘**’ 0.01 ‘*’ 0.05 ‘.’ 0.1 ‘ ’ 1.
Residual standard error: 3.856 on 600 degrees of freedom.
Multiple R-squared: 0.663, adjusted R-squared: 0.6597.
F-statistic: 196.8 on 6 and 600 DF, p-value: <2.2e−16.
Residual standard error: 4.086 on 600 degrees of freedom.
Multiple R-squared: 0.6647, adjusted R-squared: 0.6614.
F-statistic: 198.3 on 6 and 600 DF, p-value: <2.2e−16.

in the boxplots of Fig. 3, where there is an overlapping between Table 6


Analysis of variance. Comparison of LSH versus the sum of the amplitudes of the
condition states 1 and 2.
peaks.
This M2 motor was also fed by three different voltage supplies
(UT, AB and SM inverters), which were also compared, consider- Res. Df RSS Df sum of Sq F p-value
ing the UT supply as the reference. The ANOVA results show that Motors LSH 1263 61,872
the LSH and USH fault signatures are significantly different when Condition LSH 1260 23,448 688.26 <2.2e−16
the motor is fed by the AB inverter compared to the UT voltage Motors LSH + USH 1263 230,558
Condition LSH + USH 1260 80,765 778.97 <2.2e−16
supply. This important result should be considered in the design
of a general-purpose condition monitoring strategy. Fault signa- Signif. codes: 0 ‘***’ 0.001 ‘**’ 0.01 ‘*’ 0.05 ‘.’ 0.1 ‘ ’ 1.
tures when the motor is fed by the SM inverter show a different
behavior. The ANOVA results provide high p-values for both fault 4.3. Influence of the slip
signatures, which proves that they have relatively similar distribu-
tions for both motor supplies (UT and SM). These different results As aforementioned, the motor was tested in a broad range of
could be explained by the different control strategies used by each load conditions in each group of tests. Hence, so far analyzed
inverter. results mix up all motor load conditions. The performed ANOVA
This subsection has shown the results obtained when different (Tables 4 and 5) shows the significant impact of slip in the dis-
motor supplies are considered. The type of voltage supply has a sub- tinction between condition states. The analysis is now performed
stantial effect on the amplitude of the fault signatures. It has been independently for different load conditions with the aim to deter-
observed that when the inverter has an independent adjustment of mine how the fault diagnosis could be affected by the slip or motor
voltage and frequency, the results are similar to the UT case. In the load. Fig. 4 shows the boxplots of the LSH (Fig. 4a) and the USH
case of sensorless vector control, the results are very different than (Fig. 4b) distributions for the six supplies and four condition states
for the rest of supplies. Two different situations have been observed considered in this study. But here, the datasets are divided in two
for the V/f linear control. In one of them (SM supply) the results are groups depending on the value of the slip. One group is labeled as
quite similar to the UT supply. Meanwhile, the condition monitor- “High” slip if its value is greater than 0.04. If this value is lower than
ing task would be more difficult if the motor is fed by the TE supply. 0.04, the other group is labeled as “Low” slip.
The reason is that this inverter produces a high noise level in the Again, the results are different depending on supply. Addition-
current spectrum. ally and not surprisingly, the boxes are less overlapped at high slips
8 O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13

Fig. 4. Boxplot of the amplitude of the broken bar signature fault (LSH: top figure, USH, bottom figure) around the main harmonic, for motors M1 and M2, six different
supplies and four condition states (denoted as 1 to 4, from healthy to full broken bar). Two sets of tests are considered according to slip being higher or lower than 0.04
(denoted as “high” and “low”).
O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13 9

80

60

dB
40

20

1.M1

2.M1

3.M1

4.M1

1.M2

2.M2

3.M2

4.M2
Fig. 5. Boxplot of the sum of the amplitudes of the broken bar signature faults LSH and USH around the main harmonic, for both motors, six different supplies and four
condition states.

than at low ones. This means that fault detection should be easier should be preferred if the influence of the drive inertia has to be
at high slips. More precisely, when motor M1 is fed by the UT sup- considered.
ply and at low slips, it is difficult to distinguish between condition
states 3 and 4. However, boxes hardly overlap at high slips. Con-
5. Additive models
clusions are analogous for conditions states 1 and 2 when the M2
motor is fed by the same supply.
The results analyzed in the previous sections show that there is
Condition states 3 and 4 are more easily differentiated at high
usually some overlapping between the boxplots of the fault sig-
slips when the motor is fed by the LN and TE inverters than when the
natures. These box overlappings make the fault detection more
AB inverter is used to feed the motor. The incipient fault detection
difficult. It is also harder to estimate the fault severity by a sim-
is also easier at high slips than at low ones. When the SM inverter
ple observation of the amplitude of the fault related harmonics.
is used as voltage supply, no significant differences are observed
Besides, the different operational conditions considered, character-
between high and low slips.
ized by the voltage supply, type of motor and variable motor load,
have been proved to have a significant impact on the amplitude of
the fault signatures. In this paper, it is proposed the use of additive
4.4. LSH versus USH models to separate the effect of these factors on the amplitude of
the fault signatures with the aim of improving fault detectability
The goal of this section is to study and compare the suitability and severity estimation.
for condition monitoring of the LSH and USH fault signatures. In an Additive models are useful data analytic tool to estimate
overall analysis and from a statistical point of view, the LSH and USH the effect of different variables in the response of a system by
distributions are quite similar not showing important differences. using nonparametric regression techniques. They are based on the
Their variances are similar or, in some cases, larger for the USH. approximation of a multivariate function f(x1 , . . ., xn ) as the sum of
A deeper analysis about the distinction between condition states univariate functions fj (xj ) [35].
1 and 2 shows that the boxes of the USH fault signature have less The estimation of the individual terms explains how the
overlapping than the boxes of the LSH. Let us not forget that incipi- dependent variable changes with the corresponding independent
ent fault detection is the most challenging situation for a condition variables and which variables do not have a significant impact in
monitoring system. the response. Therefore, additive models can be seen as a general-
All in all, it could be concluded that the USH is best suited as ization of multiple regression models, which maintain the additive
a fault signature for condition monitoring purposes. Although the nature of the models, but it is allowed to replace simple linear terms
influence of the motor and drive inertia should not be dismissed as predictors by unspecified (non-parametric) functions that can be
since the LSH and USH have a strong dependence on the motor estimated through “backfitting” algorithms. These models are flex-
plus load inertia. Rotor speed oscillations that give rise to the USH ible and easy to implement, and once the model has been identified,
are limited by the drive inertia. On the other hand, these fluctua- it is easy to assess the influence of each primary variable xj on f(x1 ,
tions reduce the amplitude of the LSH. Therefore, the LSH is higher . . ., xn ) just by plotting fj against xj [36]. They have been previously
mainly in high inertia drives, but the USH may be predominant for used to solve problems such the design of heat transfers [37], for the
very low inertia ones [20,32,33] and this is the case of our labo- planning of distributed generation [38], to obtain optimum work-
ratory tests. Nevertheless, amplitude changes are similar for both ing conditions of heat-pumps [39] and to forecast the prices in the
fault signatures, but in opposite directions and, consequently, the electric market [40,41].
sum of the amplitudes of LSH and USH remains quite constant In this work, additive models have been fitted using the R
with the inertia [34]. The boxplots of the sum of the amplitudes free software environment for statistical computing and the “gam”
of the LSH and USH of both motors are shown in Fig. 5. Table 6 package available at the CRAN repository [42]. Each response vari-
shows a comparison of the ANOVA of the LSH and the sum of able is modeled as a sum of a common overall mean value , plus
both fault harmonics. The results demonstrate that these fault sig- the effects of the type of motor and voltage supply Ti , the effect of
natures are equally suited for detection purposes, but the sum the motor load as a continuous function of the value s, plus the fault
10 O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13

Fig. 6. Additive model for the amplitude of LSH (top figure) and USH (bottom figure) around the main harmonic, for both motors, six different supplies and four condition
states.

condition state Cj where j = 1, 2, 3 and 4, plus the sum of a random can be taken into account and subtracted in order to achieve more
error term ε. That is: accurate classifications in case of an unknown condition state.
Fig. 6 shows the additive models for the LSH (Fig. 6a) and the
USH (Fig. 6b). Comparing both Figs., no significant differences exist
Dependent variable = m + Ti + s(slip) + Cj + ε
apparently between both peaks. The additive models calculated
confirm the ANOVA and Boxplots results analyzed in the previous
where the dependent variable can be the LSH, the USH or LSH + USH. sections. The models show that the three variables are relevant and
Twice-standard-error confident limits and bands have been also should be taken into account to develop a condition monitoring
included for each considered effect in the additive models. Notice expert system. The voltage supply used to feed the motor has an
that this fitted model allows understanding whether it is possible to important influence in determining the amplitude of the fault sig-
detect differences among the four considered motor fault condition natures. As it was observed in the previous sections, some supplies
states after controlling the differences in type of motor/supply or in lead to similar results: (i) LN and UT supplies in the case of motor
the slip. Moreover, in future developments, these estimated effects M1; (ii) SM and UT supplies in the case of motor M2.
O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13 11

M1_LN M1_TE M1_UT 1 2 3 4

10

10

10
5

5
partial for condition
partial for type

s(slip)
0

0
-5

-5

-5
-10

-10

-10
0.02 0.04 0.06 0.08
type condition
slip

a)
M2_AB M2_SM M2_UT 1 2 3 4
10

10

10
5

5
partial for condition
partial for type

s(slip)
0

0
-5

-5

-5
-10

-10

-10

0.01 0.02 0.03 0.04 0.05 0.06


type condition
slip

b)
Fig. 7. Additive model for motor M1 (top figure) and M2 (bottom figure). Independent variable: amplitude of the USH around the main harmonic. Dependent variables: type
of supply, slip and condition state.

As it is observed in the middle graphic of Fig. 6, the model the other factors. This way, the performance of a diagnostic or con-
shows a quasi-linear dependence with the slip, especially for slips dition monitoring system (some classifier, for example) would be
between 2 and 6%. significantly improved.
An important result can be observed in the right subplots of Fig. 7 shows the results of the additive model of the USH consid-
Fig. 6, where it is plotted the contribution of the fault severity to ering separately the data of each motor (the models for LSH and for
the amplitude of the fault signatures. It can be considered that it is LSH + USH are very similar). One of the most important results is
represented the fault signature after subtracting the contribution that the influence of TE inverter is clearly differentiated from the
of the type of motor and supply (left subplot) and the contribu- others voltage supplies. This inverter had a high noise level in the
tion of the slip (central subplot). Now, the four conditions states current spectrum.
are clearly distinguished. There is no overlapping between the four Fig. 8 is also very interesting. It shows the additive model results
boxes. The additive models allow us to point out the contribution of the case when the UT supply was used to feed both motors. Again,
of the fault severity and to separate and eliminate the influence of in the right subplot, the contribution of the four fault severities to
12 O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13

Fig. 8. Additive model for the amplitude of the USH around the main harmonic, for motors M1 and M2 fed by the utility supply, UT.

the fault signature is completely distinguishable. The left subplot All the statistical analyses have also proven that the USH around
represents the contribution of the type of motor (labeled as type the main harmonic is the best suited as a fault signature. In fact, in
in the figure). It is important to notice that each motor contributes most of the cases both fault signatures are equally valid, but, in the
differently to the amplitude of the fault signature. most challenging situations, the USH fault signature has proved
Thus, the additive models demonstrate the influence of each to be the most adequate. In our laboratory setup the motor-load
factor in the value of the fault signature. The most important result system was characterized by a low inertia. Nevertheless, the sum
is that the additive model allows us to highlight the fault severity of both sidebands is also valid as fault signature and it is mostly
contribution to the dependent variable (the amplitude of the fault independent of the inertia.
signature). This is easily observed in the right subplots in all the The obtained results also show that a universal diagnosis
figures. This variable, Cj , can be used as input data to a classifier method for an induction motor must consider the information
trained for the diagnosing of the motor. The performance of the about the type of motor, the type of supply, the load level or the
classifier would be greatly improved comparing to the case where slip. On the other hand and for the presented cases, these results
it is trained with the raw data obtained from the spectra. offer guidance about which fault signatures are more suitable for
diagnosing and if the slip or load level must be taken into account.
The most important result of this study is that the same fault
6. Conclusions severity produces different fault signature amplitudes depending
on the type of the motor, supply and load level. This is crucial in the
The main goal of this paper was the use of statistical tools to construction of a diagnosis procedure for different motors, supplies
study if some fault signatures extracted from the stator current or motors operating under a wide range of load levels. It has been
were suitable for diagnosing rotor faults in induction motors in proven that the additive models allow us to quantify the influence
steady state operation. A case study is presented where a rotor bro- of each of these variables in the amplitude of the fault signatures.
ken bar fault evolution has been tested and analyzed. The fault is These results confirm the conclusions obtained with the ANOVA
simulated by a progressive drilling of a hole in one of the rotor bars analysis. They can be very useful for diagnosis purposes allowing
in two different induction motors. These motors were fed by differ- the subtraction of the contribution of a variable in the fault signa-
ent supplies: utility supply and four different frequency inverters ture value. So, the bias produced by any of these variables in the
with different control strategies. The motors were also tested at amplitude of the fault signature can be avoided when constructing
different loads, covering from low load to full load. a universal diagnosis procedure or system.
This fault produces a pair of bands around the main harmonic.
The amplitudes of these two harmonics are considered as fault sig- Acknowledgements
natures. The results demonstrate statistically that these data are
suitable for performing a condition monitoring task. It was also García-Escudero’s research was partially supported by the
demonstrated the importance and significance on the fault diagno- Spanish Ministerio de Ciencia y Tecnología, grant MTM2011-
sis of the following variables: type of motor, voltage supply and the 28657-C02-01, by Consejería de Educación y Cultura de la JCyL,
motor load. grant VA212U130.
One of the most important results of this analysis is that the type
References
of voltage supply, used to feed the motor, has a substantial impact
on the detectability of the fault and the subsequent diagnosis. This [1] Y. Oguz, M. Dede, Speed estimation of vector controlled squirrel cage asyn-
makes the detection of the fault at an early stage especially difficult chronous motor with artificial neural networks, Energy Convers. Manag. 52
when the motor is fed by some inverters. (2011) 675–686.
O. Duque-Perez et al. / Electric Power Systems Research 121 (2015) 1–13 13

[2] J. Faiz, B.M. Ebrahimi, Locating rotor broken bars in induction motors using [22] H. Çalıs, A. Çakır, Experimental study for sensorless broken bar detection in
finite element method, Energy Convers. Manag. 50 (2009) 125–131. induction motors, Energy Convers. Manag. 49 (2008) 854–862.
[3] M.R. Mehrjou, N. Mariun, M.H. Marhaban, N. Misron, Rotor fault condition mon- [23] K. Drobnic, M. Nemec, R. Fiser, V. Ambrozic, Simplified detection of broken rotor
itoring techniques for squirrel-cage induction machine – a review, Mech. Syst. bars in induction motors controlled in field reference frame, Control Eng. Pract.
Signal Process. 25 (2011) 2827–2848. 20 (2012) 761–769.
[4] H. Keskesa, A. Brahama, Z. Lachiri, Broken rotor bar diagnosis in induction [24] L.M. Rabelo Baccarini, J.P. Braga Tavares, B. Rodrigues de Menezes, W.M. Camin-
machines through stationary wavelet packet transform and multiclass wavelet has, Sliding mode observer for on-line broken rotor bar detection, Electr. Power
SVM, Electr. Power Syst. Res. 97 (2013) 151–157. Syst. Res. 80 (2010) 1089–1095.
[5] G.K. Singh, S.A.S. Al Kazzaz, Induction machine drive condition monitoring and [25] I. Aydin, M. Karakose, E. Akin, A new method for early fault detection and
diagnostic research – a survey, Electr. Power Syst. Res. 64 (2003) 145–158. diagnosis of broken rotor bars, Energy Convers. Manag. 52 (2011) 1790–1799.
[6] A.G. Garcia-Ramirez, L.A. Morales-Hernandez, R. Osornio-Rios, J.P. Benitez- [26] F. Filippetti, G. Franceschini, C. Tassoni, P. Vas, Impact of speed ripple on rotor
Rangela, A. Garcia-Perez, R.J. Romero-Troncoso, Fault detection in induction fault diagnosis of induction machines, in: Proc. International Conference of
motors and the impact on the kinematic chain through thermographic analysis, Electric Machines and Drives, 1994, pp. 452–456.
Electr. Power Syst. Res. 114 (2014) 1–9. [27] O. Duque-Perez, D. Morinigo-Sotelo, A. Rodriguez, L.A. Garcia-Escudero, M.
[7] J. Cusidó, L. Romeral, J.A. Ortega, A. Garcia, J.R. Riba, Wavelet and PDD as fault Perez-Alonso, Experimental identification of induction motor broken bar char-
detection techniques, Electr. Power Syst. Res. 80 (2010) 915–924. acteristic frequencies using a programmable power source, in: Proc. 2010 19th
[8] M.E.H. Benbouzid, A review of induction motors signature analysis as a medium International Conference on Electrical Machines, 2010.
for faults detection, IEEE Trans. Ind. Electron. 47 (2000) 984–993. [28] S.R.H. Amrei, X. Dian, A new study on harmonics and interharmonics reduction
[9] M. Pineda-Sanchez, M. Riera-Guasp, J. Perez-Cruz, R. Puche-Panadero, Tran- with frequency selective closed-loop control in VSI inverters, in: Vehicle Power
sient motor current signature analysis via modulus of the continuous complex and Propulsion Conference, 2008, pp. 1–6, VPPC ‘08.
wavelet: a pattern approach, Energy Convers. Manag. 73 (2013) 26–36. [29] J.H. Jung, J.J. Lee, B.H. Kwon, Online diagnosis of induction motors using MCSA,
[10] F. Briz, M.W. Degner, P. Garcia, A.B. Diez, High-frequency carrier-signal voltage IEEE Trans. Ind. Electron. 53 (2006) 1842–1852.
selection for stator winding fault diagnosis in inverter-fed ac machines, IEEE [30] L.A. García-Escudero, O. Duque-Perez, D. Morinigo-Sotelo, M. Perez-Alonso,
Trans. Ind. Electron. 55 (2008) 4181–4190. Robust condition monitoring for early detection of broken rotor bars in induc-
[11] R. Wieser, C. Kral, F. Pirker, M. Schagginger, On-line rotor cage monitoring of tion motors, Expert Syst. Appl. 38 (2011) 2653–2660.
inverter-fed induction machines by means of an improved method, IEEE Trans. [31] R. Christensen, Analysis of Variance, Design, and Regression: Applied Statistical
Power Electron. 14 (1999) 858–865. Methods, Chapman and Hall, London, 1996.
[12] D.F. Pires, V.F. Pires, J.F. Martins, A.J. Pires, Rotor cage fault diagnosis in three- [32] C. Kral, F. Pirker, G. Pascoli, The impact of inertia on rotor fault effects – theo-
phase induction motors based on a current and virtual flux approach, Energy retical aspects of the Vienna monitoring method, IEEE Trans. Power Electron.
Convers. Manag. 50 (2009) 1026–1032. 23 (2008) 2136–2142.
[13] B. Akin, U. Orguner, H.A. Toliyat, M. Rayner, Low order PWM inverter harmonics [33] F. Filippetti, G. Franceschini, C. Tassoni, P. Vas, AI techniques in induction
contributions to the inverter-fed induction machine fault diagnosis, IEEE Trans. machines diagnosis including the speed ripple effect, IEEE Trans. Ind. Appl.
Ind. Electron. 55 (2008) 610–619. 34 (1998) 98–108.
[14] G.R. Bossio, C.H.D. Angelo, G.O. Garcia, J.A. Solsona, M.I. Valla, Effects of rotor [34] A. Bellini, C. Concari, G. Franceschini, E. Lorenzani, C. Tassoni, A. Toscani,
bar and end-ring faults over the signals of a position estimation strategy for Thorough understanding and experimental validation of current sideband
induction motors, IEEE Trans. Ind. Appl. 41 (2005) 1005–1012. components in induction machines rotor monitoring, IEEE 32nd Annual Con-
[15] M.F. Cabanas, F. Pedrayes, C.H. Rojas, M.G. Melero, J.G. Norniella, G.A. Orcajo, ference on Industrial Electronics, IECON (2006) 4957–4962.
J.M. Cano, F. Nuño, D.R. Fuentes, A new portable, self-powered, and wireless [35] T. Hastie, R. Tibshirani, Generalized Additive Models, Chapman and Hall, Lon-
instrument for the early detection of broken rotor bars in induction motors, don, 1990.
IEEE Trans. Ind. Electron. 58 (2011) 4917–4929. [36] G. De Nicolao, R. Scattolini, C. Siviero, Modelling the volumetric efficiency of ic
[16] C. Bruzzese, Analysis and application of particular current signatures (symp- engines: parametric, non-parametric and neural techniques, Control Eng. Pract.
toms) for cage monitoring in nonsinusoidally fed motors with high rejection 4 (1996) 1405–1415.
to drive load, inertia, and frequency variations, IEEE Trans. Ind. Electron. 55 [37] B. Sahin, A. Demir, Thermal performance analysis and optimum design param-
(2008) 4137–4155. eters of heat exchanger having perforated pin fins, the planning of distributed
[17] D. Morinigo-Sotelo, L.A. Garcia-Escudero, O. Duque-Perez, M. Perez-Alonso, generation, Energy Convers. Manag. 49 (2008) 1684–1695.
Practical aspects of mixed eccentricity detection in PWM voltage source [38] M.R. AlRashidi, M.F. AlHajri, Optimal planning of multiple distributed genera-
inverter fed induction motors, IEEE Trans. Ind. Electron. 57 (2010) tion sources in distribution networks: a new approach, Energy Convers. Manag.
252–262. 52 (2011) 3301–3308.
[18] I.P. Georgakopoulos, E.D. Mitronikas, A.N. Safacas, Detection of induction motor [39] O. Çomakli, C. Çelik, S. Erdogan, Determination of optimum working condi-
faults in inverter drives using inverter input current analysis, IEEE Trans. Ind. tions in heat-pumps using nonazeotropic refrigerant mixtures, Energy Convers.
Electron. 58 (2011) 4365–4373. Manag. 40 (1999) 193–203.
[19] M. Akar, Detection of a static eccentricity fault in a closed loop driven induction [40] R.J. Bessa, M.A. Matos, Global against divided optimization for the participation
motor by using the angular domain order tracking analysis method, Mech. Syst. of an EV aggregator in the day-ahead electricity market. Part I: theory, Electr.
Signal Process. 34 (2013) 173–182. Power Syst. Res. 95 (2013) 309–318.
[20] A. Bellini, F. Filippetti, C. Tassoni, G.A. Capolino, Advances in diagnostic [41] R.J. Bessa, M.A. Matos, Optimization models for an EV aggregator selling sec-
techniques for induction machines, IEEE Trans. Ind. Electron. 55 (2008) ondary reserve in the electricity market, Electr. Power Syst. Res. 106 (2014)
4109–4126. 36–50.
[21] B. Payne, A. Ball, F. Gu, Detection and diagnosis of induction motor faults using [42] R Development Core Team R, A language and environment for statistical com-
statistical measures, Proc. Int. J. COMADEM 5 (2002) 5–19. puting, R Foundation for Statistical, 2009.

You might also like