Professional Documents
Culture Documents
3, MARCH 2015
0278-0046 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
FROSINI et al.: INDUCTION MACHINE BEARING FAULT DETECTION BY MEANS OF STATISTICAL PROCESSING 1847
In [15], Kokko states that the most interesting leakage fluxes frequency bandwidth since the derivation tends to increase
from the diagnostic point of view are at the stator end winding, the magnitude of high-frequency components. A variable gain
rotor end winding, and rotor end ring. These fluxes leak in (from 10 to 100) amplifier is connected at the terminals of this
the axial direction outside the motor and can be detected by flux sensor. Moreover, a lowpass anti-aliasing filter is used in
external axial flux sensors. The determination of the complex order to set the frequency bandwidth to a correct range for the
3D pattern of this leakage flux is difficult but not necessary. In spectrum analysis. In [16], the tests have been carried out on
fact, the condition monitoring of motors by axial leakage flux an 11 kW four-pole squirrel-cage IM supplied from both the
is based on the relative changes in certain flux frequency com- mains and an inverter, at standstill, at no-load and at rated load.
ponents, and their absolute amplitude values are not required. The leakage flux analysis has been proven more effective to
In [15], the frequencies to analyze in the axial flux spectrum detect stator faults with respect to the motor current signature
are identified, on the basis of the literature and of the manual analysis technique. In [30], the same motor is tested in normal
of the commercial system, and are divided into “low” and operation, and the stray flux sensor is positioned parallel to the
“high” components. The low-frequency components simply are frontal section of the machine. In [32], different rotor faults
a function of the supply frequency, slip, and number of poles. of various IMs have been investigated. The tests have been
The high-frequency components are supplementary functions carried out for different values of load. Note that to detect
also of the number of stator and rotor slots. Consequently, stator short circuits, the frequencies investigated are under
the low-frequency components are simple to calculate, even 1 kHz, whereas to diagnose broken rotor bars, the harmonic
for motors used in industrial environment, whereas the others components of interest are the sidebands (1 ± 2s) fs around
require usually not well-known information. The threshold the supply frequency fs . Finally, the broken bar diagnosis has
values of these axial flux harmonics, which can distinguish a been investigated by means of the stray flux measurement after
faulty motor from a healthy motor, are not easy to predeter- supply disconnection [33].
mine, because several factors affect them. For this reason, it Another case studied by the same authors is the monitoring of
is recommendable to collect a reference measurement of the the stray flux harmonic components induced by a gearbox in a
axial flux for each healthy motor, to find out experimentally the 4 kW four-pole wound rotor and in a 5.5 kW eight-pole squirrel-
relative distribution of these harmonic components. In fact, the cage rotor IM. The motors have been tested at low load fed by
experimental results in [15] show that there are quite significant the power grid and at no-load supplied by the inverter. Some
differences in the harmonic distributions of various machines characteristic frequencies due to the gearbox can be observed in
and applications; hence, it is not possible to define general the stray flux spectrum, whereas they cannot be detected in the
parameters for diverse machines used in various applications. stator current spectrum. On the contrary, when the motors are
Moreover, the result of the stator current analysis cannot be supplied by the inverter, other harmonic components disappear
directly used as a reference value for axial fluxes. The stator from the flux spectrum [34].
current spectra are quite alike for similar motors; hence, the In [17], a different type of external flux sensor is proposed: It
spectrum of one motor can be quite reliably used as a reference is made of 300 turns on a “C” magnetic core, and it is located
value for another similar motor. In the axial flux spectra, there on the machine frame. Bellini et al. used it to detect broken
are so many differences among the various motors that it is rotor bars. They observed that the right sideband component
better to set a reference measurement for each machine. In the amplitude increases with the slip more than the left one because
case of two nearby installed PWM converter supplied motors, the measured variable is the flux derivative. The conclusion of
the flux probe placed near one of the motors also detects the this paper is that line current and stray flux signals can be used
field induced by the other motor. Moreover, as the sensitivity of with the same effectiveness in order to detect and quantify rotor
the flux coil is the least at low frequencies, sensitivity problems faults. The optimal choice depends on the specific application
can arise for variable-speed-driven motors when working at low and on the easiness of installing flux or current sensors in the
speeds. specific industrial environment. This is because stray flux is
Interesting information can be obtained also from the time- induced by stator and rotor currents, but the effect of stator
domain analysis of the stray flux, as presented in [15] and [16]. currents prevails, since the stator acts as a magnetic shield with
In [16] and in the following papers, the authors use a stray flux respect to the rotor. Hence, stray flux analysis is expected to
sensor to detect stator winding faults [16], [30], [31], broken convey the same information that can be obtained by conven-
rotor bars [32], [33], and to monitor the gearbox [34]. The tional stator current analysis [18].
circular air coil stray flux sensor having several hundred turns In [19], the axial leakage flux was measured with a circular
has to be placed near the machine body. In [16], it is proposed search coil of a diameter comparable to the motor. This search
that this has to be positioned parallel to the horizontal axis coil was concentrically mounted with the shaft on the rear of
of the machine (in practice, perpendicular with respect to the an IM. The frequencies of interest to detect broken bars were
sensor used in [15]). The authors maintain that the diameter the (1 ± 2s) fs sidebands around the supply main component at
of the sensor has to be much less than the total height of the fs . The positioning of the flux coil during the tests was found
machine body, in order to perform the measurement of flux to affect the flux spectra. Moving the flux coil by about 10 cm
in an area covering the width of several stator slots. Then, the away from the motor in an axial direction caused the amplitude
dimension of this coil is not independent from the machine size. of the flux sidebands to increase by about 5 dB relative to the
The voltage at the coil terminals is proportional to the derivative main flux component. Placing the flux coil at an angle relative
of the stray flux; hence, it has a low magnitude and a large- to the motor caused these sidebands to decrease relative to
FROSINI et al.: INDUCTION MACHINE BEARING FAULT DETECTION BY MEANS OF STATISTICAL PROCESSING 1849
the main component. In conclusion, the authors state that the Performing the survey on the stray-flux-based diagnosis, one
analysis of the current spectrum offers a more accurate broken of the main conclusions was that even if the stator current
bar fault detection than that of the stray flux spectrum. harmonics excited by bearing faults are theoretically related to
In [20], an air coil has been used to measure the external specific frequencies, these do not always appear, whereas some
leakage flux in the radial direction coming from a 3 kW four- integer harmonics in the stray flux spectra are amplified when
pole squirrel-cage IM supplied by the grid. The spectrum of the the bearings are damaged [37].
radial flux proves not to be very sensitive to the broken rotor bar Based on these considerations, the authors started their re-
fault. Whereas in the case of stator interturn short-circuit faults, search with the idea of finding in the stray flux spectra some
it is revealed to be more sensitive with respect to the spectrum integer multiples of the fundamental frequency, excited in case
of the line current. of bearing faults. Note that these harmonic components can
In [21], Ceban et al. consider the axial–radial decomposition be easily determined in the absence of the specific machine
of the external magnetic field. The axial field is in a plane parameters, contrary to other harmonics evaluated, e.g., in [15],
that includes the axis of the machine and is generated by which are functions of the stator and rotor slots numbers.
currents in the stator end windings or rotor cage end ring. The The proposed fault detection method, being statistical, re-
radial field is located in a perpendicular plane to the machine quires at least ten data acquisitions of the stray flux, performed
axis, and it is an image of the air-gap flux density, which is under identical conditions, both for the healthy machine (con-
attenuated by the stator magnetic circuit and by the external sidered as reference) and the same machine having diverse
frame of the machine. These fields can be separately measured bearing faults. The method pursues the following subsequent
by a convenient placement of a wound flux sensor. When the steps [38].
sensor is positioned on the body of the machine and parallel • Each integer multiple of the fundamental, between 100
to its longitudinal plane, the flux linked to the sensor is purely and 1000 Hz, is normalized with respect to the 50 Hz
radial. On the contrary, when the sensor is perpendicular to this fundamental.
position, it measures the radial field, but it also embraces one • For every integer harmonic component taken into account,
part of the axial field. Analyzing the magnetic field spectrum a mean value of ten acquisitions is computed, for both the
emitted by an IM, there has been observed the appearance of a healthy and the faulty conditions of the machine (mh and
component at sfs , only in the axial field. Its magnitude can be mf , respectively).
relatively low for a machine in a healthy condition. Moreover, • The difference of the mean values mentioned above (d =
in the spectrum of the axial field, the appearance of the 3sfs mh − mf ) is calculated.
harmonic can be observed, generated by rotor broken bars. The • In order to evaluate the diagnostic content of the processed
fault diagnosis becomes more difficult for weak loads, because data, the absolute value of the difference (Δ = |d|) is com-
these harmonics do not appear for a very low slip. pared with the standard deviation (S) of the harmonics in
A Bell 7030 Tesla meter fixed in the middle of the stator the case of the healthy motor.
frame length to measure the tangential component of the stray Based on this comparison, three levels of fault significance
flux is presented in [22]. Vitek et al. affirm that this equipment is are considered [38]:
very expensive for practical industrial applications, particularly • low, if Δ > S;
for small IMs. With this sensor, dynamic rotor eccentricity and • medium, if Δ > 2S;
a bearing fault in the inner race was investigated. It was con- • high, if Δ > 5S.
cluded that the stray flux is advantageous for the detection of
In order to overcome the problems due to noisy references,
dynamic eccentricity, due to a significant relationship between
a fault is signaled only if at least one of the above conditions
the amplitude of characteristic spectral components and the
is fulfilled. If none of these conditions are fulfilled, an incipient
eccentricity level. On the other hand, the practical utilization
bearing failure is impossible to be detected by means of this
of the magnetic stray flux for observing bearing defect is
method.
controversial, since the amplitudes of the characteristic spectral
The proposed bearing fault detection method based on
components are very low in both stator current and stray flux.
statistical computations is actually applicable in industrial
In another approach, giant magnetoresistance (GMR) sensors
environment as a truly accurate, yet simple and robust fault
are used to measure the stray flux around electrical actuators.
indicator [39].
GMR sensors produce a large change in resistance when the
devices are subjected to a magnetic field. They are particularly
suited for such purposes due to their measurement range and IV. E XPERIMENTAL PART
their linearity [35].
A. Experimental Setup
The measurements were performed in the Laboratory of
III. P ROPOSED FAULT D ETECTION M ETHOD
Electric Drives at the University of Pavia, Italy on a test bench
As was also previously presented, the most interesting fea- described in detail in [40].
ture of stray flux around an IM is its dependence on the stator The grid-connected three-phase 2445T4050-type IM (FIR
and rotor currents [16]. Therefore, studying the significant Elettromeccanica S.r.l.) has the following rated data: power of
frequency components of the stray flux, stator or rotor asym- 2.2 kW, current of 8.7/5 A, and speed of 2800 r/min. It has two
metries can be detected [36]. NSK 6205Z-type rolling ball bearings with nine balls, which
1850 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 62, NO. 3, MARCH 2015
TABLE II
N UMBER OF I NTEGER H ARMONICS F ULFILLING THE T WO M AJOR
L EVELS OF FAULT S IGNIFICANCE
Fig. 8. Integer harmonics of the radial leakage flux measured for two
IMs of the same power.
These were obtained by using the custom flux probe for mea-
suring the radial stray flux on the drive end of the half-loaded
machine. In both plots, the Δ difference values are marked for
each integer harmonic in the range of 100 ÷ 1000 Hz by black
bullets. Via different colored areas, the three fault significance
bands are also highlighted. In both cases, the numerous black
bullets mainly in the Δ > 2S and Δ > 5S fault significance
bands clearly indicate the bearing faults in the IM taken into
study.
To prove the repeatability of the proposed measurements and
data processing, a part of the tests were also performed in the
Electrical Machines Laboratory at the Technical University of
Cluj-Napoca, Romania. An IM having the same power and
number of poles was used. The fluxes were measured with a
similar custom flux probe. The results of the radial leakage flux
measurements on the drive end (performed at 50% of the rated
load) of the healthy machines are given in Fig. 8.
As can be seen, the outcomes of the tests performed in the
two laboratories are very close.
V. C ONCLUSION
In this paper, the benefits arising from the use of a custom
stray flux sensor for the diagnostics of rolling bearing faults in
an IM have been presented. These faults are generally slowly
Fig. 6. Δ versus frequency plot for damaged bearing seal condition. progressive; therefore, continuous online monitoring aimed at
detecting them in real time is not necessary.
The proposed method, which can be defined as noninvasive
and quasi-online, needs an initial data set as “healthy reference”
for comparisons to the successive measurements during the
motor lifetime. This data set should be collected during the
commissioning of the motor or, anyway, in the first period of
its lifetime (when it can be reasonably considered “healthy”),
possibly by comparing the initial data sets of identical machines
and/or requiring the manufacturer a particular quality control on
the bearings. Note that several other comparison-based methods
are used in the industry for diagnostic purposes (e.g., partial
Fig. 7. Δ versus frequency plot for a hole in the outer race condition.
discharge analysis).
The custom flux probe has been successfully employed to
• The fault detection efficiency of the most severe fault detect three types of bearing faults, one of them very poorly
index (Δ > 5S) is relatively poor. investigated in the literature (the deformation of the seal); its
Next, to deepen the understanding of the proposed fault performance has been evaluated in different positions around
detection method, two plotted results are given in Figs. 6 and 7. the motor and compared with those obtained with a commercial
FROSINI et al.: INDUCTION MACHINE BEARING FAULT DETECTION BY MEANS OF STATISTICAL PROCESSING 1853
A PPENDIX
As the magnetic flux measurements highly depend on the Fig. 10. Normalized integer harmonics of the axial stray flux measured
used flux sensor and on its amplification and filtering stage, a at the fan end by means of the two types of flux probes.
comparison between the two flux measuring systems has been
the fan end by means of both flux sensors, for the fully loaded
performed.
healthy machine, are given in Fig. 10.
The Emerson flux probe is practically an air coil without
As it can be seen in Fig. 10, there are no significant differ-
nonlinear magnetic materials; therefore, it has linear amplitude
ences between the harmonic values for each frequency. This
characteristics, and its parameters are very stable in time. The
means that the proposed statistical-processing-based bearing
custom probe has a soft magnetic iron core, which leads to a
fault detection method can be efficiently used with both types
significant improvement of its characteristics. The toll to pay
of flux probes.
for this enhancement is the loss of linearity at high flux mag-
nitudes and frequencies [44]. As the proposed fault detection R EFERENCES
method requires the measurement of weak stray fluxes and [1] H. Henao et al., “Trends in fault diagnosis for electrical machines—A
the frequency domain of interest is under 1 kHz, the proposed review of diagnostic techniques,” IEEE Ind. Electron. Mag., vol. 8, no. 2,
custom flux probe always works in the linear domain. pp. 31–42, Jun. 2014.
[2] P. Zhang, Y. Du, T. G. Habetler, and B. Lu, “A survey of condition mon-
The output characteristics of both sensors have to be defined, itoring and protection methods for medium-voltage induction motors,”
since also those of the industrial flux probe were not specified IEEE Trans. Ind. Appl., vol. 47, no. 1, pp. 34–46, Jan./Feb. 2011.
in the product data sheet [41]. The performances of the sensors [3] A. Garcia-Perez, R. de Jesus Romero-Troncoso, E. Cabal-Yepez, and
R. A. Osornio-Rios, “The application of high-resolution spectral analy-
and the applied measuring system were analyzed only in the sis for identifying multiple combined faults in induction motors,” IEEE
frequency domain of interest for the proposed fault detection Trans. Ind. Electron., vol. 58, no. 5, pp. 2002–2010, May 2011.
method (50 Hz ÷ 1 kHz). [4] F. Immovilli, A. Bellini, R. Rubini, and C. Tassoni, “Diagnosis of bearing
faults in induction machines by vibration or current signals: A critical
The frequency response of the two flux measuring systems is comparison,” IEEE Tran. Ind. Appl., vol. 46, no. 4, pp. 1350–1359,
given in Fig. 9. Jul./Aug. 2010.
As can be seen, the response of both systems is linear in this [5] F. Immovilli, C. Bianchini, M. Cocconcelli, A. Bellini, and
R. Rubini, “Bearing fault model for induction motor with externally
frequency domain. The frequency response of the custom flux induced vibration,” IEEE Tran. Ind. Appl., vol. 60, no. 8, pp. 3408–3418,
probe is more constant than that of the industrial one. Jul./Aug. 2013.
Moreover, the sensitivity of the custom probe is better [6] M. Blodt, P. Granjon, B. Raison, and G. Rostaing, “Models for bearing
damage detection in induction motors using stator current monitoring,”
(240 mV/T) than that of the other probe (80 mV/T). IEEE Trans. Ind. Electron., vol. 55, no. 4, pp. 1813–1822, Apr. 2008.
All these characteristics emphasize the usefulness of the cus- [7] S. H. Kia, H. Henao, and G.-A. Capolino, “A high-resolution frequency
tom magnetic flux probe used for the proposed fault detection estimation method for three-phase induction machine fault detection,”
IEEE Trans. Ind. Electron., vol. 54, no. 4, pp. 2305–2314, Aug. 2007.
method. [8] R. Romary, R. Pusca, J. Lecointe, and J. Brudny, “Electrical machines
By normalizing the harmonics with respect to the funda- fault diagnosis by stray flux analysis,” in Proc. IEEE WEMDCD, Paris,
mental, the measurement differences due to the unlike sensor France, 2013, pp. 247–256.
[9] N. Mehala and R. Dahiya, “Detection of bearing faults of induction motor
sensitivities are diminished. In order to illustrate this statement, using Park’s vector approach,” Int. J. Eng. Technol., vol. 2, no. 4, pp. 263–
the normalized harmonics of the axial stray flux measured at 266, 2010.
1854 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 62, NO. 3, MARCH 2015
[10] A. Ibrahim, M. El Badaoui, F. Guillet, and F. Bonnardot, “A new bearing [30] H. Henao, G.-A. Capolino, and C. S. Marţiş, “On the stray flux analysis
fault detection method in induction machines based on Instantaneous for the detection of the three-phase induction machine faults,” in Conf.
Power Factor,” IEEE Trans. Ind. Electron., vol. 55, no. 12, pp. 4252–4259, Rec. 38th IEEE IAS Annu. Meeting, 2003, vol. 2, pp. 1368–1373.
Dec. 2008. [31] A. Yazidi et al., “Detection of stator short-circuit in induction machines
[11] K. S. Gaeid, H. W. Ping, M. K. Masood, and L. Szabó, “Survey of wavelet using an external leakage flux sensor,” in Proc. IEEE ICIT, Hammamet,
fault diagnosis and tolerant of induction machines with case study,” Int. Tunisia, 2004, pp. 166–169.
Rev. Elect. Eng., vol. 7, no. 3, pp. 4437–4457, May 2012. [32] A. Yazidi, H. Henao, and G.-A. Capolino, “Broken rotor bars fault de-
[12] E. Ayaz, A. Ozturk, and S. Seker, “Continuous wavelet transform for tection in squirrel cage induction machines,” in Proc. IEEE IEMDC,
bearing damage detection in electric motors,” in Proc. IEEE MELECON, San Antonio, TX, USA, 2005, pp. 741–747.
Malaga, Spain, 2006, pp. 1130–1133. [33] S. H. Kia, H. Henao, G.-A. Capolino, and C. S. Marţiş, “Induction ma-
[13] M. D. Negrea, “Electromagnetic flux monitoring for detecting faults in chine broken bars fault detection using stray flux after supply disconnec-
electrical machines,” Ph.D. dissertation, Dept. Elect. Commun. Eng., tion,” in Proc. IEEE IECON, Paris, France, 2006, pp. 1498–1503.
Helsinki Univ. Technol., Espoo, Finland, 2006. [34] S. M. J. Rastegar Fatemi, H. Henao, and G.-A. Capolino, “Gearbox
[14] J. Penman, H. G. Sedding, B. A. Lloyd, and W. T. Fink, “Detection monitoring by using the stray flux in an induction machine based elec-
and location of interturn short circuits in the stator windings of operat- tromechanical system,” in Proc. IEEE MELECON, Ajaccio, France, 2008,
ing motors,” IEEE Trans. Energy Convers., vol. 9, no. 4, pp. 652–658, pp. 484–489.
Dec. 1994. [35] M. Brela, N. Kassim, and J. Franke, “Characterization of magnetic actu-
[15] V. Kokko, “Condition monitoring of squirrel-cage motors by axial mag- ators by measuring of magnetic stray fields with GMR-sensors,” in Proc.
netic flux measurements,” M.S. thesis, Dept. Elect. Eng., Optoelectron. 3rd Int. EDPC, Nuremberg, Germany, 2013, pp. 1–7.
Meas., Univ. Oulu, Oulu, Finland, 2006. [36] R. R. Schoen, T. G. Habetler, F. Kamran, and R. G. Bartheld, “Motor
[16] H. Henao, C. Demian, and G.-A. Capolino, “A frequency-domain de- bearing damage detection using stator current monitoring,” IEEE Trans.
tection of stator winding faults in induction machines using an external Ind. Appl., vol. 31, no. 6, pp. 1274–1279, Nov./Dec. 1995.
flux sensor,” IEEE Trans. Ind. Appl., vol. 39, no. 5, pp. 1272–1279, [37] L. Frosini and E. Bassi, “Stator current and motor efficiency as indicators
Sep./Oct. 2003. for different types of bearing faults in induction motors,” IEEE Trans. Ind.
[17] A. Bellini, S. Concari, G. Franceschini, C. Tassoni, and A. Toscani, “Vi- Electron., vol. 57, no. 1, pp. 244–251, Jan. 2010.
brations, currents and stray flux signals to asses induction motor rotor [38] L. Frosini, A. Borin, L. Girometta, and G. Venchi, “A novel approach to
condition,” in Proc. IEEE IECON, Paris, France, 2006, pp. 4963–4968. detect short circuits in low voltage induction motor by stray flux measure-
[18] C. Concari, G. Franceschini, and C. Tassoni, “Differential diagnosis ment,” in Proc. IEEE ICEM, Marseille, France, 2012, pp. 1538–1544.
based on multivariable monitoring to assess induction machine rotor [39] C. Harlişca, L. Szabó, L. Frosini, and A. Albini, “Diagnosis of rolling
conditions,” IEEE Trans. Ind. Electron., vol. 55, no. 12, pp. 4156–4166, bearings faults in electric machines through stray magnetic flux monitor-
Dec. 2008. ing,” in Proc. Int. Symp. ATEE, Bucureşti, Romania, 2013, pp. 1–6.
[19] J. M. B. Siau, A. L. Graff, W. L. Soong, and N. Ertugrul, “Broken bar [40] C. Harlişca, L. Szabó, L. Frosini, and A. Albini, “Bearing faults detec-
detection in induction motors using current and flux spectral analysis,” tion in induction machines based on statistical processing of the stray
Aust. J. Elect. Electron. Eng., vol. 1, pp. 171–178, 2004. fluxes measurements,” in Proc. IEEE SDEMPED, Valencia, Spain, 2013,
[20] R. Romary, R. Corton, D. Thailly, and J. F. Brudny, “Induction machine pp. 371–376.
fault diagnosis using an external radial flux sensor,” Eur. Phys. J., Appl. [41] Model 343 Flux Coil—Product Data Sheet, Emerson Process Manage-
Phys., vol. 32, no. 2, pp. 125–132, Nov. 2005. ment, Knoxville, TN, USA, 2004.
[21] A. Ceban, R. Pusca, and R. Romary, “Eccentricity and broken rotor bars [42] L. Frosini, A. Borin, L. Girometta, and G. Venchi, “Development of a
faults—Effects on the external axial field,” in Proc. IEEE ICEM, Rome, leakage flux measurement system for condition monitoring of electrical
Italy, 2010, pp. 1–6. drives,” in Proc. IEEE SDEMPED, Bologna, Italy, 2011, pp. 356–363.
[22] O. Vitek, M. Janda, V. Hajek, and P. Bauer, “Detection of eccentricity and [43] L. Frosini, A. Borin, A. Albini, and F. Benzi, “New techniques to simulate
bearing faults using stray flux monitoring,” in Proc. IEEE SDEMPED, and diagnose stator winding faults in low voltage induction motors,” in
Bologna, Italy, 2011, pp. 456–461. Proc. IEEE ICEM, Marseille, France, 2012, pp. 1783–1789.
[23] A. Bellini, F. Filippetti, C. Tassoni, and G.-A. Capolino, “Advances in di- [44] P. Ripka, Magnetic Sensors and Magnetometers. Boston, MA, USA:
agnostic techniques for induction machines,” IEEE Trans. Ind. Electron., Artech House, 2001.
vol. 55, no. 12, pp. 4109–4126, Dec. 2008.
[24] T. Boukra, A. Lebaroud, and G. Clerc, “Statistical and neural-network
approaches for the classification of induction machine faults using the
Lucia Frosini received the M.Sc. and Ph.D. degrees in electrical engi-
ambiguity plane representation,” IEEE Trans. Ind. Electron., vol. 60,
neering from the University of Pavia, Pavia, Italy.
no. 9, pp. 4034–4042, Sep. 2013.
She is currently an Assistant Professor with the University of Pavia.
[25] M. D. Prieto, G. Cirrincione, A. G. Espinosa, J. A. Ortega, and H. Henao,
She is the author of about 60 scientific publications, mainly on diagnos-
“Bearing fault detection by a novel condition-monitoring scheme based on
tics of electrical machines.
statistical-time features and neural networks,” IEEE Trans. Ind. Electron.,
vol. 60, no. 8, pp. 3398–3407, Aug. 2013.
[26] R. J. Romero-Troncoso et al., “FPGA-based online detection of multiple
combined faults in induction motors through information entropy and Ciprian Harlişca received the B.Sc., M.Sc., and Ph.D. degrees in
fuzzy inference,” IEEE Trans. Ind. Electron., vol. 58, no. 11, pp. 5263– electrical engineering from the Technical University of Cluj-Napoca,
5270, Nov. 2011. Cluj-Napoca, Romania.
[27] R. Romary, C. Demian, P. Schlupp, and J.-Y. Roger, “Offline and online He has published more than ten papers, all in the field of bearing fault
methods for stator core fault detection in large generators,” IEEE Trans. detection of induction machines.
Ind. Electron., vol. 60, no. 9, pp. 4084–4092, Sep. 2013.
[28] C. H. De Angelo et al., “Online model-based stator-fault detection and
identification in induction motors,” IEEE Trans. Ind. Electron., vol. 56, Loránd Szabó (M’05) is a Full Professor of electrical machines with
no. 11, pp. 4671–4680, Nov. 2009. the Technical University of Cluj-Napoca, Cluj-Napoca, Romania. His
[29] W. T. Thomson, “A review of on-line condition monitoring techniques for research interests include variable reluctance machines, linear motors,
three-phase squirrel-cage induction motors—Past present and future,” in and condition monitoring and diagnosis of electrical machines. He has
Proc. IEEE SDEMPED, Gijon, Spain, 1999, pp. 3–18. published more than 240 papers in these fields.