Professional Documents
Culture Documents
NEW DRAWING
MODIFIED
DRAWING
Micom 346
3xCT
250/5
MODIFIED
40VA
40IN.5P10
YHCEI-7ASR
DRAWING
PTx2
11000/110V
200VA P21
1.0CL P11 P31
YHP-12 Connection for Resistor should
be on TB which will be
finalized after discussion.
P11
P21
P31
C23 C63
C24 C73
C22
C62
C24 C72
3xCT
250/5
C21 40VA C61
40IN.5P20
C24 YHCEI-6ARN C71
CTT4
G11/CTT Y34 G11 G12
X1-1
G21/CTT Y35 G21 G22
X1-2
P346
E1-CP10
2P,10A X23 X24 X25 X26 X27 X28 X29 X30 X31 X32
X23
51NX-1
51NX-1
12 8
9 5
X18 X19
NGR
X1-3 X1-5
Z28
Z29
PTT-1/OUT
U Phase
PTT-1/OUT
PTT-1/OUT
W Phase
V Phase
X21
X23
N110C
26
terminal by Vendor.
P31
P21
P11
X20
Watch Dog
X39
27X
Under Voltage trip X24
Z29
P110C
SHT9-1/8E X22
50X
Over Current trip X27
P110C
SHT9-1/5E
40X
Loss of Exitation trip X28
P110C
SHT9-1/3E
32PX
X29
Reverse Active Power P110C
trip SHT9-1/2E
DC110 Supply For
Micom, And new
Reverse Reactive
32QX Breaker Install
X30
Power trip SHT9-1/2E P110C SHT09-1/8E
C24
C24
C23
C22
C73
C21
C63
C62
C72
C71
C61
CTT-2/OUT
CTT-2/OUT
CTT-2/OUT
CTT-2/OUT
V Phase
U Phase
W Phase
WATT-M /TB#3S
New CTT plug and Wire
WATT-M /TB#1S
CTT-3/OUT
CTT-3/OUT
N
U Phase
V Phase
CTT-3/OUT
X-11
W Phase
NEW DRAWING