Wiring Diagram
RELAY OUTPUT
MAX 24V AC / DC – 2A
(SELV)
Transponder Reader with bell
POWER SUPPLY (SELV)
12 / 24 V AC
TR32A09KNX– Varnished Light Grey 12 / 32 V DC
TR32A19KNX– Anthracite 1 2 3 4
TR32A29KNX– White
OUT 1 OUT 2
INPUT 1 6
tal, Offices, Parking, etc..) where the access control applica- 1 Power Supply 12/24 VAC 12/32V /DC (must be SELV)
BUS INTERFACE
tion is required. 2 Power Supply 12/24 VAC 12/32V /DC (must be SELV)
The device is equipped with two binary inputs (potential free 3 OUT1 terminal relay 1 (NO) (must be SELV)
contacts) that can be used, for instance, to control whether the 4 OUT2 terminal relay2 (NO) (must be SELV)
door lock has been opened or closed or other signals coming 5 COM Outputs
KNX / EIB
from external switches/contacts (i.e. windows, bathroom emer- 6 IN 1 (potential free)
gency alarms, etc..) and with one frontal switch freely config- 7 IN 2 (potential free)
urable by ETS. 8 COM Inputs
The transponder reader is equipped also with two output re- 9 Programming LED
lays which can be used for any purposes, typically to open the Physical specifications and Dimensions 10 Programming push button
door or turning on the courtesy light inside the room. 11 Bus Connection Terminal:
The product provides on the front side four LEDs in order to • Housing: plastic Black = bus polarity (-)
enlighten 4 icons to display the following states (e.g. in case of • Colours: Light Grey Varnished (TR22A02KNX), Red = bus polarity (+)
Hotel management): Anthracite (TR22A12KNX) 12 Led 4
Access Allowed/Not Allowed White (TR22A22KNX) 13 Led 3
SOS request • Dimensions: (W x H x D): 110 x 78 x 37.1 mm 14 Led 2
Service Call (clean room, etc..) 15 Led red/green
• Weight: approx. 120 g.
Client status (“Busy room” or “Do not Disturb”) 16 Switch
• Installation: Flash mounting in 2 or 3 modules or wall round
box Ø60mm, 40mm deep
The LEDs and icons can be configured in association with
other alarms or events. Installation Instructions
The transponder reader can reads cards or keys at a maximum
distance of 30mm from the front side.
The access control follows a sequence where the “build num- The device may be used for permanent indoor installations
ber” has been checked at first, then the “data” to check if it has in dry locations within wall boxes.
been elapsed or not, next the password ID for cli-
ent/guest/service identification, then the enabled entrance tim- WARNING
ing window. In case card reading pass all checks the door is • The device must not be connected to 230V AC cables.
opened and, if set, the courtesy light inside is switched on. At • Device must be installed in a single box ; any other device
the same time the Transponder Holder can send the reading in the same box must be SELV.
response to the bus. • The prevailing safety rules must be heeded.
The device configuration for commissioning in terms of physi-
• The device must be mounted and commissioned by an
cal address, group addresses and parameters is done with
authorised installer.
ETS ( Engineering Tool Software) through a download of the
• The applicable safety and accident prevention regulations
Application Program.
must be observed.
Electrical Safety • The device must not be opened. Any faulty devices
Application Program should be returned to manufacturer.
• Compliant with LV Directive 2006/95/EC • For planning and construction of electric installations, the
• Pollution degree : 2 (according to EN 60664-1) relevant guidelines, regulations and standards of the re-
ETS Database downlodable from website www.eelectron.com
• Protection class IP20 (according to EN 60529) spective country are to be considered.
• Safety class: III (according to EN 61140)
Technical Specifications • Overvoltage category: III (according to EN 60664-1)
Mounting and Wiring hints
• Bus: safety extra low voltage SELV DC 24 V
Power Supply • Device complies with EN 50090 and EN 60664-1
• External Auxiliary Voltage: 12/24 VAC 12/32VDC (SELV) WARNING
• Maximum current : 100mA Electromagnetic compatibility The device must be mounted in horizontal position.
• Bus line: 9
Eelectron SpA
email: info@eelectron.com
Web: www.eelectron.com
TR32AX9KNXFI01010001.DOC
Schema di Connessione
USCITA RELE’ – 2A
MAX 24V AC / DC
(SELV)
Lettore Transponder con pulsante
ALIMENTAZIONE (SELV)
12 / 24 V AC
TR32A09KNX – Grigio Chiaro verniciato 12 / 32 V DC
TR32A19KNX – Antracite
1 2 3 4
TR32A29KNX – Bianco
OUT 1 OUT 2
Descrizione del prodotto e suo funzionamento COM 5
INPUT 1 6
Il lettore di transponder TR32Ax9KNX è un apparecchio INPUT 2
EIB/KNX in esecuzione per montaggio ad incasso dedicato al 7
Eelectron SpA
email: info@eelectron.com
Web: www.eelectron.com