Professional Documents
Culture Documents
Form 5233
May 1999 Type 2390 and 2390B
Dry Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 1. Type 2390 or 2390B Liquid Level Transmitter
Principle of Operation . . . . . . . . . . . . . . . . . . . . 17 and Typical Sensor
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Printed Wiring Board Compartment Parts
Checking Transmitter Hall-Effect Removal and Replacement . . . . . . . . . . . . . . . 22
Sensor Assembly . . . . . . . . . . . . . . . . . . . . . . . . 20 Removing the Analog Output Meter . . . . . . . . . . 22
Checking the Analog Output Meter . . . . . . . . . . . 21 Removing the Printed Wiring Board Assembly 22
Removing the Transmitter from a Removing a Potentiometer Assembly . . . . . . . . 22
249 Series Sensor . . . . . . . . . . . . . . . . . . . . . . . 21 Removing and Re-installing the Transmitter
249 Series Sensor in Standard Hall-Effect Sensor Assembly . . . . . . . . . . . . . 22
Temperature Application . . . . . . . . . . . . . . . . . 21 Re-installing a Potentiometer Assembly . . . . . . 22
249 Series Sensor in High Temperature Re-installing a Printed Wiring Board Assembly 22
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Re-installing the Analog Output Meter . . . . . . . . 22
D200364X012
Type 2390 and 2390B
Contents (Continued)
Sensor Connection Compartment Parts Removal
and Re-installation . . . . . . . . . . . . . . . . . . . . . . . 23
Removing the Lever Assembly . . . . . . . . . . . . . . 23
Removing and Replacing the Flexure Strips . . 23
Removing the Dry Span Scale . . . . . . . . . . . . . . 24
Re-installing the Dry Span Scale . . . . . . . . . . . . 24
Re-installing the Lever Assembly . . . . . . . . . . . . 24
Parts Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Repair Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Type 2390 and 2390B Liquid Level
Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
249 Series Sensor Insulator Assembly . . . . . . . . 30
Product Description
Specifications
Type 2390 and 2390B Transmitters
Specifications for a Type 2390 or 2390B transmitter
The Type 2390 or 2390B liquid level transmitter is are listed in table 1. Some specifications for an individ-
used with the 249 Series sensors to measure changes ual transmitter, as it comes from the factory, are found
in liquid level, the level of interface between two liq- on the nameplate (figure 2).
2
Type 2390 and 2390B
Table 1. Specifications
3
Type 2390 and 2390B
Table 1. Specifications (continued)
4
Type 2390 and 2390B
Installation
WARNING
5
Type 2390 and 2390B
A5497/IL
2N10065-L
A3544-2/il
Transmitter Orientation
Note
Mount the transmitter with the vent opening pointing
Caged sensors have a rod and block downward to allow accumulated moisture drainage.
installed on each end of the displacer to The transmitter and torque tube arm are attached to
protect the displacer in shipping. Re- the displacer in either a right- or left-hand mounting
move these parts before installing the style, as shown in figure 8. This can be changed in the
sensor to allow the displacer to function field on the 249 Series sensors (refer to the appropri-
properly. ate sensor instruction manual). Changing the mount-
6
Type 2390 and 2390B
17A8552-A
B1874-1/IL
17A8552-A
B1875-1/IL
7
Type 2390 and 2390B
LEVER ASSEMBLY ALIGNMENT 3. Position the transmitter so the vent plug is on the
ADJUSTMENT
bottom of the transmitter.
Mounting the Transmitter on a 249 2. Remove the vent plug (figure 9) and loosen the
Series Sensor shaft clamp with the hex nut driver inserted through
the vent plug hole.
Key numbers are referenced in figure 21 or 22 except
where otherwise indicated. 3. Remove the hex nuts (key 62, figure 21 or 22) from
the mounting studs (key 61, figure 21 or 22).
1. Remove the vent plug (figure 9) and loosen the
shaft clamp (figure 9) with a hex nut driver inserted 4. Position the insulator (key 35) on the transmitter,
through the vent plug hole. sliding the insulator straight over the mounting studs.
8
Type 2390 and 2390B
MN28800
20A7423-C
B2707 / IL
SENSOR TRANSMITTER
9
Type 2390 and 2390B
FIELD WIRING COMPARTMENT P 1
GND
+
+ 24 V DC
POWER
- SUPPLY
+ LOAD - -
2
SAFETY EARTH
GROUND GROUND
P
FIELD WIRING COMPARTMENT 1
+
+ 24 V DC
POWER
2 - SUPPLY
+ LOAD - -
2
TYPE 2390B LCIE (CENELEC) FLAMEPROOF TRANSMITTERS
NOTES:
1 CABLE IS NO. 14 TO 18 AWG (2.08 TO 0.82 mm2), SHIELDED, TWISTED PAIR WITH DRAIN WIRE.
B1983-1/IL 2 REFER TO NATIONAL AND LOCAL CODES FOR APPROPRIATE GROUNDING REQUIREMENTS.
2. Bring the field wiring into the transmitter via one of 4. Connect the safety ground (seal the conduit open-
the two threaded openings. Rigid metal conduit is rec- ing) and the earth ground as shown in figure 12. Re-
ommended. Be sure to follow all local installation place and hand tighten the cover to the housing. When
codes and approvals. the loop is ready for startup, apply power to the power
supply.
3. Connect the wire from the positive power supply
terminal to the positive screw terminal on the terminal
block in the field wiring compartment. Connect the
positive load connection to the negative screw terminal Calibration
in the field wiring compartment as shown in figure 12.
Connect the wire from the negative power supply ter- Precalibration Considerations
minal to the negative load terminal to complete the
loop. A Type 2390 or 2390B transmitter must be matched to
a specific Type 249 sensor and then calibrated with
that sensor to a specific process requirement. Thus,
before a transmitter and sensor combination can be
WARNING installed for use, matching and calibration must be
performed.
The matching procedure records the displacer/torque
Personal injury or property damage can tube rotational span on the transmitter dry span scale.
result from the discharge of static elec- The scale is calibrated so that 0 to 100% represents
tricity. Connect a 14 AWG (2.08 mm2) the nominal design span of 4.4 degrees. The sensitiv-
ground strap between the transmitter ity of the system varies due to the wide assortment
and earth ground when flammable or and tolerances of torque tubes and displacer volumes.
hazardous gases are present. Refer to For standard combinations using water at 70"F (21"C)
national and local codes and standards as the measured liquid, the value of the sensitivity will
for grounding requirements. fall between 85 and 100%.
10
Type 2390 and 2390B
Matching is done at the factory, using water with a ing the actual process. The various compensations for
specific gravity of 1, for transmitter/sensor combina- specific gravity and temperature are accounted for in
tions that are ordered together. Matching must be the calculation of calibration weights.
done in the field when: Once the instrument is matched to the sensor using
one of the two methods, you can use the Dry Span
! the transmitter is ordered separately from the Scale system to rerange the instrument (change the
sensor, zero and span). This method artificially drives the me-
chanical input to the computed set points relative to
! the transmitter is replaced in the field, the nominal calibration supplied by the Wet Calibration
or Calibration by Weights methods. Therefore, dry cal-
! any time the sensor or sensor parts (torque tube ibration can be performed only after the instrument
or displacer) are replaced, or has been matched to the sensor.
11
Type 2390 and 2390B
SPAN RED SHIPPING SCREW
POTENTIOMETER
ADJUSTMENT SHAFT SCALE
INDICATOR
ZERO
POTENTIOMETER SPRING WIRE
ADJUSTMENT SHAFT
HOLDING
POSITION (USE ONLY WHEN
DRY SPAN
INSTALLING SHIPPING
KNOB
SCREW)
POINTER
VENT PLUG
CALIBRATION DOOR
SHIPPING
SCREW CLIP CALIBRATION
DOOR SCREW
W5073-2/IL
CAUTION
7. Set the dry span scale in the center of its slip range
Figure 14. Transmitter Calibration Setup as follows:
a. Loosen the set screw in the dry span knob.
4. Verify that plug P2 is in the correct position for di-
rect or reverse action as appropriate (figure 7). b. Hold the dry span knob so that it can’t rotate.
12
Type 2390 and 2390B
2. Set the displacer to the lowest possible process 10. Loosen the torque tube shaft clamp nut.
condition, (i.e. lowest water level or minimum specific
gravity, highest temperature) or replace the displacer 11. Move the spring wire to the R holding position.
by the heaviest calibration weight.
12. Determine a new coupling position from the
following:
Note
New coupling % = (−1) (dry span scale reading in step
Interface or density applications with 9)
displacer/torque tube sized for a small
total change in specific gravity are de-
Example: X% = (–1) (–10)
signed to be operated with the displacer
X% = +10
always submerged. In these applica-
tions, the torque rod is sometimes rest-
ing on a stop while the displacer is dry. Example: X% = (–1) (+7)
The torque tube does not begin to move X% = –7
until a considerable amount of liquid
has covered the displacer. In this case, 13. Move the dry span knob to the new coupling
it is necessary to couple with the displa- position.
cer submerged in the fluid with the low-
est density and the highest process 14. Retighten the torque tube shaft clamp nut.
temperature condition, or to an equiva-
lent condition simulated with the calcu- 15. Return the spring wire to the neutral (center)
lated weights, position.
The spring wire must be in the neutral ! For direct action: adjust the output current to
(center) position for operation in the au- 4 mA
tomatic mode.
! For reverse action: adjust the output current to
6. Turn the dry span knob to the AUTO position. 20 mA
7. Use the zero potentiometer (marked “Z”) to adjust 18. Slowly turn the dry span knob until the output cur-
the output current as follows: rent reading barely begins to move off the zero value.
13
Type 2390 and 2390B
19. Loosen the scale set screw. 2. Turn the dry span knob until the current output is
20 mA for direct action or 4 mA for reverse action.
3. Mark this position on the scale with a felt tip pen
Note and record the scale reading of the mark on a calibra-
Firmly hold onto the dry span knob tion sticker inside the dry span door. (This marked
while turning the scale. span position is used later in calibrating to specific ap-
plication requirements).
20. Slip the scale to indicate 0 percent without moving 4. Turn the dry span knob counterclockwise to the
the dry span knob. If you cannot get the scale to the AUTO position.
appropriate mark, loosen the dry span knob set screw, 5. Move the spring wire to the neutral (center)
re-center the scale, hand tighten the set screw, and position.
return to step 9).
21. Hand Tighten the scale set screw. Securing the Unit for Shipment or Placing
the Unit In Service
22. Return the dry span knob to the AUTO position. 1. If the system is to be moved without blocking the
displacer before being placed in service (as in skid
mounted systems), perform the following:
Zero and Span Adjustment
1. Depending on the transmitter action, perform one a. Uncouple the transmitter from the torque tube
or the other of the following: and install the shipping screw. (The spring wire
may be hooked in the “L” position to facilitate en-
! For direct action: move the displacer to the low- gaging the shipping screw in the lever assembly
est position (i.e., lowest water level or minimum specif- threads.)
ic gravity, highest process temperature) or replace the
displacer by the heaviest calibration weight. b. Tag the calibration door with the appropriate
warning and indicate that the transmitter will need
! For Reverse Action: move the displacer to the to be re-coupled before placing in service. (When
desired highest position (i.e., highest water level or re-coupling, the dry span scale mark will still be
maximum specific gravity, lowest process tempera- correct after the zero is aligned with the dry displa-
ture) or replace the displacer by the lightest calibration cer condition.)
weight. 2. If the system is being placed in service, or is being
2. Adjust the output current to 4 mA with the zero moved with the displacer blocked, the shipping screw
potentiometer. should be stored in the holding clip inside the door.
3. Depending on the transmitter action, perform one 3. Close the calibration door and tighten the door
or the other of the following: screw.
4. Turn the zero and span potentiometer adjustment
! For Direct Action: move the displacer to the cover back over the potentiometer adjustment screws
highest position (i.e., highest water level or maximum and tighten the cover screw.
specific gravity, lowest process temperature) or re-
place the displacer by the lightest calibration weight.
Determining Suspended Weight for
! For Reverse Action: move the displacer to the Calibration
lowest position (i.e., lowest water level or minimum
specific gravity, highest process temperature) or re- CAUTION
place the displacer by the heaviest calibration weight.
4. Adjust the output current to 20 mA with the span To avoid overloading a torque tube
potentiometer. sized for interface or density applica-
5. Repeat steps 1 and 3 to verify calibration and trim tions under dry conditions, consult your
values if necessary. Fisher sales office or sales representa-
tive for the maximum allowable substi-
tute weight Ws that can be used with
Recording the Sensor Span your particular construction.
1. To record the sensor output span on the dry span
scale, first move the spring wire to the R holding posi- To determine the total weight that must be suspended
tion. from the displacer rod to simulate a certain condition
14
Type 2390 and 2390B
of process temperature, fluid level or specific gravity, where:
solve the following equation:
V = Volume of the displacer, in cubic inches (cu-
"W d # $%# w&(V s)(SG)'( bic centimeters). '(/4 (displacer diameter)2 x
Ws ! (length of displacer submerged)]
[1 # $(%T)]
hl = Relative length of displacer that is immersed
where: in the lighter fluid. [(length of the displacer
immersed in lighter fluid)/(length of the displa-
Ws = Total suspended weight in pounds (kilo- cer)]
grams) [should never be less than 0.5 lbs
(0.227 kg)]. SGl = Specific gravity of the lighter fluid at operat-
ing temperature.
SG = Specific gravity of the process fluid at oper- 1. Loosen the screw on the calibration door and open
ating temperature. the door.
For interface level measurement, the equation be- 2. If the red shipping screw is installed (clamping the
comes: lever assembly) in the housing wall, remove it and
stow it in the clip on the door. The transmitter is most
"W d # %# w&(V)[(h l)(SG l) ) (h h)(SG h)]( likely uncoupled from the torque tube. In this case,
Ws ! perform the Coupling steps of the Matching the Trans-
[1 # $(%T)] mitter to a 249 Series Sensor procedure before pro-
15
Type 2390 and 2390B
ceeding. To confirm that the unit is coupled, observe the torque tube when using water at ambi-
that the spring wire moves as the displacer is lifted ent conditions as the process fluid)
8. Depending on the transmitter action, perform one
or the other of the following:
Note
Place the shipping screw in the clip pro- ! For direct action, turn the dry span knob to 0
vided in the calibration door for re- percent on the appropriate scale.
installation after completing the calibra-
! For reverse action, turn the dry span knob to
tion procedures if the unit is to be
the calculated 100% scale setting on the appropriate
moved. scale.
3. Connect the transmitter to the test equipment per 9. Adjust the zero potentiometer until the output cur-
the calibration setup (figure 14) and turn on the power rent is 4 mA.
supply and the DVM. 10. Depending on the transmitter action, perform one
or the other of the following:
4. Move the spring wire to the R holding position.
! For direct action, turn the dry span knob to the
5. Loosen the screw on the zero and span potentiom- calculated 100% scale setting on the appropriate
eter adjustment cover plate and turn the cover plate to scale.
expose the adjustments.
! For reverse action, turn the dry span knob to 0
percent on the appropriate scale.
Note
11. Adjust the span potentiometer until the output cur-
The span control pivots the output rent is 20 mA.
transfer characteristic around the 4 mA 12. Proceed to step 13.
output point. For this reason, the 4 mA
output point is adjusted first with the Dry Calibration for Interface Level or Density
zero control, for both direct and reverse Measurement Applications (Steps 7 through 12)
action.
7. If the transmitter was initially coupled at dry displa-
6. Steps 7 through 12 of this procedure are broken cer condition and marked with SG = 1.0, compute the
into two parts, one for level applications and one for 0% and 100% dry span scale settings for the dry span
interface level or density measurement. Perform one scale as follows:
or the other of steps 7 through 12 depending upon the
application 0% scale setting = (SGmin) x (PBwater)
Dry Calibration for Level Applications (Steps 7 100% scale setting = (SGmax) x (PBwater)
through 12)
where:
7. Determine the calculated dry span scale setting
(PBprocess) required for 100% level calibration point by SGmin = lowest specific gravity for density or specif-
using the following formula: ic gravity of top phase for interface.
PBprocess = (SGprocess) x (PBwater)
SGmax = highest specific gravity for density or spe-
where: cific gravity of bottom phase for interface
SGprocess = specific gravity of process fluid PBwater = recorded or marked dry span scale value
from the wet calibration procedure (equiv-
PBwater = recorded or marked dry span scale value alent to the mechanical proportional band
from the wet calibration procedure (equiva- of the torque tube when using water at
lent to the mechanical proportional band of ambient conditions as the process fluid)
16
Type 2390 and 2390B
Note
! For direct action, turn the dry span knob to 0% 15. Remove the test equipment.
on the appropriate scale.
16. Close the calibration door and tighten the door
! For reverse action, turn the dry span knob to screw.
the calculated 100% scale setting on the appropriate
scale. 17. Turn the zero and span potentiometer adjustment
cover back over the adjustment shafts and tighten the
9. Adjust the zero potentiometer until the output cur- machine screw.
rent is 4 mA.
10. Depending on the transmitter action, perform one
or the other of the following:
! For direct action, turn the dry span knob to the Principle of Operation
calculated 100% scale setting on the appropriate
scale. A level, density, or interface level change in the mea-
sured fluid causes a change in the displacer position
! For reverse action, turn the dry span knob to (figure 15). This change is transferred to the torque
0% on the appropriate scale. tube assembly. As the measured fluid changes, the
torque tube assembly rotates up to 4.4 degrees for a
11. Adjust the span potentiometer until the output cur- 249 Series sensor, varying the transmitter output be-
rent is 20 mA. tween 4 and 20 mA. This conversion is described in
12. Proceed to step 13. the following paragraphs and shown in the block dia-
gram (figure 16).
Dry Calibration Continued (Steps 13 through 17)
The rotary motion is transferred to the transmitter le-
13. Move the spring wire to the neutral (center) ver assembly (via a bellows) supported by flexure
position. strips. The rotary motion moves a magnet attached to
the lever assembly, changing the magnetic field that is
sensed by the Hall-effect position sensor. The sensor
Note then converts the magnetic field signal to an electronic
signal.
The spring wire must be in the neutral
(center) position for operation in the au- The electronic signal is ambient-temperature-compen-
tomatic mode. sated and amplified by the differential amplifier. The
signal is then linearized to compensate for the nonlin-
14. Turn the dry span scale to the AUTO position. earity of the magnetic field. The first and second-order
17
Type 2390 and 2390B
SK588
B1842-1/IL
Figure 16. Block Diagram of Type 2390 and 2390B Transmitter Operation
low pass filters dampen the effects of process turbu- properly set up transmitter can be the source of the
lence and prevent saturation of the dc amplifier and problem. If recalibrating does not clear up the problem,
the current driver. The dc amplifier provides noninter- proceed with this section.
acting zero and span adjustments.
Key numbers are shown in figure 21 or 22 unless
The current driver circuit develops a 4 to 20 mA cur- otherwise indicated.
rent output signal proportional to the dc amplifier volt-
age output. The voltage regulator provides stable sup- 1. Isolate the problem to the sensor or transmitter.
ply voltages for the transmitter circuits under varying Set up the transmitter as if to do the calibration proce-
operating conditions. dure shown in figure 14. Then slowly move the dis-
placer up and down by changing the liquid level. The
Circuits within the transmitter provide reverse polarity output should follow the change in liquid level.
protection, transient power surge protection, and elec-
tromagnetic interference (EMI) protection. 2. If there is no change in output in step 1, open the
calibration door (key 4) and carefully observe the
movement of the spring wire on the lever assembly
(figure 9) while changing the liquid level. If movement
cannot be detected:
Maintenance a. Remove the vent plug (figure 9) and loosen the
shaft clamp (figure 9) on the lever assembly (key
WARNING 12) with the hex nut driver inserted through the
vent plug hole.
To avoid personal injury due to fire or b. Manually move the spring wire (figure 13) up
explosion, remove electrical power be- and down and observe the output. If there is no
fore removing the transmitter in a haz- output or an abnormal output is observed the mal-
ardous area. Do not apply power to the function is in the transmitter. Further troubleshoot-
transmitter, with the covers removed, ing of the transmitter can be done by following table
while in a hazardous area. 4 and figure 17, or the transmitter can be returned
to the factory for repair. If a 0 to 100 percent output
can be obtained by moving the spring wire, the
Troubleshooting transmitter is functional and the problem lies with
either the torque tube shaft coupling or the displac-
Prior to reading the following text, go through the cal- er of the sensor. Consult the appropriate Type 249
ibration section and check the items as described in sensor instruction manual for further instructions on
the Precalibration Considerations procedure. An im- the sensor.
18
3N10061-G/IL
19
Type 2390 and 2390B
Type 2390 and 2390B
Table 4. Troubleshooting Guide
Symptom Possible Cause Check Corrective Action
1. No output Incorrectly wired Wiring Wire correctly
2. Output is below 3.2 mA dc Incorrect supply voltage or Voltage at field terminals should be Check power supply voltage
excessive field wiring resistance between 11 and 45 and total field wiring resistance
volts dc against figure 3.
Sensor assembly failure Sensor assembly by performing Replace sensor assembly
the Checking Transmitter Sensor
Assembly procedure
3. Output is constant at 3.2 or Sensor assembly failure Sensor assembly by performing Replace sensor assembly
30 mA dc the Checking Transmitter Sensor
Assembly procedure
Open zero or span potentiometer Confirm resistance for zero and Replace potentiometers or
or wiring harness span potentiometers (20K ohms), repair wiring harness
continuity, solder joints, and
connector crimps of harness
4. Lever assembly magnet Sensor assembly failure Sensor assembly by performing Replace sensor assembly
movement across Hall sensor does the Checking Transmitter Sensor
not change output signal Assembly procedure
Printed wiring board failure Sensor assembly checks OK and Replace printed wiring board
magnet has not been
demagnetized.
5. Output drifting or erratic Printed wiring board failure or Replace parts successively to Replace faulty part
on bench at constant temperature sensor failure isolate problem
After any disconnection or troubleshooting, recalibrate 7. Observe the output of the sensor on the DVM while
the transmitter using the Matching the Transmitter to a slowly rotating the dry span knob from 0 to 100 per-
249 Series Sensor procedure before putting it back cent on the R scale. The DVM reading should be pro-
into operation. portional to rotation, as follows:
20
Type 2390 and 2390B
ohms, replace the sensor assembly. If the resistance with the hex nut driver inserted through the vent plug
is within specifications, proceed to step 12. hole.
12. Connect a milliammeter between pins 1(+) 2. Turn the dry span scale to the auto position and
and 2(−) on the printed wiring board connector J1. move the spring wire to the L position to make re-
installing the shipping screw easier.
13. Turn the power supply on.
14. The current should be between 2.08 and 2.12 mA 3. Re-install the red shipping screw (key 57) that was
at 70"F (21"C). [If measured at −40"F (−40"C), the removed in the “Installation” or “Calibration” section.
current should be approximately 0.05 mA lower than
the 70"F (21"C) value. At +176"F (80"C), the current 4. Loosen and remove the hex nuts (key 62) from the
should be approximately 0.05 mA higher than the mounting studs (key 61).
70"F (21"C) value.]
15. If the current meets specification but the sensor 5. Carefully pull the transmitter straight off the sensor
output is not within the ranges given in step 7 for torque tube.
100% span (4.4 degree rotation of the input shaft), the
sensor assembly sensitivity is non-standard and it 6. When re-installing the transmitter, follow the ap-
must be replaced. propriate procedure outlined in the “Installation” sec-
tion.
16. To replace the sensor, see Removing the Printed
Wiring Board Assembly and Removing and Re-Instal-
ling the Transmitter Sensor Assembly. 249 Series Sensor in High Temperature
Application
Key numbers are shown in figure 10 except where
Checking the Analog Output Meter
otherwise indicated.
The analog output meter resistance should be approxi-
mately 3.5 ohms. 1. Remove the vent plug (figure 9) and loosen the
shaft clamp (figure 9) on the lever assembly (key 12,
figure 21 or 22) with the hex nut driver inserted
through the vent plug hole.
Removing the Transmitter from a 249 2. Turn the dry span scale to the auto position and
Series Sensor move the spring wire to the L position to make re-
installing the shipping screw easier.
21
Type 2390 and 2390B
Printed Wiring Board Compartment Removing and Re-installing the
Parts Removal and Replacement Transmitter Hall-Effect Sensor Assembly
1. Remove the two machine screws (key 167).
CAUTION 2. Slide the sensor assembly (key 11) out of the hous-
ing (key 1).
Electrostatic voltages present in the 3. To re-install, slide the O-ring (key 10) over the sen-
field environment and transferred to the sor assembly.
printed wiring board can cause failure
or degraded performance. Use appropri- 4. Slide the Hall-effect sensor assembly into the
ate antistatic procedures any time the housing.
printed wiring board housing cover is 5. Insert the two screws (key 167) and alternately
removed. tighten.
3. Unscrew the two machine screws (key 18). Re-installing a Printed Wiring Board
Assembly
4. Disconnect connector plug P5 from board connec-
tion J5 (figure 7). CAUTION
5. Remove the entire output meter assembly (key 16) To avoid damaging wiring that can inter-
from the housing (key 1). rupt transmitter operation when the ana-
log output meter and printed wiring
board are installed, verify that wires are
Removing the Printed Wiring Board routed around the posts and through
Assembly the notch in the printed wiring board as
shown in figure 18.
1. Disconnect connector plugs P1, P2, P3, P4, P6, 1. Route the Hall-effect sensor wires as shown in
and P7 from board connections J1, J2 or J2.1, J3, J4, figure 18.
J6, and J7 respectively (figure 7).
2. Insert the printed wiring board assembly (key 64)
2. Remove the three machine screws (key 20). into the housing (key 1).
3. Tighten the three machine screws (key 21).
3. Carefully remove the printed wiring board (key 64)
from the housing (key 1). 4. Reconnect connector plugs P1, P2, P3, P4, P6,
and P7 to board connections J1, J2 or J2.l, J3, J4, J6,
and J7 respectively as identified in figure 7.
Removing a Potentiometer Assembly
1. Loosen the hex nut on the potentiometer assembly
Re-installing the Analog Output Meter
until the threads are disengaged.
CAUTION
2. Pull the potentiometer (key 27 or 28) and shaft cou-
pling (key 25) slowly and carefully off of the potentiom- To avoid damaging wiring that can inter-
eter shaft extension (key 22) with a twisting motion. rupt transmitter operation, verify that
22
Type 2390 and 2390B
WIRES MUST NOT CROSS THIS EDGE OF SENSOR FLANGE 2. Remove the two funnel plate machine screws
AMPLIFIER
PWB
TO PREVENT CUTTING WHEN METER IS INSTALLED (key 19) and funnel plate (key 45).
ANALOG METER
LOCATION 3. Loosen and remove the red shipping screw
POST (key 57) if installed.
RED &
BLUE GREEN & Note
WIRES YELLOW
WIRES Place the shipping screw in the clip pro-
SENSOR
ASSEMBLY vided on the calibration door for re-
installation after completing the calibra-
17B0679-A / DOC
tion procedures if the unit is to be
moved.
Figure 18. Hall-Effect Sensor Wire Routing
4. Loosen and remove the two cap screws (key 20).
3. Position the aperture (key 17) over the meter, Remove the lever assembly as described in the pre-
insert the machine screws (key 18) through the apera- vious procedure.
ture and output meter mounting holes and tighten
snugly. 1. Position the alignment tool as shown in figure 19,
step 1.
4. Screw the printed wiring board housing cover
(key 222) snugly onto the housing (key 1). 2. Insert the alignment tool guides into the holes on
the bracket assembly as shown in figure 19, step 2.
Key numbers are shown in figure 21 or 22 except Hold the alignment tool firmly when re-
where otherwise indicated. placing flexure strips to prevent pos-
sible bending or stressing that could
cause inaccurate operation.
Removing the Lever Assembly
4. Carefully position the new flexure strips and then
1. Remove the nuts (key 62) and slide the adapter insert the washers, plates and cap screws. Lightly
ring (key 3) off the housing and mounting studs snug the cap screws to hold the flexure strips in posi-
(keys 1 and 61). tion.
23
Type 2390 and 2390B
FLEXURE
STRIP
FLEXURE
STRIP
CAP SCREWS
WASHER
STRIP
ALIGNMENT
TOOL
NOTE:
MAINTAIN CONSTANT PRESSURE ON ALIGNMENT TOOL AND
LEVER ASSEMBLY DURING REMOVAL AND REINSTALLATION.
W5605/IL W5604/IL
5. Tighten the cap screws at the solid end of the flex- Re-installing the Dry Span Scale
ure, then alternately tighten all the cap screws to
9 lbf#in (1 N#m). 1. Put the dry span scale over the shaft with the
proper scale orientation (figure 20).
6. Remove the alignment tool. 2. Put the pointer over the shaft and screw the knob
clockwise loosely onto the cam disk assembly shaft.
Removing the Dry Span Scale 3. Put a 9/32 inch (7 mm) wrench on the shaft nut and
hold firmly. The scale can also be assembled by in-
Key numbers are shown in figure 21 or 22 except serting a small rod through the aligned hole in the dial
where otherwise indicated. and housing.
1. Loosen the door screw on the calibration door 4. Tighten the dry span knob.
(figure 13) and open the door.
5. Set the dry span scale to its middle position
2. Loosen the scale set screw (figure 13) on the dry (figure 20) in reference to the scale adjustment stop.
span knob with a screwdriver.
6. Tighten the scale set screw on the dry span knob
with a screwdriver.
3. Put a 9/32 inch or a 7 mm wrench on the cam disk
assembly shaft nut (key 46) and hold firmly. The scale
can also be removed by inserting a small rod through Re-installing the Lever Assembly
the aligned hole in the dial and housing. Key numbers are shown in figure 21 or 22 except
where otherwise indicated.
4. Turn the dry span knob counterclockwise and re-
move the knob, pointer, and scale (keys 50, 49, 1. Insert the lever assembly (key 12) into its mounting
and 48) from the shaft. position.
24
Type 2390 and 2390B
DUAL SCALE SHOWN WITH KNOB AND POINTER IN PLACE DUAL SCALE SHOWN WITH KNOB AND
SPRING WIRE IS IN NEUTRAL (CENTER) POSITION POINTER REMOVED
2. Insert and tighten the two cap screws (key 20). 7. Turn the wrench to move the lever assembly until
the output is 0 (zero) !13 mVdc. Retighten the lever
assembly mounting screws.
3. Carefully move the lever assembly back and forth
over the sensor assembly (key 11). There should be
no touching or restriction of free travel. 8. Move the spring wire to the R holding position
(figure 20).
12. Loosen the locking cap screw (key 92, figure 23)
Note with a 5/64 inch (2 mm) Allen wrench.
14. Tighten the locking cap screw (key 92, figure 23).
6. Loosen the cap screws (key 20) slightly and insert
an Allen wrench in the lever assembly adjustment
hole. 15. Return spring wire to the neutral (center) position.
25
Type 2390 and 2390B
Note Key Description Part Number
11* Sensor Assembly, stainless steel 1N10074 G022
To recheck, turn the scale to the AUTO 12* Lever Assembly, aluminum
position and confirm the 0 (zero) !13 Type 2390 (inch) 2N10086 X012
Type 2390B (metric) 2N10086 X022
mVdc (millivolts dc) Hall-effect sensor
output. If the output is 30 mVdc or 15 Set Screw, stainless steel (not shown)
greater, the flexure strips may be dam- Used with flameproof
aged and require replacement. The Type 2390B only, 1N10110 G012
transmitter should be in the mounting 16* Analog Output Meter Assembly, 4−20 mA 1N10111 G012
position with vent plug on the bottom. 17 Aperture (used with meter only), aluminum 1N10117 G012
18 Machine Screw (used with meter only)
16. Re-install the funnel plate. Stainless steel (2 req’d)
Type 2390 1N10313 G012
Type 2390B 1N10312 G012
17. Re-install the funnel plate screws and tighten. 19 Machine Screw, stainless steel
Type 2390 (3 req’d) 1N10183 G012
18. Slide the adapter ring onto the mounting studs. Type 2390B (4 req’d) 1N10364 G012
20 Cap Screw, stainless steel (2 req’d)
19. Re-install the transmitter according to the ap- Type 2390 1N10307 G012
propriate Installation procedures. Type 2390B 1N10306 G012
APPLY LUB/SEALANT
4N10228-M/ DOC
27
Type 2390 and 2390B
4N10059-R / DOC
28
Type 2390 and 2390B
APPLY EPOXY
2N10086-K / DOC VIEW A-A
30
Type 2390 and 2390B
29A5848-F/DOC
31
Type 2390 and 2390B
Fisher, Fisher-Rosemount, and Managing The Process Better are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
$Fisher Controls International, Inc. 1985, 1999; All Rights Reserved
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.