You are on page 1of 32

Instruction Manual

Form 5233
May 1999 Type 2390 and 2390B

Type 2390 and 2390B Liquid Level Transmitters


Contents
Introduction ...............................2
Scope of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Type 2390 and 2390B Transmitters . . . . . . . . . . . . 2
249 Series Sensors . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Test Equipment and Tools Required . . . 4 W4078/IL

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 TYPE 2390 OR 2390B LIQUID LEVEL TRANSMITTER


Pre-installation Requirements . . . . . . . . . . . . . . . . . . 6
Direct or Reverse Action Setup Verification . . . . . 6
Transmitter Orientation . . . . . . . . . . . . . . . . . . . . . . . 6
Mounting the Transmitter on a 249 Series
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Mounting the Transmitter for High Temperature
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 TYPE 2390 OR 2390B
LIQUID LEVEL TRANSMITTER
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Precalibration Considerations . . . . . . . . . . . . . . . . 10
Matching the Transmitter to a 249 Series
Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Zero and Span Adjustment . . . . . . . . . . . . . . . . . 14
Recording the Sensor Span . . . . . . . . . . . . . . . . 14
CAGED TYPE 249B SENSOR
Securing the Unit for Shipment or
Placing the Unit In Service . . . . . . . . . . . . . . . 14
Determining Suspended
Weight for Calibration . . . . . . . . . . . . . . . . . . . . 14 W4067-1*/IL

Dry Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 1. Type 2390 or 2390B Liquid Level Transmitter
Principle of Operation . . . . . . . . . . . . . . . . . . . . 17 and Typical Sensor
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Printed Wiring Board Compartment Parts
Checking Transmitter Hall-Effect Removal and Replacement . . . . . . . . . . . . . . . 22
Sensor Assembly . . . . . . . . . . . . . . . . . . . . . . . . 20 Removing the Analog Output Meter . . . . . . . . . . 22
Checking the Analog Output Meter . . . . . . . . . . . 21 Removing the Printed Wiring Board Assembly 22
Removing the Transmitter from a Removing a Potentiometer Assembly . . . . . . . . 22
249 Series Sensor . . . . . . . . . . . . . . . . . . . . . . . 21 Removing and Re-installing the Transmitter
249 Series Sensor in Standard Hall-Effect Sensor Assembly . . . . . . . . . . . . . 22
Temperature Application . . . . . . . . . . . . . . . . . 21 Re-installing a Potentiometer Assembly . . . . . . 22
249 Series Sensor in High Temperature Re-installing a Printed Wiring Board Assembly 22
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Re-installing the Analog Output Meter . . . . . . . . 22
D200364X012
Type 2390 and 2390B
Contents (Continued)
Sensor Connection Compartment Parts Removal
and Re-installation . . . . . . . . . . . . . . . . . . . . . . . 23
Removing the Lever Assembly . . . . . . . . . . . . . . 23
Removing and Replacing the Flexure Strips . . 23
Removing the Dry Span Scale . . . . . . . . . . . . . . 24
Re-installing the Dry Span Scale . . . . . . . . . . . . 24
Re-installing the Lever Assembly . . . . . . . . . . . . 24
Parts Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Repair Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Type 2390 and 2390B Liquid Level
Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
249 Series Sensor Insulator Assembly . . . . . . . . 30

Introduction Figure 2. Typical Nameplate

Scope of Manual uids, or the specific gravity (density) changes of a liq-


uid. These changes exert a buoyant force on the dis-
This instruction manual provides installation, calibra- placer, which rotates the torque tube shaft. This rotary
tion, maintenance, and parts ordering information for motion is applied to the transmitter, and the resulting
the Type 2390 and 2390B liquid level transmitters current output signal is sent to an indicating or final
used with the 249 Series level sensors. A typical control element.
transmitter-sensor combination is shown in figure 1.
A wide variety of 249 Series sensors are used with the
Refer to the Principle of Operation section for a more Type 2390 or 2390B transmitters.
comprehensive discussion of how the Type 2390 and
2390B liquid level transmitters operate.
249 Series Sensors
Only personnel qualified through training or experience ! The Type 249, 249B, 249BF, 249C, 249K, 249L,
should install, operate, and maintain this transmitter. If and 249N sensors side-mount on the vessel with the
there are any questions concerning these instructions displacer mounted inside a cage outside the vessel.
contact your Fisher Controls sales office or sales rep- (The Type 249BF is available only in Europe, Middle
resentative before proceeding. East, and Africa.) These sensors are called caged
sensors.
Note ! The Type 249BP, 249CP, and 249P sensors top-
This manual does not include sensor mount on the vessel with the displacer hanging down
installation instructions, maintenance into the vessel. These sensors are called cageless
instructions, or parts lists. For this in- sensors.
formation, refer to the appropriate sen-
! The Type 249V sensor side-mounts on the ves-
sor instruction manual.
sel with the displacer hanging out into the vessel
(cageless sensor).

Product Description
Specifications
Type 2390 and 2390B Transmitters
Specifications for a Type 2390 or 2390B transmitter
The Type 2390 or 2390B liquid level transmitter is are listed in table 1. Some specifications for an individ-
used with the 249 Series sensors to measure changes ual transmitter, as it comes from the factory, are found
in liquid level, the level of interface between two liq- on the nameplate (figure 2).

2
Type 2390 and 2390B
Table 1. Specifications

Transmitter Input Signal(1) CSA and SAA Certified or FM Approved Trans-


Liquid level, interface level, or density changes mitter (2390): 11 to 30 volts dc for intrinsically safe or
move the displacer up or down to provide rotary 11 to 30 volts dc for flameproof units
motion to the torque tube shaft LCIE or PTB (CENELEC) Approved Transmitter
(2390B): 11 to 32.5 volts dc for intrinsically safe
Transmitter Output Signal(1) (PTB) and 11 to 45 volts dc for flameproof (LCIE)
4 to 20 milliamperes (mA) dc (direct action—in- units
creasing input increases transmitter output; or re-
verse action—increasing input decreases transmit- Transmitter Span Adjustment
ter output) 10 to 100% of displacer length for level applications
using a standard volume displacer
Transmitter Performance (Transmitter Only)
(Specific Gravity of 1.0) Transmitter Zero Adjustment
Transmitter Output Reference Accuracy(1): 100% of displacer length
!0.5% of full scale output
Transmitter Environmental Protection
Hysteresis(1): !0.1% of full scale output
Enclosure Protection
Repeatability(1): !0.1% of full scale output
Type 2390: Meets NEMA 4X, CSA Type 4X, and
Dry Span Calibration: !2.5% of full scale at a spe-
IP65 ratings
cific gravity of 1.0
Type 2390B: Meets EN 60529 IP66 rating
Optional Analog Output Meter Accuracy: !2.5%
Complies with the European EMC directive
of full scale
Transient Power Surge Protection: No damage for
Frequency Response: A second order fit of the
a line-to-line power surge of up to 100 kilowatts for
combined torque tube and transmitter transfer func-
100 nanoseconds, or 1.5 kilowatts for 1 millisecond
tion is characterized by a natural frequency (!n) of
3 radians/second and a damping ratio (") of 0.9. Transmitter Hazardous Area Classification
The −3 dB point (90" phase shift) occurs between
Refer to the Hazardous Area Classifications bulle-
0.4 and 0.5 Hz.
tins for appropriate approvals
Transmitter Performance With 249 Series Sensor(2) Transmitter Weight
(Specific Gravity of 1.0, Standard Torque Tube)
7.7 pounds (3.5 kg)
Independent Linearity(1): !0.75% of full scale out-
put Standard Sensor Displacer Volumes
Hysteresis(1): 0.4% of full scale output Type 249C, 249CP Displacers: 60 cubic inches
(983 cm3)
Transmitter Operating Influences(1)
All Other Displacers: 100 cubic inches (1639 cm3)
Electromagnetic Interference (EMI)(1): With trans-
mitter covers on, product meets requirements of Minimum Sensor Differential Specific Gravity
SAMA standard PMC 33.1-1978; Class 3-abc out- 0.1 with standard volume displacers
put changes less than !0.5% of actual span when
operated in an electromagnetic field strength of 30 Mounting Positions
V/m [this is equivalent to a 5-watt, 20 to 1000 MHz Transmitter may be right or left hand mounted on
radio transmitter operating 19 inches (0.5 m) from sensor. All level sensors with cage displacers have a
the level transmitter] rotatable head. The head can be rotated through 360
Power Supply Effect: Output signal changes less degrees to any of eight different positions as shown in
than !0.002% of full scale output per 1.0 volt change figure 8
in power supply voltage between 11 and 45 volts dc
Caged Sensor Connection Styles
Transmitter Power Supply Requirements(3) Cages can be furnished in a variety of end connec-
Figure 3 tion styles to facilitate mounting on vessels; the
Standard Transmitter: 11 to 45 volts dc with re- equalizing connection styles are numbered and are
verse polarity protection shown in figure 4
−Continued−

3
Type 2390 and 2390B
Table 1. Specifications (continued)

Operating Limits Normal


Transport
Nominal
Conditions and Storage
Process Temperature: See table 3 and figure 11 Limits(1) Reference(1)
Limits(1)
Ambient Temperature and Humidity: See below Ambient – 40 to 176"F – 58 to 176"F 77"F
Temperature(1) (– 40 to 80"C) (– 50 to 80"C) (25"C)
Ambient
10 to 95% 10 to 95% 40%
Relative Humidity
1. These terms are defined in ISA Standard S51.1-1979.
2. Specific gravity of 1.0 on standard wall torque tube with full input change.
3. All versions have reverse polarity protection.

Table 2. Additional Tools Required


TOOL SIZE FOR TYPE
TOOL COMPONENT 2390 OR 2390B TRANSMITTER
Type 2390, Inches Type 2390B, mm
Hex nut driver Shaft clamp 11/32 7
Allen head wrench Shipping screw 9/64 3
Open-end wrench Cam disk assembly 9/32 7
Allen head wrench Heat insulator 5/64 2
Open-end wrench Mounting hex nuts 1/2 13
Open-end wrench Vent plug 15/16 24
Open-end wrench Eccentric pin 3/16 5
Allen head wrench Flexure screws 3/32 2.5
Allen head wrench Lever assembly adjustment 9/64 3
Allen head wrench Eccentric pin lock 5/64 2
Allen head wrench Cover, CENELEC flameproof 5/64 2

Table 3. Allowable Process Temperatures for Common 249


1700 FOR A 4−20
Sensor Component Materials MILLIAMPERE
CIRCUIT,
Process Temperature MAXIMUM
Material 1450
Min. Max. ALLOWABLE
LOAD
LOAD RESISTANCE, OHMS

Cast Iron −20"F (−29"C) 450"F (232"C) 1250 RESISTANCE IS


1700 OHMS
Steel −20"F (−29"C) 800"F (427"C)
1000
Stainless Steel −325"F (−198"C) 800"F (427"C)
N05500 (K-Monel) −325"F (−198"C) 700"F (371"C) 750
Graphite Laminate/SST CSA CERTIFIED OR
−325"F (−198"C) 800"F (427"C) FM APPROVED
Gaskets TRANSMITTERS
500
INTRINSICALLY-
Monel/PTFE Gaskets −100"F (−73"C) 400"F (204"C) SAFE AND
FLAME-PROOF
250
STANDARD AND
LCIE (CENELEC)
0 FLAME-PROOF
10 15 20 25 30 35 40 45 TRANSMITTERS
11 32.5
Test Equipment and Tools Required POWER SUPPLY VOLTAGE, V dc
PTB (CENELEC)
INTRINSICALLY-SAFE
A3542-2 / IL APPROVED TRANSMITTERS
The following equipment is required for installation, Figure 3. Power Supply Requirements and Load Resistance
calibration, and maintenance of the Type 2390 and
2390B liquid level transmitters.
! Optionally, a 250 ohm, !0.1 percent, 1/2-watt
! Power supply capable of supplying up to 24 volts resistor may be used for converting the 4−20 mA
dc in series with a load. transmitter signals to 1–5 volts dc for voltage mea-
surements.
! A 4-digit digital voltmeter (DVM), with an imped-
ance of at least 250,000 ohms, that measures volt- ! General-purpose multimeter with an input imped-
ages in the range of 0 to 10 volts dc with an accuracy ance greater than 30,000 ohms per volt.
of !1 millivolt, and currents in the range of 0 to 50 mA
dc with an accuracy of !0.01 mA. ! An alignment tool (part number 1N10323 G012).

4
Type 2390 and 2390B

STYLE 1 STYLE 2 STYLE 3 STYLE 4


TOP AND BOTTOM CONNECTIONS, TOP AND LOWER SIDE CONNECTIONS, UPPER AND LOWER SIDE CONNECTIONS, UPPER SIDE AND BOTTOM CONNECTIONS,
SCREWED (S-1) OR FLANGED (F-1) SCREWED (S-2) OR FLANGED (F-2) SCREWED (S-3) OR FLANGED (F-3) SCREWED (S-4) OR FLANGED (F-4)
27A0973-A
B1820-1 / IL

Figure 4. Style Number of Equalizing Connections

! Refer to table 2 for additional tools required.

Refer to Repair Kits under Parts List in this instruction


manual for a tool kit for the Type 2390 transmitter.

Installation

WARNING

Personal injury or property damage due


to sudden release of pressure, contact
with hazardous fluid, fire, or explosion
can be caused by puncturing, heating,
or repairing a displacer that is retaining
process pressure or fluid. This danger
may not be readily apparent when disas-
sembling the sensor or removing the
displacer. Before disassembling the
sensor or removing the displacer, ob- A3789/IL

serve the appropriate warnings provided


in the sensor instruction manual. Figure 5. Typical Caged Sensor Mounting

The Type 249 sensor is mounted using one of two


methods, depending on the specific type of sensor. If The Type 2390 or 2390B transmitter is typically
the sensor has a caged displacer, it typically mounts shipped attached to the sensor. If ordered separately,
on the side of the vessel as shown in figure 5. If the it may be convenient to mount the transmitter to the
sensor has a cageless displacer, the sensor mounts sensor and perform the matching and initial calibration
on the side or top of the vessel as shown in figure 6. before installing the sensor on the vessel.

5
Type 2390 and 2390B

A5497/IL

2N10065-L
A3544-2/il

Figure 7. Printed Wiring Board Connections

Check that you have received the proper Hazardous


Area Approval rating on the transmitter. The name-
plate on the transmitter (figure 2) specifies the approv-
al agency (if required) for the transmitter.

Direct or Reverse Action Set-Up


Verification
Before installing the transmitter, determine that the
instrument is set up properly for direct or reverse ac-
tion. Direct action (increasing level produces an in-
creasing output) or reverse action (increasing level
produces a decreasing output) is set up as shown in
figure 7, depending on whether the sensor is right- or
left-hand mounted. If your transmitter is set up incor-
rectly, refer to the table in figure 7 before proceeding
with the installation. When changing action, the plug
must be rotated 180 degrees to insert it in the other
A3788/IL
socket. (The wires from the plug exit toward the top of
Figure 6. Typical Cageless Sensor Mounting the transmitter when in J2 and toward the bottom
when in J2.1, in order to engage the locking tangs on
the connectors.) On units with an output indicator, the
indicator mounting screws may have to be loosened to
Pre-installation Requirements allow easy access to the J2.1 socket.

Transmitter Orientation
Note
Mount the transmitter with the vent opening pointing
Caged sensors have a rod and block downward to allow accumulated moisture drainage.
installed on each end of the displacer to The transmitter and torque tube arm are attached to
protect the displacer in shipping. Re- the displacer in either a right- or left-hand mounting
move these parts before installing the style, as shown in figure 8. This can be changed in the
sensor to allow the displacer to function field on the 249 Series sensors (refer to the appropri-
properly. ate sensor instruction manual). Changing the mount-

6
Type 2390 and 2390B

17A8552-A
B1874-1/IL

17A8552-A
B1875-1/IL

Figure 8. Head Mounting Positions for 249 Series Caged Sensor


with Rotatable Head (Top View)

7
Type 2390 and 2390B
LEVER ASSEMBLY ALIGNMENT 3. Position the transmitter so the vent plug is on the
ADJUSTMENT
bottom of the transmitter.

4. Carefully slide the mounting studs into the sensor


mounting holes until the transmitter is snug against the
sensor.

5. Reinstall the hex nuts on the mounting studs and


tighten the hex nuts to 88.5 lbf#in (10 N#m).

Mounting the Transmitter for High


Temperature Applications
CAM-DISK SHAFT CLAMP
ASSEMBLY
VENT PLUG
Key numbers are shown in figure 10 except where
ECCENTRIC PIN
ECCENTRIC PIN COVER LOCKING SCREW
otherwise indicated.
LOCKING CAP SCREW (FLAME-PROOF TYPE 2390B ONLY)
4N10233-D
A3543-4/IL The transmitter requires an insulator assembly when
Figure 9. Sensor Connection Compartment temperatures exceed the limits shown in figure 11.

A torque tube shaft extension is required for a 249 Se-


ing style also changes the effective action, because ries sensor when using an insulator assembly.
the torque tube rotation for increasing level, (looking at
the protruding shaft), is clockwise in a right hand
mounted unit and counterclockwise in a left hand
mounted unit. See table in Figure 7 for required config-
CAUTION
uration adjustment.
Measurement errors can occur if the
All caged 249 Series sensors have a rotatable head. sensor torque tube assembly is bent or
That is, the transmitter can be positioned at any of misaligned during installation.
eight alternate positions around the cage as indicated
by the position numbers 1 through 8 in figure 8. To 1. For mounting a transmitter on a 249 Series sensor,
rotate the head, remove the head flange bolts and secure the shaft extension (key 37) to the sensor
nuts and position the head as desired. torque tube shaft via the shaft coupling (key 36) and
set screws (key 38), with the coupling centered as
shown in figure 10.

Mounting the Transmitter on a 249 2. Remove the vent plug (figure 9) and loosen the
Series Sensor shaft clamp with the hex nut driver inserted through
the vent plug hole.
Key numbers are referenced in figure 21 or 22 except
where otherwise indicated. 3. Remove the hex nuts (key 62, figure 21 or 22) from
the mounting studs (key 61, figure 21 or 22).
1. Remove the vent plug (figure 9) and loosen the
shaft clamp (figure 9) with a hex nut driver inserted 4. Position the insulator (key 35) on the transmitter,
through the vent plug hole. sliding the insulator straight over the mounting studs.

5. Re-install the four hex nuts on the mounting studs


2. Remove the hex nuts (key 62) from the mounting
and tighten the nuts.
studs (key 61).
6. Carefully slide the transmitter with the attached in-
sulator over the shaft coupling so that the vent plug is
CAUTION on the bottom of the transmitter.

7. Secure the transmitter and insulator to the torque


Measurement errors can occur if the tube arm with four cap screws (key 39).
torque tube assembly is bent or misa-
ligned during installation. 8. Tighten the cap screws to 88.5 lbf#in (10 N#m).

8
Type 2390 and 2390B

MN28800
20A7423-C
B2707 / IL

SENSOR TRANSMITTER

Figure 10. Transmitter Mounting on Sensor in High Temperature Applications

tions are applicable to the Type 2390B


with LCIE approval of flameproof. If
AMBIENT TEMPERATURE ("C)
there is a possibility that the tempera-
PROCESS TEMPERATURE ( C)
PROCESS TEMPERATURE ( F)

−40 −30 −20 −10 0 10 20 30 40 50 60 70 80


"
800 425
400
" ture of the surface to which the trans-
HEAT INSULATOR
TOO
HOT 300 mitter is mounted will exceed 70"C, then
400
REQUIRED 200 the autoignition temperature of the at-
100 mosphere surrounding the transmitter
0 NO HEAT INSULATOR NECESSARY 0 must be at least 15"C greater than the
1 −100 surface temperature, but not less than
TOO HEAT INSULATOR
−200 85"C. For example, a surface tempera-
−325 COLD REQUIRED
−40 −20 0 20 40 60 80 100 120 140 160 176 ture of 75"C would require that the at-
AMBIENT TEMPERATURE ("F) mosphere have an autoignition tempera-
STANDARD TRANSMITTER ture of at least 90"C.
NOTES:
1 FOR PROCESS TEMPERATURES BELOW −20"F (−29"C) AND
ABOVE 400"F (204"C) SENSOR MATERIALS MUST BE
APPROPRIATE FOR THE PROCESS — SEE TABLE 3. Note
2. IF AMBIENT DEW POINT IS ABOVE PROCESS TEMPERATURE, ICE
39A4070-B
A5494-1/IL
FORMATION MIGHT CAUSE INSTRUMENT MALFUNCTION AND REDUCE
INSULATOR EFFECTIVENESS.
For intrinsically safe applications, refer
to the loop schematics at the end of this
Figure 11. Guidelines for Use of Optional manual or to instructions supplied by
Heat Insulator Assembly the barrier manufacturer.

The transmitter is normally powered by a 24-volt pow-


er supply in series with a load. Figure 12 shows typical
Wiring field wiring.

Wire the transmitter as follows:


WARNING
1. Remove the field wiring compartment cover (key
Personal injury or property damage can 38, figure 21 or 22) from the housing (key 1, figure 21
result if a suitable conduit seal is not or 22). This compartment has two threaded openings
installed. For explosion-proof applica- available for fittings.
tions, install the seal no more than 18
inches (457 mm) from the transmitter. Note
For European applications, the Type
2390B can be wired with a conduit entry
WARNING adapter or cable gland (key 42, figure
22). Figure 12 shows typical field wiring.
To avoid personal injury or property Be sure to follow all local codes and ap-
damage, the following special condi- provals.

9
Type 2390 and 2390B
FIELD WIRING COMPARTMENT P 1

GND
+
+ 24 V DC
POWER
- SUPPLY
+ LOAD - -

2
SAFETY EARTH
GROUND GROUND

TYPE 2390 STANDARD, FM APPROVED OR CSA CERTIFIED TRANSMITTERS

P
FIELD WIRING COMPARTMENT 1

+
+ 24 V DC
POWER
2 - SUPPLY
+ LOAD - -

2
TYPE 2390B LCIE (CENELEC) FLAMEPROOF TRANSMITTERS

NOTES:
1 CABLE IS NO. 14 TO 18 AWG (2.08 TO 0.82 mm2), SHIELDED, TWISTED PAIR WITH DRAIN WIRE.
B1983-1/IL 2 REFER TO NATIONAL AND LOCAL CODES FOR APPROPRIATE GROUNDING REQUIREMENTS.

Figure 12. Typical 2-Wire Analog Signal Conditioner Connections

2. Bring the field wiring into the transmitter via one of 4. Connect the safety ground (seal the conduit open-
the two threaded openings. Rigid metal conduit is rec- ing) and the earth ground as shown in figure 12. Re-
ommended. Be sure to follow all local installation place and hand tighten the cover to the housing. When
codes and approvals. the loop is ready for startup, apply power to the power
supply.
3. Connect the wire from the positive power supply
terminal to the positive screw terminal on the terminal
block in the field wiring compartment. Connect the
positive load connection to the negative screw terminal Calibration
in the field wiring compartment as shown in figure 12.
Connect the wire from the negative power supply ter- Precalibration Considerations
minal to the negative load terminal to complete the
loop. A Type 2390 or 2390B transmitter must be matched to
a specific Type 249 sensor and then calibrated with
that sensor to a specific process requirement. Thus,
before a transmitter and sensor combination can be
WARNING installed for use, matching and calibration must be
performed.
The matching procedure records the displacer/torque
Personal injury or property damage can tube rotational span on the transmitter dry span scale.
result from the discharge of static elec- The scale is calibrated so that 0 to 100% represents
tricity. Connect a 14 AWG (2.08 mm2) the nominal design span of 4.4 degrees. The sensitiv-
ground strap between the transmitter ity of the system varies due to the wide assortment
and earth ground when flammable or and tolerances of torque tubes and displacer volumes.
hazardous gases are present. Refer to For standard combinations using water at 70"F (21"C)
national and local codes and standards as the measured liquid, the value of the sensitivity will
for grounding requirements. fall between 85 and 100%.

10
Type 2390 and 2390B
Matching is done at the factory, using water with a ing the actual process. The various compensations for
specific gravity of 1, for transmitter/sensor combina- specific gravity and temperature are accounted for in
tions that are ordered together. Matching must be the calculation of calibration weights.
done in the field when: Once the instrument is matched to the sensor using
one of the two methods, you can use the Dry Span
! the transmitter is ordered separately from the Scale system to rerange the instrument (change the
sensor, zero and span). This method artificially drives the me-
chanical input to the computed set points relative to
! the transmitter is replaced in the field, the nominal calibration supplied by the Wet Calibration
or Calibration by Weights methods. Therefore, dry cal-
! any time the sensor or sensor parts (torque tube ibration can be performed only after the instrument
or displacer) are replaced, or has been matched to the sensor.

! any time the transmitter is disconnected from the


Note
torque tube.
A transmitter factory-mounted on a sen-
sor is already matched and does not re-
Note quire the matching procedure. The
If the transmitter is disconnected from matching is performed using water with
the torque tube, and none of the other a specific gravity of 1 or with appropri-
conditions listed occured, then only the ate weights, and the scale is marked at
coupling steps of the matching proce- full actual travel (span) and will be the
dure need to be performed. larger value on the appropriate scale.
One of two methods may be used to match the trans- Before starting the matching procedure, confirm that
mitter to the sensor:
the transmitter is correctly set up and installed on the
! Wet Calibration—this method calibrates the in- sensor as described in the “Installation” section.
strument by raising and lowering the fluid level while
the displacer is in the fluid. This is the most accurate
method. Matching the Transmitter to a 249 Series
Sensor
! Calibration by Weights—this method may be
used on the bench, the displacer is removed from the All locations in this procedure are referenced in figure
torque tube. Here, computed weights are used to sim- 13 unless otherwise indicated. The transmitter should
ulate the combined displacer weight and buoyant be installed on the torque tube arm, with the shaft
force. clamp (figure 9) loose.
If possible, the system should be coupled and cali-
brated with the process fluids at the process tempera- Setup
ture. When this is impractical or unsafe, various
means may be employed to simulate actual process 1. Loosen the door screw on the calibration door and
conditions. open the door.
If the process temperature is close to ambient condi- 2. Remove the red shipping screw.
tions, simply suspend the displacer to appropriate
depths in a liquid having a specific gravity equal to that
of the process liquid. For a caged sensor, the liquid Note
used can be poured into the cage. If necessary, water
can be used for matching in the shop. If water is used, Place the shipping screw in the clip pro-
compensation must be made for the difference be- vided in the calibration door for rein-
tween the specific gravity of water and that of the pro- stallation after completing the calibra-
cess liquid by scaling the levels used by the fluid spe- tion procedures if the unit is to be
cific gravity. moved.
If the process temperature will be considerably differ-
ent than the calibration temperature, the variation in 3. Connect the transmitter to the test equipment per
torque tube spring rate with temperature must also be the calibration setup (figure 14) and turn on the power
considered. (Ref. TM−18) In some cases calibration supply and DVM. Set the DVM to measure milliam-
by weights may be the only feasible means of simulat- peres (mA).

11
Type 2390 and 2390B
SPAN RED SHIPPING SCREW
POTENTIOMETER
ADJUSTMENT SHAFT SCALE
INDICATOR

ZERO AND SPAN HOLDING


POTENTIOMETER POSITION
ADJUSTMENT
COVER
SCALE SET
SCREW

ZERO
POTENTIOMETER SPRING WIRE
ADJUSTMENT SHAFT

HOLDING
POSITION (USE ONLY WHEN
DRY SPAN
INSTALLING SHIPPING
KNOB
SCREW)

POINTER

VENT PLUG

CALIBRATION DOOR

SHIPPING
SCREW CLIP CALIBRATION
DOOR SCREW

W5073-2/IL

Figure 13. Calibration Adjustments

CAUTION

The cam can be damaged if the dry span


knob is rotated in the incorrect direc-
tion. Always rotate the dry span knob
clockwise when moving away from the
AUTO position. Rotate the dry span
knob counterclockwise when moving
toward the AUTO position.
A3545-2/IL

7. Set the dry span scale in the center of its slip range
Figure 14. Transmitter Calibration Setup as follows:
a. Loosen the set screw in the dry span knob.
4. Verify that plug P2 is in the correct position for di-
rect or reverse action as appropriate (figure 7). b. Hold the dry span knob so that it can’t rotate.

c. With a free finger, slip the scale clockwise until it


stops, then counterclockwise to the opposite stop,
5. Loosen the screw on the zero and span potentiom- noting limits of travel.
eter adjustment cover and turn the cover to expose
the potentiometer adjustment shafts. d. Position the scale so that it is midway between
the two stops and hand tighten the set screw.

6. Turn the span potentiometer (marked ‘‘S’’) to its full Coupling


counterclockwise position and then clockwise two full 1. Turn the dry span knob to 0 percent using the ap-
turns. propriate right- or left-hand dry span scale.

12
Type 2390 and 2390B
2. Set the displacer to the lowest possible process 10. Loosen the torque tube shaft clamp nut.
condition, (i.e. lowest water level or minimum specific
gravity, highest temperature) or replace the displacer 11. Move the spring wire to the R holding position.
by the heaviest calibration weight.
12. Determine a new coupling position from the
following:
Note
New coupling % = (−1) (dry span scale reading in step
Interface or density applications with 9)
displacer/torque tube sized for a small
total change in specific gravity are de-
Example: X% = (–1) (–10)
signed to be operated with the displacer
X% = +10
always submerged. In these applica-
tions, the torque rod is sometimes rest-
ing on a stop while the displacer is dry. Example: X% = (–1) (+7)
The torque tube does not begin to move X% = –7
until a considerable amount of liquid
has covered the displacer. In this case, 13. Move the dry span knob to the new coupling
it is necessary to couple with the displa- position.
cer submerged in the fluid with the low-
est density and the highest process 14. Retighten the torque tube shaft clamp nut.
temperature condition, or to an equiva-
lent condition simulated with the calcu- 15. Return the spring wire to the neutral (center)
lated weights, position.

3. Move the spring wire to the R holding position.


Note
4. Remove the vent plug and insert the hex nut driver
The spring wire must be in the neutral
into the hole and onto the torque tube shaft clamp nut.
(center) position for operation in the au-
Tighten to a maximum torque of 18 lbf#in. (2.1 N#m).
tomatic mode.
5. Return the spring wire to its neutral (center)
16. Turn the dry span knob to the AUTO position.
position.
17. Use the zero potentiometer (marked “Z”) to adjust
Note the output current as follows:

The spring wire must be in the neutral ! For direct action: adjust the output current to
(center) position for operation in the au- 4 mA
tomatic mode.
! For reverse action: adjust the output current to
6. Turn the dry span knob to the AUTO position. 20 mA

7. Use the zero potentiometer (marked “Z”) to adjust 18. Slowly turn the dry span knob until the output cur-
the output current as follows: rent reading barely begins to move off the zero value.

! For direct action: adjust the output current to


4 mA. Note
If the transmitter has been precalibrated
! For reverse action: adjust the output current to for 4 to 20 mA output with reference to 0
20 mA. to 100% on the dry span scale, (a stand−
alone transmitter is shipped in this con-
8. Determine the point where the cam touches the dition), each dry span scale division in-
eccentric pin by slowly turning the dry span knob until dicates 1% of span. With this initial
the output current begins to move off the zero value. condition, the dry span knob may be ro-
tated till the output current is 1% of
9. If the resulting dry span scale reading is within !5 span (0.16 mA) inside the current range
percent, go to step 19. If it is not, record the dry span limit, then align the scale at the 1%
scale reading and proceed with the next step. mark.

13
Type 2390 and 2390B
19. Loosen the scale set screw. 2. Turn the dry span knob until the current output is
20 mA for direct action or 4 mA for reverse action.
3. Mark this position on the scale with a felt tip pen
Note and record the scale reading of the mark on a calibra-
Firmly hold onto the dry span knob tion sticker inside the dry span door. (This marked
while turning the scale. span position is used later in calibrating to specific ap-
plication requirements).
20. Slip the scale to indicate 0 percent without moving 4. Turn the dry span knob counterclockwise to the
the dry span knob. If you cannot get the scale to the AUTO position.
appropriate mark, loosen the dry span knob set screw, 5. Move the spring wire to the neutral (center)
re-center the scale, hand tighten the set screw, and position.
return to step 9).

21. Hand Tighten the scale set screw. Securing the Unit for Shipment or Placing
the Unit In Service
22. Return the dry span knob to the AUTO position. 1. If the system is to be moved without blocking the
displacer before being placed in service (as in skid
mounted systems), perform the following:
Zero and Span Adjustment
1. Depending on the transmitter action, perform one a. Uncouple the transmitter from the torque tube
or the other of the following: and install the shipping screw. (The spring wire
may be hooked in the “L” position to facilitate en-
! For direct action: move the displacer to the low- gaging the shipping screw in the lever assembly
est position (i.e., lowest water level or minimum specif- threads.)
ic gravity, highest process temperature) or replace the
displacer by the heaviest calibration weight. b. Tag the calibration door with the appropriate
warning and indicate that the transmitter will need
! For Reverse Action: move the displacer to the to be re-coupled before placing in service. (When
desired highest position (i.e., highest water level or re-coupling, the dry span scale mark will still be
maximum specific gravity, lowest process tempera- correct after the zero is aligned with the dry displa-
ture) or replace the displacer by the lightest calibration cer condition.)
weight. 2. If the system is being placed in service, or is being
2. Adjust the output current to 4 mA with the zero moved with the displacer blocked, the shipping screw
potentiometer. should be stored in the holding clip inside the door.

3. Depending on the transmitter action, perform one 3. Close the calibration door and tighten the door
or the other of the following: screw.
4. Turn the zero and span potentiometer adjustment
! For Direct Action: move the displacer to the cover back over the potentiometer adjustment screws
highest position (i.e., highest water level or maximum and tighten the cover screw.
specific gravity, lowest process temperature) or re-
place the displacer by the lightest calibration weight.
Determining Suspended Weight for
! For Reverse Action: move the displacer to the Calibration
lowest position (i.e., lowest water level or minimum
specific gravity, highest process temperature) or re- CAUTION
place the displacer by the heaviest calibration weight.
4. Adjust the output current to 20 mA with the span To avoid overloading a torque tube
potentiometer. sized for interface or density applica-
5. Repeat steps 1 and 3 to verify calibration and trim tions under dry conditions, consult your
values if necessary. Fisher sales office or sales representa-
tive for the maximum allowable substi-
tute weight Ws that can be used with
Recording the Sensor Span your particular construction.
1. To record the sensor output span on the dry span
scale, first move the spring wire to the R holding posi- To determine the total weight that must be suspended
tion. from the displacer rod to simulate a certain condition

14
Type 2390 and 2390B
of process temperature, fluid level or specific gravity, where:
solve the following equation:
V = Volume of the displacer, in cubic inches (cu-
"W d # $%# w&(V s)(SG)'( bic centimeters). '(/4 (displacer diameter)2 x
Ws ! (length of displacer submerged)]
[1 # $(%T)]
hl = Relative length of displacer that is immersed
where: in the lighter fluid. [(length of the displacer
immersed in lighter fluid)/(length of the displa-
Ws = Total suspended weight in pounds (kilo- cer)]
grams) [should never be less than 0.5 lbs
(0.227 kg)]. SGl = Specific gravity of the lighter fluid at operat-
ing temperature.

hh = Relative length of displacer that is immersed


Note
in the heavier fluid. [(length of the displacer
For liquid level control at standard tem- immersed in heavier fluid)/(length of the dis-
perature and pressure only, simulate the placer)]
lower range limit of the input span by
hanging the displacer on the displacer SGh = Specific gravity of the heavier fluid at operat-
rod. For other values of process temper- ing temperature.
ature or input span, remove the displac-
er and suspend the appropriate weight
as determined in the equation above. Dry Calibration
The appropriate Matching the Transmitter to a 249
$ = (% change in torque tube modulus per "F Series Sensor procedure must have been completed,
("C))/100% (Ref. TM-18 or call engineering) and its sensitivity recorded, before performing this pro-
cedure. All locations referenced in this procedure are
%T = (Expected process temperature) − (tempera- shown in figure 13 unless otherwise indicated.
ture of torque tube during calibration), in "F
("C)
Note
Wd = Weight of the displacer, in pounds (kilo- A transmitter factory-mounted on a sen-
grams) [determine by weighing displacer].
sor is already matched and does not re-
Note: for top-mounted sensors, also include
quire the matching procedure. The
the weight of the displacer stem.
matching is performed at room tempera-
ture using water with a specific gravity
&w = Density of water (specific gravity = 1.0), of 1 or with appropriate weights. The
0.0361 pounds per cubic inch (9.992 x 10−4 scale is marked at full actual travel
kilograms per cubic centimeter) (span) and will be the larger value on
the appropriate scale. If other condi-
Vs = Volume of the displacer, in cubic inches (cu- tions are used in matching, they should
bic centimeters), that would be submerged at be indicated on a calibration sticker in-
the level required by the calibration proce- side the dry span door, If such is the
dure. '(/4 (displacer diameter)2 x (length of case, the following procedure will not
displacer submerged)] be applicable without modification

SG = Specific gravity of the process fluid at oper- 1. Loosen the screw on the calibration door and open
ating temperature. the door.

For interface level measurement, the equation be- 2. If the red shipping screw is installed (clamping the
comes: lever assembly) in the housing wall, remove it and
stow it in the clip on the door. The transmitter is most
"W d # %# w&(V)[(h l)(SG l) ) (h h)(SG h)]( likely uncoupled from the torque tube. In this case,
Ws ! perform the Coupling steps of the Matching the Trans-
[1 # $(%T)] mitter to a 249 Series Sensor procedure before pro-

15
Type 2390 and 2390B
ceeding. To confirm that the unit is coupled, observe the torque tube when using water at ambi-
that the spring wire moves as the displacer is lifted ent conditions as the process fluid)
8. Depending on the transmitter action, perform one
or the other of the following:
Note
Place the shipping screw in the clip pro- ! For direct action, turn the dry span knob to 0
vided in the calibration door for re- percent on the appropriate scale.
installation after completing the calibra-
! For reverse action, turn the dry span knob to
tion procedures if the unit is to be
the calculated 100% scale setting on the appropriate
moved. scale.
3. Connect the transmitter to the test equipment per 9. Adjust the zero potentiometer until the output cur-
the calibration setup (figure 14) and turn on the power rent is 4 mA.
supply and the DVM. 10. Depending on the transmitter action, perform one
or the other of the following:
4. Move the spring wire to the R holding position.
! For direct action, turn the dry span knob to the
5. Loosen the screw on the zero and span potentiom- calculated 100% scale setting on the appropriate
eter adjustment cover plate and turn the cover plate to scale.
expose the adjustments.
! For reverse action, turn the dry span knob to 0
percent on the appropriate scale.
Note
11. Adjust the span potentiometer until the output cur-
The span control pivots the output rent is 20 mA.
transfer characteristic around the 4 mA 12. Proceed to step 13.
output point. For this reason, the 4 mA
output point is adjusted first with the Dry Calibration for Interface Level or Density
zero control, for both direct and reverse Measurement Applications (Steps 7 through 12)
action.
7. If the transmitter was initially coupled at dry displa-
6. Steps 7 through 12 of this procedure are broken cer condition and marked with SG = 1.0, compute the
into two parts, one for level applications and one for 0% and 100% dry span scale settings for the dry span
interface level or density measurement. Perform one scale as follows:
or the other of steps 7 through 12 depending upon the
application 0% scale setting = (SGmin) x (PBwater)
Dry Calibration for Level Applications (Steps 7 100% scale setting = (SGmax) x (PBwater)
through 12)
where:
7. Determine the calculated dry span scale setting
(PBprocess) required for 100% level calibration point by SGmin = lowest specific gravity for density or specif-
using the following formula: ic gravity of top phase for interface.
PBprocess = (SGprocess) x (PBwater)
SGmax = highest specific gravity for density or spe-
where: cific gravity of bottom phase for interface

SGprocess = specific gravity of process fluid PBwater = recorded or marked dry span scale value
from the wet calibration procedure (equiv-
PBwater = recorded or marked dry span scale value alent to the mechanical proportional band
from the wet calibration procedure (equiva- of the torque tube when using water at
lent to the mechanical proportional band of ambient conditions as the process fluid)

16
Type 2390 and 2390B
Note

Normal factory matching procedure is


done with a specific gravity of 1.0. If a
specific gravity other than 1.0 was used
in the factory matching procedure, or
the transmitter was coupled at other TORQUE
TUBE
than dry displacer condition, the zero
and span settings for the dry span scale DISPLACER
and the associated SG values are shown
on a label (key 171) on the inside sur-
face of the calibration door. In this case,
use the values on the label to confirm
the calibration, rather than the formula
shown above. The rated accuracy of the
dry span scale is only 2.5% of 4.4 de-
grees and the resolution is about 1% of
4.4 degrees, so its usefulness is limited W1389-1*/IL

at low proportional band settings. 249 SERIES (SIDE VIEW)

8. Depending on the transmitter action, perform one


Figure 15. Typical Sensor Operation
or the other of the following:

! For direct action, turn the dry span knob to 0% 15. Remove the test equipment.
on the appropriate scale.
16. Close the calibration door and tighten the door
! For reverse action, turn the dry span knob to screw.
the calculated 100% scale setting on the appropriate
scale. 17. Turn the zero and span potentiometer adjustment
cover back over the adjustment shafts and tighten the
9. Adjust the zero potentiometer until the output cur- machine screw.
rent is 4 mA.
10. Depending on the transmitter action, perform one
or the other of the following:

! For direct action, turn the dry span knob to the Principle of Operation
calculated 100% scale setting on the appropriate
scale. A level, density, or interface level change in the mea-
sured fluid causes a change in the displacer position
! For reverse action, turn the dry span knob to (figure 15). This change is transferred to the torque
0% on the appropriate scale. tube assembly. As the measured fluid changes, the
torque tube assembly rotates up to 4.4 degrees for a
11. Adjust the span potentiometer until the output cur- 249 Series sensor, varying the transmitter output be-
rent is 20 mA. tween 4 and 20 mA. This conversion is described in
12. Proceed to step 13. the following paragraphs and shown in the block dia-
gram (figure 16).
Dry Calibration Continued (Steps 13 through 17)
The rotary motion is transferred to the transmitter le-
13. Move the spring wire to the neutral (center) ver assembly (via a bellows) supported by flexure
position. strips. The rotary motion moves a magnet attached to
the lever assembly, changing the magnetic field that is
sensed by the Hall-effect position sensor. The sensor
Note then converts the magnetic field signal to an electronic
signal.
The spring wire must be in the neutral
(center) position for operation in the au- The electronic signal is ambient-temperature-compen-
tomatic mode. sated and amplified by the differential amplifier. The
signal is then linearized to compensate for the nonlin-
14. Turn the dry span scale to the AUTO position. earity of the magnetic field. The first and second-order

17
Type 2390 and 2390B

SK588
B1842-1/IL
Figure 16. Block Diagram of Type 2390 and 2390B Transmitter Operation

low pass filters dampen the effects of process turbu- properly set up transmitter can be the source of the
lence and prevent saturation of the dc amplifier and problem. If recalibrating does not clear up the problem,
the current driver. The dc amplifier provides noninter- proceed with this section.
acting zero and span adjustments.
Key numbers are shown in figure 21 or 22 unless
The current driver circuit develops a 4 to 20 mA cur- otherwise indicated.
rent output signal proportional to the dc amplifier volt-
age output. The voltage regulator provides stable sup- 1. Isolate the problem to the sensor or transmitter.
ply voltages for the transmitter circuits under varying Set up the transmitter as if to do the calibration proce-
operating conditions. dure shown in figure 14. Then slowly move the dis-
placer up and down by changing the liquid level. The
Circuits within the transmitter provide reverse polarity output should follow the change in liquid level.
protection, transient power surge protection, and elec-
tromagnetic interference (EMI) protection. 2. If there is no change in output in step 1, open the
calibration door (key 4) and carefully observe the
movement of the spring wire on the lever assembly
(figure 9) while changing the liquid level. If movement
cannot be detected:
Maintenance a. Remove the vent plug (figure 9) and loosen the
shaft clamp (figure 9) on the lever assembly (key
WARNING 12) with the hex nut driver inserted through the
vent plug hole.

To avoid personal injury due to fire or b. Manually move the spring wire (figure 13) up
explosion, remove electrical power be- and down and observe the output. If there is no
fore removing the transmitter in a haz- output or an abnormal output is observed the mal-
ardous area. Do not apply power to the function is in the transmitter. Further troubleshoot-
transmitter, with the covers removed, ing of the transmitter can be done by following table
while in a hazardous area. 4 and figure 17, or the transmitter can be returned
to the factory for repair. If a 0 to 100 percent output
can be obtained by moving the spring wire, the
Troubleshooting transmitter is functional and the problem lies with
either the torque tube shaft coupling or the displac-
Prior to reading the following text, go through the cal- er of the sensor. Consult the appropriate Type 249
ibration section and check the items as described in sensor instruction manual for further instructions on
the Precalibration Considerations procedure. An im- the sensor.

18
3N10061-G/IL

Figure 17. Schematic Diagram of Type 2390 and 2390B 4 to 20 mA Transmitter

19
Type 2390 and 2390B
Type 2390 and 2390B
Table 4. Troubleshooting Guide
Symptom Possible Cause Check Corrective Action
1. No output Incorrectly wired Wiring Wire correctly
2. Output is below 3.2 mA dc Incorrect supply voltage or Voltage at field terminals should be Check power supply voltage
excessive field wiring resistance between 11 and 45 and total field wiring resistance
volts dc against figure 3.
Sensor assembly failure Sensor assembly by performing Replace sensor assembly
the Checking Transmitter Sensor
Assembly procedure
3. Output is constant at 3.2 or Sensor assembly failure Sensor assembly by performing Replace sensor assembly
30 mA dc the Checking Transmitter Sensor
Assembly procedure
Open zero or span potentiometer Confirm resistance for zero and Replace potentiometers or
or wiring harness span potentiometers (20K ohms), repair wiring harness
continuity, solder joints, and
connector crimps of harness
4. Lever assembly magnet Sensor assembly failure Sensor assembly by performing Replace sensor assembly
movement across Hall sensor does the Checking Transmitter Sensor
not change output signal Assembly procedure
Printed wiring board failure Sensor assembly checks OK and Replace printed wiring board
magnet has not been
demagnetized.
5. Output drifting or erratic Printed wiring board failure or Replace parts successively to Replace faulty part
on bench at constant temperature sensor failure isolate problem

After any disconnection or troubleshooting, recalibrate 7. Observe the output of the sensor on the DVM while
the transmitter using the Matching the Transmitter to a slowly rotating the dry span knob from 0 to 100 per-
249 Series Sensor procedure before putting it back cent on the R scale. The DVM reading should be pro-
into operation. portional to rotation, as follows:

+47 !8 mV at the 0% extreme


0 !7 mV at the 50% position, and
Checking Transmitter Hall-Effect Sensor −47 !8 mV at the 100% position
Assembly
8. If the output does not change with rotation, the
Key numbers are shown in figure 21 or 22 unless sensor assembly is not functioning properly. Proceed
otherwise indicated. to step 10.
9. If the output varies but is not within the above
1. Remove the printed wiring board housing cover specifications, the lever assembly may be damaged or
(key 2) from the transmitter. out of alignment. Inspect the lever assembly for dam-
aged or loose flexures, failed bonds on bellows joints,
2. Remove the analog output meter (key 16), if magnet damage, etc. Make any required repairs, or
installed, as described in the Removing the Analog replace with a lever assembly that is known to be in
good condition. Perform the Reinstalling the Lever As-
Output meter procedure.
sembly procedure in the “Maintenance” section of this
manual. Then repeat the troubleshooting tests. If the
3. Apply +24 volts dc to transmitter (via field wiring). output is still not within specification, proceed to
step 10. If the output is within specification, proceed
4. Disconnect the Hall-effect sensor assembly plug to step 12.
P2 (figure 7) from the printed wiring board and connect
it to the DVM [+ to yellow (pin 1) and − to green 10. Turn the power supply off and measure the resist-
(pin 2)] . ance between pins 1 and 2 of the sensor output plug
P2. If the reading is not between 900 and 1200 ohms,
5. Center the dry span scale in its slip range per step replace the sensor assembly (key 11). If the resist-
7 of the Matching the Transmitter to a 249 Series Sen- ance is within specification, proceed to step 11.
sor, Setup procedure.
11. Disconnect plug P1 (figure 7) from the printed wir-
6. Move the spring wire to the R holding position ing board and measure between its pins (blue and red
(figure 13). wires). If the reading is not between 900 and 1200

20
Type 2390 and 2390B
ohms, replace the sensor assembly. If the resistance with the hex nut driver inserted through the vent plug
is within specifications, proceed to step 12. hole.

12. Connect a milliammeter between pins 1(+) 2. Turn the dry span scale to the auto position and
and 2(−) on the printed wiring board connector J1. move the spring wire to the L position to make re-
installing the shipping screw easier.
13. Turn the power supply on.

14. The current should be between 2.08 and 2.12 mA 3. Re-install the red shipping screw (key 57) that was
at 70"F (21"C). [If measured at −40"F (−40"C), the removed in the “Installation” or “Calibration” section.
current should be approximately 0.05 mA lower than
the 70"F (21"C) value. At +176"F (80"C), the current 4. Loosen and remove the hex nuts (key 62) from the
should be approximately 0.05 mA higher than the mounting studs (key 61).
70"F (21"C) value.]
15. If the current meets specification but the sensor 5. Carefully pull the transmitter straight off the sensor
output is not within the ranges given in step 7 for torque tube.
100% span (4.4 degree rotation of the input shaft), the
sensor assembly sensitivity is non-standard and it 6. When re-installing the transmitter, follow the ap-
must be replaced. propriate procedure outlined in the “Installation” sec-
tion.
16. To replace the sensor, see Removing the Printed
Wiring Board Assembly and Removing and Re-Instal-
ling the Transmitter Sensor Assembly. 249 Series Sensor in High Temperature
Application
Key numbers are shown in figure 10 except where
Checking the Analog Output Meter
otherwise indicated.
The analog output meter resistance should be approxi-
mately 3.5 ohms. 1. Remove the vent plug (figure 9) and loosen the
shaft clamp (figure 9) on the lever assembly (key 12,
figure 21 or 22) with the hex nut driver inserted
through the vent plug hole.

Removing the Transmitter from a 249 2. Turn the dry span scale to the auto position and
Series Sensor move the spring wire to the L position to make re-
installing the shipping screw easier.

CAUTION 3. Re-install the red shipping screw (key 57, figure 21


or 22) that was removed in the “Installation” or “Cal-
ibration” section.
Take special care during removal of the
transmitter from the 249 Series sensor. 4. Loosen and remove the cap screws (key 39).
Bending or side-loading of the sensor
torque tube assembly could cause er-
rors in measurement on re-installation. 5. Carefully pull the transmitter straight off the torque
tube shaft or torque tube shaft extension (key 37).

6. Loosen and remove the hex nuts (key 62, figure 21


or 22) from the mounting studs (key 61, figure 21
249 Series Sensor in Standard or 22).
Temperature Application
7. Pull the heat insulator (key 35) off the mounting
Key numbers are referenced in figure 21 or 22 except studs.
where otherwise indicated.
8. When re-installing the transmitter, follow the ap-
1. Remove the vent plug (figure 9) and loosen the propriate procedure outlined in the “Installation” sec-
shaft clamp (figure 9) on the lever assembly (key 12) tion.

21
Type 2390 and 2390B
Printed Wiring Board Compartment Removing and Re-installing the
Parts Removal and Replacement Transmitter Hall-Effect Sensor Assembly
1. Remove the two machine screws (key 167).
CAUTION 2. Slide the sensor assembly (key 11) out of the hous-
ing (key 1).
Electrostatic voltages present in the 3. To re-install, slide the O-ring (key 10) over the sen-
field environment and transferred to the sor assembly.
printed wiring board can cause failure
or degraded performance. Use appropri- 4. Slide the Hall-effect sensor assembly into the
ate antistatic procedures any time the housing.
printed wiring board housing cover is 5. Insert the two screws (key 167) and alternately
removed. tighten.

Key numbers are shown in figure 21 or 22 except Re-installing a Potentiometer Assembly


where otherwise indicated.
1. The potentiometer assembly comes with the shaft
coupling (key 25) installed on the potentiometer
Removing the Analog Output Meter (key 27 or 28). Slip the shaft coupling (key 25) over
the potentiometer shaft extension (key 22).
1. Disconnect power.
2. Unscrew the hex nut on the potentiometer bushing
2. Unscrew and remove the printed wiring board until it is near the end of the bushing. Insert the poten-
housing cover (key 222). tiometer assembly (keys 27 or 28) into the bracket and
snugly tighten the hex nut.

3. Unscrew the two machine screws (key 18). Re-installing a Printed Wiring Board
Assembly
4. Disconnect connector plug P5 from board connec-
tion J5 (figure 7). CAUTION
5. Remove the entire output meter assembly (key 16) To avoid damaging wiring that can inter-
from the housing (key 1). rupt transmitter operation when the ana-
log output meter and printed wiring
board are installed, verify that wires are
Removing the Printed Wiring Board routed around the posts and through
Assembly the notch in the printed wiring board as
shown in figure 18.
1. Disconnect connector plugs P1, P2, P3, P4, P6, 1. Route the Hall-effect sensor wires as shown in
and P7 from board connections J1, J2 or J2.1, J3, J4, figure 18.
J6, and J7 respectively (figure 7).
2. Insert the printed wiring board assembly (key 64)
2. Remove the three machine screws (key 20). into the housing (key 1).
3. Tighten the three machine screws (key 21).
3. Carefully remove the printed wiring board (key 64)
from the housing (key 1). 4. Reconnect connector plugs P1, P2, P3, P4, P6,
and P7 to board connections J1, J2 or J2.l, J3, J4, J6,
and J7 respectively as identified in figure 7.
Removing a Potentiometer Assembly
1. Loosen the hex nut on the potentiometer assembly
Re-installing the Analog Output Meter
until the threads are disengaged.
CAUTION
2. Pull the potentiometer (key 27 or 28) and shaft cou-
pling (key 25) slowly and carefully off of the potentiom- To avoid damaging wiring that can inter-
eter shaft extension (key 22) with a twisting motion. rupt transmitter operation, verify that

22
Type 2390 and 2390B
WIRES MUST NOT CROSS THIS EDGE OF SENSOR FLANGE 2. Remove the two funnel plate machine screws
AMPLIFIER
PWB
TO PREVENT CUTTING WHEN METER IS INSTALLED (key 19) and funnel plate (key 45).
ANALOG METER
LOCATION 3. Loosen and remove the red shipping screw
POST (key 57) if installed.

RED &
BLUE GREEN & Note
WIRES YELLOW
WIRES Place the shipping screw in the clip pro-
SENSOR
ASSEMBLY vided on the calibration door for re-
installation after completing the calibra-
17B0679-A / DOC
tion procedures if the unit is to be
moved.
Figure 18. Hall-Effect Sensor Wire Routing
4. Loosen and remove the two cap screws (key 20).

5. Pull the lever assembly (key 12) gently out of the


wires are not pinched between the out- housing.
put meter assembly and the printed wir-
ing board when installing the output 6. Inspect the flexure strips (key 85, figure 23) to see
meter. A notch in the meter hole is pro- if they are in any way bent or damaged. If they are
vided for wires to pass through the damaged, replace as described in the following proce-
printed wiring board. dure.

1. Insert the output meter assembly (key 16) into the


hole in the printed wiring board (key 64). Removing and Replacing the Flexure
Strips
2. Connect connector plug P5 to the board connection
Key numbers are shown in figure 23 except where
J5 (figure 7).
otherwise indicated.

3. Position the aperture (key 17) over the meter, Remove the lever assembly as described in the pre-
insert the machine screws (key 18) through the apera- vious procedure.
ture and output meter mounting holes and tighten
snugly. 1. Position the alignment tool as shown in figure 19,
step 1.
4. Screw the printed wiring board housing cover
(key 222) snugly onto the housing (key 1). 2. Insert the alignment tool guides into the holes on
the bracket assembly as shown in figure 19, step 2.

3. While firmly grasping the alignment tool, remove


Sensor Connection Compartment Parts the cap screws (key 89), washer plate (key 93), and
Removal and Re-installation the flexure strips (key 85) from the lever assembly.

Remove the transmitter from the 249 Series sensor as


described in the Removing the Transmitter from a 249 CAUTION
Series Sensor procedure.

Key numbers are shown in figure 21 or 22 except Hold the alignment tool firmly when re-
where otherwise indicated. placing flexure strips to prevent pos-
sible bending or stressing that could
cause inaccurate operation.
Removing the Lever Assembly
4. Carefully position the new flexure strips and then
1. Remove the nuts (key 62) and slide the adapter insert the washers, plates and cap screws. Lightly
ring (key 3) off the housing and mounting studs snug the cap screws to hold the flexure strips in posi-
(keys 1 and 61). tion.

23
Type 2390 and 2390B

FLEXURE
STRIP

FLEXURE
STRIP
CAP SCREWS

WASHER
STRIP

ALIGNMENT
TOOL

NOTE:
MAINTAIN CONSTANT PRESSURE ON ALIGNMENT TOOL AND
LEVER ASSEMBLY DURING REMOVAL AND REINSTALLATION.
W5605/IL W5604/IL

STEP 1—ALIGNMENT TOOL POSITIONED


STEP 2—ALIGNMENT TOOL IN PLACE
Figure 19. Removing and Reinstalling Flexure Strips

5. Tighten the cap screws at the solid end of the flex- Re-installing the Dry Span Scale
ure, then alternately tighten all the cap screws to
9 lbf#in (1 N#m). 1. Put the dry span scale over the shaft with the
proper scale orientation (figure 20).
6. Remove the alignment tool. 2. Put the pointer over the shaft and screw the knob
clockwise loosely onto the cam disk assembly shaft.

Removing the Dry Span Scale 3. Put a 9/32 inch (7 mm) wrench on the shaft nut and
hold firmly. The scale can also be assembled by in-
Key numbers are shown in figure 21 or 22 except serting a small rod through the aligned hole in the dial
where otherwise indicated. and housing.

1. Loosen the door screw on the calibration door 4. Tighten the dry span knob.
(figure 13) and open the door.
5. Set the dry span scale to its middle position
2. Loosen the scale set screw (figure 13) on the dry (figure 20) in reference to the scale adjustment stop.
span knob with a screwdriver.
6. Tighten the scale set screw on the dry span knob
with a screwdriver.
3. Put a 9/32 inch or a 7 mm wrench on the cam disk
assembly shaft nut (key 46) and hold firmly. The scale
can also be removed by inserting a small rod through Re-installing the Lever Assembly
the aligned hole in the dial and housing. Key numbers are shown in figure 21 or 22 except
where otherwise indicated.
4. Turn the dry span knob counterclockwise and re-
move the knob, pointer, and scale (keys 50, 49, 1. Insert the lever assembly (key 12) into its mounting
and 48) from the shaft. position.

24
Type 2390 and 2390B

W5602-1/IL W5603-1/IL PIN


SPRING WIRE
CAM
SCALE ADJUSTMENT STOP

DUAL SCALE SHOWN WITH KNOB AND POINTER IN PLACE DUAL SCALE SHOWN WITH KNOB AND
SPRING WIRE IS IN NEUTRAL (CENTER) POSITION POINTER REMOVED

Figure 20. Transmitter Dry Span Scale

2. Insert and tighten the two cap screws (key 20). 7. Turn the wrench to move the lever assembly until
the output is 0 (zero) !13 mVdc. Retighten the lever
assembly mounting screws.
3. Carefully move the lever assembly back and forth
over the sensor assembly (key 11). There should be
no touching or restriction of free travel. 8. Move the spring wire to the R holding position
(figure 20).

4. Connect the transmitter test equipment per the set-


up shown in figure 14 and turn on the power supply 9. Loosen the scale set screw (figure 13) and slip the
scale to its approximate middle position. The scale can
and DVM.
be rotated approximately 7 dry span scale divisions
from center in either direction.
5. Measure the output from the unconnected A or B
connector (figure 7). If the reading is 0 (zero) !13 10. Tighten the scale set screw.
mVdc, go to step 8. If the reading is not within the !13
mVdc limits, continue with the following step.
11. Set the dry span scale to 50% on the scale.

12. Loosen the locking cap screw (key 92, figure 23)
Note with a 5/64 inch (2 mm) Allen wrench.

The transmitter should be in the mount-


ing position with the vent plug on the 13. Adjust the eccentric pin (key 91, figure 23) until
bottom. the output voltage equals 0 (zero) !1 mVdc.

14. Tighten the locking cap screw (key 92, figure 23).
6. Loosen the cap screws (key 20) slightly and insert
an Allen wrench in the lever assembly adjustment
hole. 15. Return spring wire to the neutral (center) position.

25
Type 2390 and 2390B
Note Key Description Part Number
11* Sensor Assembly, stainless steel 1N10074 G022
To recheck, turn the scale to the AUTO 12* Lever Assembly, aluminum
position and confirm the 0 (zero) !13 Type 2390 (inch) 2N10086 X012
Type 2390B (metric) 2N10086 X022
mVdc (millivolts dc) Hall-effect sensor
output. If the output is 30 mVdc or 15 Set Screw, stainless steel (not shown)
greater, the flexure strips may be dam- Used with flameproof
aged and require replacement. The Type 2390B only, 1N10110 G012
transmitter should be in the mounting 16* Analog Output Meter Assembly, 4−20 mA 1N10111 G012
position with vent plug on the bottom. 17 Aperture (used with meter only), aluminum 1N10117 G012
18 Machine Screw (used with meter only)
16. Re-install the funnel plate. Stainless steel (2 req’d)
Type 2390 1N10313 G012
Type 2390B 1N10312 G012
17. Re-install the funnel plate screws and tighten. 19 Machine Screw, stainless steel
Type 2390 (3 req’d) 1N10183 G012
18. Slide the adapter ring onto the mounting studs. Type 2390B (4 req’d) 1N10364 G012
20 Cap Screw, stainless steel (2 req’d)
19. Re-install the transmitter according to the ap- Type 2390 1N10307 G012
propriate Installation procedures. Type 2390B 1N10306 G012

21 Machine Screw, stainless steel (4 req’d)


20. Recalibrate the transmitter as described in the Type 2390 1N10185 G012
“Calibration” section. Type 2390B 1N10119 G012
22 Potentiometer Shaft Extension
Stainless steel (2 req’d) 1N10122 G012
23 O-Ring, nitrile (2 req’d) 1H2926 G0012
24 Cover Plate, aluminum 1N10123 G012

Parts Ordering 25* Potentiometer Shaft Coupling,


silicone rubber (2 req’d) 1N10124 G012
When corresponding with the Fisher Controls sales 27* Potentiometer Assembly (Zero), includes key 25
office or sales representative about this equipment, 20K ohm (R28)
always mention the transmitter serial number. When For Type 2390 or intrinsically safe 2390B 1N10126 G012
For 2390B w/LCIE flameproof approval 1N10126 G022
ordering replacement parts, refer to the part number of 28* Potentiometer Assembly (Span), includes key 25
each required part as found in the following parts lists. 20K ohm (R35)
For Type 2390 or intrinsically safe 2390B 1N10319 G012
For 2390B w/LCIE flameproof approval 1N10319 G022

30 Wire Assembly, copper (red wire) 1N10199 G012


Repair Kits 31 Wire Assembly, copper (blue wire) 1N10199 G022
Flexure strips for Type 249 32 Wire Assembly (2 req’d), copper (black wire)
(includes four of key 85) R2390 X00032 Type 2390 1N10194 G012
Cover O-rings (includes keys 8 and 9) R2390 X00022 Type 2390B 1N10135 G012
Alignment Tool 1N10323 G012
Tool Kit (Type 2390) 5N10477 X012 33 Barrier Strip,
Type 2390 1H2904 06992
Type 2390B
flameproof 1N10243 G022
Intrinsically safe 1N10243 G012
Parts List 34 Polarity Marker
Type 2390, fiber (+ and −) 1H3105 06992
Type 2390B, plastic (+) 1N10245 G012
Type 2390 and 2390B Liquid Level 35 Polarity Marker
Type 2390B only, plastic (−) 1N10246 G012
Transmitters (figures 21, 22, and 23) 36 Twist Guard
Type 2390B only 1N10244 G012
Key Description Part Number
1 Housing, A03600 aluminum alloy casting 37 Wire Retainer (internal earthing terminal)
The housing is not field replacable. Send the unit Type 2390, zinc pl steel 16A2821 X012
to a Fisher service center for housing replacement. Flameproof 2390B, nickel pl brass 1N10136 G012
3 Adaptor Ring, A03600 aluminum alloy casting 1N10160 G012 Not used on intrinsically safe 2390B −−−
8* O-Ring, nitrile 1V3657 X0012 41 Nameplate
9* O-Ring, nitrile 1N10121 G012 42 Screwed Gland, plastic
10* O-Ring, nitrile 1F1139 G0012 Intrinsically safe Type 2390B only 11B3870 X012

26 * Recommended spare part.


Type 2390 and 2390B

APPLY LUB/SEALANT
4N10228-M/ DOC

Figure 21. Type 2390 Transmitter Assembly

27
Type 2390 and 2390B

4N10059-R / DOC

Figure 22. Type 2390B Transmitter Assembly

28
Type 2390 and 2390B

APPLY EPOXY
2N10086-K / DOC VIEW A-A

Figure 23. Type 2390 or 2390B Lever Assembly

Key Description Part Number Key Description Part Number


43 Plug 63 Retaining Ring, stainless steel (2 req’d) 1N10163 G012
For Type 2390, stainless steel, 1A3692 X0462 64* Printed Wiring Board Assembly
For intrinsically safe Type 2390B, plastic 12B0912 X012 4 to 20 milliamperes 2N10065 G012
For Flameproof 2390B, stainless steel 12B1547 X012 66 Certificate
44* Vent Plug, plastic 1N10142 G012 Intrinsically safe (PTB, EEx ia) 1N10062 G012
45 Funnel Plate, stainless steel 1N10143 G012 Flameproof (LCIE, EEx d) 11B4663 X022
67 Adhesive, Loctite 430
46 Cam Disk Assembly, stainless steel 1N10144 X012 (not furnished with the transmitter)
47 Disk, stainless steel 1N10147 X012
48* Scale, aluminum 2N10148 X012 68 Lubricant, Lubriplate Mag-1
49 Pointer, polycarbonate 1N10149 G012 (not furnished with the transmitter)
70 Thread Lock, Loctite 242
50 Knob, aluminum (not furnished with the transmitter)
Type 2390 1N10188 G012 85* Flexure Strip for Type 249,
Type 2390B 1N10150 G012 stainless steel (2 req’d)
51 Straight Pin, stainless steel 1N10151 X012 Order the flexure strip repair kit, (see Repair Kits)
53 Disk Spring, stainless steel 1N10378 G012 89 Cap Screw, stainless steel (8 req’d)
54* Gasket, nitrile 1N10156 G012 Type 2390 1H2905 G0012
55 Hinge Pin, stainless steel 1N10157 G012 Type 2390B 1N10256 G012
56 Machine Screw, stainless steel
Type 2390 1N10190 G012 91 Eccentric Pin 1N10654 G012
Type 2390B 1N10158 G012 92 Cap Screw, 18-8 stainless steel
57 Red Shipping Screw, stainless steel Type 2390 1N10669 X012
Type 2390 1N10191 G012 Type 2390B 1N10668 X012
Type 2390B 1N10159 G012 93 Strip, stainless steel (4 req’d) 1N10330 G012
94 Spring Wire 1N10168 G022
59 Clamping Saddle 154 Machine Screw, stainless steel (2 req’d)
Type 2390B only 18B3951 X012 Type 2390 only 1P4743 X0012
60 Spring Washer, stainless steel 155 Lock Washer, stainless steel (2 req’d)
Type 2390 (2 req’d) 610006 10X12 Type 2390 only 6100058 0X12
Type 2390B (3 req’d) 610006 10X12 158 Warning Label 1N10318 G012
61 Stud, stainless steel (4 req’d) 161 Cable Tie 1N10310 G012
Type 2390 1N10192 G012 167 Machine Screw, stainless steel (2 req’d)
Type 2390B 1N10162 G012 Type 2390 1N10375 G012
62 Hex Nut, stainless steel (4 req’d) Type 2390B 1N10374 G012
Type 2390 1E9440 X0352
Type 2390B 1N10252 G012

*Recommended spare parts 29


Type 2390 and 2390B
Key Description Part Number Key Description Part Number
170 Hex Socket Wrench, 223 Dry Span Door Ass’y, includes key 54 17B0678 X012
For flameproof Type 2390B only 1N10455 G012 227 Wire Retainer, znpl steel (external earthing terminal)
171 Label, Calibration (not shown) Type 2390 only 17B7757 X012
(use only when specified) 1N10459 G012
172
216
Plain Washer, stainless steel
Lock Washer,
1N10492 G012
249 Series Sensor Insulator Assembly
Type 2390B only 1H3137 28992 (figure 10)
217 Machine Screw, 35 Insulator, 304 stainless steel 22A0033 X012
Type 2390B only 13B8766 X012 36 Shaft Coupling, 303 stainless steel 1A5779 35032
219 Adhesive, epoxy (ITW Devcon) 37 Shaft Extension, N05500 nickel alloy 1B6815 40022
(not furnished with transmitter) 38 Set Screw, stainless steel (2 req’d) 1E6234 X0022
221 Terminal Cover Assembly
Type 2390 & intrinsically safe 2390B 17B0672 X012 39 Cap Screw, plated steel (4 req’d) 1A3816 K0012
Flameproof Type 2390B 17B0673 X012
222 End Cover Ass’y
w/analog output meter
Type 2390 24B7343 X012 Loop Schematics
Intrinsically safe 2390B 24B7390 X012
Flameproof 2390B 21B4665 X012
This section includes loop schematics required for wir-
w/o analog output meter ing of intrinsically safe installations. If you have any
Type 2390 & intrinsically save 2390B 11B2460 X022 questions, contact your Fisher Controls sales repre-
Flameproof 2390B 24B8008 X012 sentative or sales office.

27A1473-C Sheet 1 of 2/DOC

30
Type 2390 and 2390B

27A1473-C Sheet 2 of 2/DOC

29A5848-F/DOC

31
Type 2390 and 2390B

20B2577-B Sheet 1 of 2/DOC

20B2577-B Sheet 2 of 2/DOC

Fisher, Fisher-Rosemount, and Managing The Process Better are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc.
$Fisher Controls International, Inc. 1985, 1999; All Rights Reserved

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.

For information, contact Fisher Controls:


Marshalltown, Iowa 50158 USA
Cernay 68700 France
Sao Paulo 05424 Brazil
Singapore 128461
32
Printed in U.S.A.

You might also like