Wind Analysis For Low-Rise Building, Based On ASCE 7-98 Input Data
Wind Analysis For Low-Rise Building, Based On ASCE 7-98 Input Data
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Wind Analysis for Low-rise Building, Based on ASCE 7-98
INPUT DATA
Exposure category (A, B, C or D) = B
Importance factor, pg 55, (0.87, 1.0 or 1.15) I = 1.00 Category II
Basic wind speed V = 90 mph
Topographic factor (Sec.6.5.7.2, pg 29 & 39) Kzt = 1 Flat
Building height to eave he = 35 ft
Building height to ridge hr = 39 ft
Building length L = 100 ft
Building width B = 60 ft
Effective area of components A = 50 ft2
DESIGN SUMMARY
Max horizontal force normal to building length, L, face = 39.00 kips
Max horizontal force normal to building length, B, face = 22.20 kips
Max total horizontal force at wind with any angle to building = 39.00 kips
Max total upward force = 60.48 kips
ANALYSIS
Velocity pressure
qh = 0.00256 Kh Kzt Kd V2 I = 13.08 psf
where: qh = velocity pressure at mean roof height, h. (Eq. 6-13, page 30)
Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-5, Case 1,pg 60) = 0.74
Kd = wind directionality factor. (Tab. 6-6, for building, page 61) = 0.85
h = mean roof height = 37.00 ft
< 60 ft, [Satisfactory]
Design pressures for MWFRS
p = qh [(G Cpf )-(G Cpi )]
where: p = pressure in appropriate zone. (Eq. 6-16, page 32).
G Cp f = product of gust effect factor and external pressure coefficient, see table below. (Fig. 6-4, page 43)
G Cp i = product of gust effect factor and internal pressure coefficient. (Tab. 6-7, Enclosed Building, page 62)
= 0.18 or -0.18
a = width of edge strips, Fig 6-4, note 7, page 43, (IBC 1609.6.3), MAX[ MIN(0.1B, 0.4h), 0.04B,3] = 6.00 ft
INPUT DATA
Exposure category (A,,B, C or D) = B
Importance factor (0.87, 1.0 or 1.15) I = 1.00 Category II, page 55
Basic wind speed V = 90 mph
Topographic factor (Sec.6.5.7.2) Kzt = 1 Flat, page 29 & 39
Building height to roof H = 108 ft
Parapet height HP = 0 ft
Building length L = 100 ft
Building width B = 50 ft
Effective area of mullion AM = 55 ft2
Effective area of panel AP = 27 ft2
DESIGN SUMMARY
Max building horizontal force normal to building length, L, face = 187.7 kips
Max base moment at wind normal to building length, L, face = 11595.0 ft - kips
Max building horizontal force normal to building length, B, face = 77.5 kips
Max base moment at wind normal to building length, B, face = 5234.5 ft - kips
Max building upward force = 78.7 kips
Max building torsion force = 586.6 ft - kips
ANALYSIS
Velocity pressures
qz = 0.00256 Kz Kzt Kd V2 I
where: qz = velocity pressure at height, z. (Eq. 6-13, page 30)
Kz = velocity pressure exposure coefficient evaluated at height, z. (Tab. 6-5, Case 2, page 60)
Kd = wind directionality factor. (Tab. 6-6, for building, page 61) = 0.85
z = height above ground
z (ft) 108 108 108 108 108 108 108 108 108 108
Kz 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01 1.01
qz (psf) 17.80 17.80 17.80 17.80 17.80 17.80 17.80 17.80 17.80 17.80
90 8.30 14.71 Surface Dist. (ft) GCPi - GCPi Surface Dist. (ft) GCPi - GCPi
100 8.66 15.07 0 - 50 -18.94 -12.53 0 - 54 -18.94 -12.53
108 8.90 15.31 100 -13.80 -7.39
Roof Roof