You are on page 1of 4

Measurement control & energy management


DIRIS® system DIRIS A20
DIRIS A20

Functions
The DIRIS A20 is a multi-function meter
for measuring electrical values in all low
voltage networks. All the parameters can
be configured and displayed on its front
panel and measuring and timing functions
used.

Conformity to standards
• IEC 62053-22 class 0,5 S
• IEC 62053-23 class 2
• IEC 61010-1
• IEC 61000-4-2
• IEC 61000-4-3
• IEC 61000-4-4
• IEC 61000-4-5
• IEC 61000-4-6
• IEC 61000-4-8
• IEC 61000-4-11
• IEC 60068-2-6
• IEC 60068-2-11
diris_560_a_1_x_cat

• IEC 60068-2-30

1 2 3 4 5
DIRIS A20
1. LCD display 4. Direct access key for active, reactive and
2. Direct access key for instantaneous and max. apparent power (instantaneous and max.
currents values values) and power factor
3. Direct access key for voltages and frequency 5. Direct access key for energies

Applications
Using electrical parameters means using Measurement in real effective values
several analog or digital single-function (TRMS) of :
products such as ammeters, voltmeters or • current per phase and neutral in instant
wattmeters. • phase-to-neutral and phase-to-phase
DIRIS A20, with its six direct access keys voltages
and LCD display, helps you use all the • frequency
parameters in an LV or HV installation.
• active positive power total in instant and
These parameters can be centralized on a
maximum value over a programmable
PC or PLC through an RS485 link using
period
JBUS/MODBUS protocol®. The casing is
Diris A20 RS485 Diris A20 designed so that the installer can easily fit • reactive positive power total in instant
the DIRIS A20 to the door of a cabinet. To • apparent positive power total in instant
485 Main
232 meter panel facilitate and optimize the operator's work, • Power Factor (PF) total with inductive or
PLC the DIRIS A20 uses one of the most capacitive indication.
functional principles for integrating Energies meters
communications or metering. Simply fit a • Positive active energy meter
PC Currents module to the rear of the casing to add a
per phase • Positive reactive energy meter.
diris_576_a_1_gb_cat

curve function.
Logi

CON
ciel
de
supe

TRO
rvisi

L VISI
on
DIR
IS
®

ON
et
CO

®
UN
TIS

1
®

CONTROL VISION software

B. 1 SOCOMEC general catalogue


Measurement control & energy management
DIRIS A20

diris_560_a_2_cat
References
Basic device DIRIS A20
Auxiliary power supply Us
Reference
110 … 400 V~ / 120 … 350 V 4825 0A20

Options
Plug-in modules
Reference
Pulse output module 4825 0080
Communication module RS485 JBUS / MODBUS® 4825 0082

Pulse output
1 configurable output impulses (type, weight and duration) for kWh + and kvarh +.
DIRIS 445 A
DIRIS 563 A

Communication
RS485 link with JBUS/MODBUS® protocol (speed up to 38400 bauds)
DIRIS 447 A

Overall dimensions
Type panel mounting
92 + 0.8
-0
.0 Dimensions H x W x D 96 x 96 x 60 mm
Case protection rating IP 20
Front protection rating IP 52
Display type LCD
Terminal block type fixed and pull-out
Voltage and other connection section 0,2 … 2,5 mm2
96 Current connection section 0,5 … 6 mm2
92 + 0.
-0 8
.0
Weight 400 g
diris_577_a_1_x_cat

20
60
96

SOCOMEC general catalogue B. 2


Measurement control & energy management


DIRIS® system DIRIS A20
DIRIS A20

Electrical characteristics
Current measurement on inputs (TRMS) Frequency measurement
CT primary 9 999 A Measurement range 45 … 65 Hz
CT secondary 5A Measurement updating period 1s
Measurement range 0 … 11 kA Accuracy 0,1 %
Input consumption 0,6 VA
Energy accuracy
Measurement updating period 1s
Accuracy 0,2 % Active (according to IEC 62053-22) class 0,5 S
Sustained overload 6A Reactive (according to IEC 62053-23) class 2
Intermittent overload 10 In for 1 s
Auxiliary power supply
Voltage measurement (TRMS)
AC voltage 110 … 400 V~
Direct measurement between phases 5 … 500 V~ AC tolerance ± 10 %
Direct measurement between phase and neutral 3 … 289 V~ DC voltage 120 … 350 V
Input consumption ≤ 0,1 VA DC tolerance ± 20 %
Mesaurement updating period 1s Frequency 50 / 60 Hz
Accuracy 0,2 % Consumption 10 VA
Sustained overload 800 V~
Outputs (Pulse)
Power measurement
Number of relays 1
Mesaurement updating period 1s Type 100 V - 0,5 A - 10 VA
Accuracy 0,5 % Max. number of operations ≤ 108

Power factor measurement Communication


Measurement updating period 1s Link RS485
Accuracy 0,5 % Type 2 … 3 wires half duplex
Protocol JBUS/MODBUS® in RTU mode
JBUS/MODBUS® speed 1400 … 38400 bauds

Operating conditions
Operating temperature - 10 … + 55 °C
Storage temperature - 20 … + 85 °C
Relative humidity 95 %

Terminal blocks
V1 V2 V3 VN A U X S1 S2 S1 S2 S1 S2
diris_578_a_1_x_cat

S1 - S2 : current inputs
I1 I2 I3

AUX : auxiliary power supply Us


DIRIS A20 V1, V2, V3 & VN : voltage inputs

• Communication module • Pulse output module

0V - + 1 8 19
diris_579_a_1_x_cat

diris_580_a_1_x_cat

1
0n
RS485 R = 120 Ω

OUT 1
DIRIS A20 DIRIS A20

Liaison RS485 18 - 19 : pulse output no. 1


R = 120 Ω : internal resistance for the RS485 link

B. 3 SOCOMEC general catalogue


Measurement control & energy management
DIRIS A20

Connections
Recommendation : when disconnecting the DIRIS, it is essential This can be done automatically using a product from the
that the secondaries of each current transformer be short- SOCOMEC catalogue, the PTI.
circuited.


Low voltage balanced network


• 3/4 wires with 1 CT • Single phase • Two phase

N
P1 P1 P1
L1 L1 L1
S1 S2 S1 S2 S1 S2
L2 N L2
L3
Fus. 0,5 A gG

Fus. 0,5 A gG

Fus. 0,5 A gG
diris_392_a_1_x_cat

diris_393_a_1_x_cat

diris_394_a_1_x_cat
V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2

I1 I2 I3 I1 I2 I3 I1 I2 I3

The use of 1 CT reduces by 0.5 % the accuracy of the


phases whose current is worked out by vector calculation.


Low voltage unbalanced network


• 3/4 wires with 3 CTs • 3 wires with 2 CTs • 3 wires with 2 CTs
N P1 P1
P1 L1 L1
L1 S1 S2 S1 P1
S1 S2 L2 L2
L2 P1 S1 S2
P1 L3 L3
L3 S1 S2
S1 S2
Fus. 0,5 A gG

Fus. 0,5 A gG
Fus. 0,5 A gG
diris_395_a_1_x_cat

diris_396_a_1_x_cat

diris_397_a_1_x_cat

V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2 V1 V2 V3 VN S1 S2 S1 S2 S1 S2

I1 I2 I3 I1 I2 I3 I1 I2 I3

The use of 2 CTs reduces by 0.5 % the accuracy of the The use of 2 CTs reduces by 0.5 % the accuracy of the
phase whose current is worked out by vector calculation. phase whose current is worked out by vector calculation.


Other information
• Communication via RS485 link • Alternating and direct voltage auxiliary
power supply

110 / 400 V~
120 / 350 V

LIYCY-CY
diris_398_a_1_x_cat

diris_501_a_1_x_cat

0V - + A U X
1
0n

RS485 R=120 Ω

It is recommended that the auxiliary power supply be


protected by the use of BS88 2A gG fuses

SOCOMEC general catalogue B. 4