5.1 SCOPE
The provisions of this chapter shall control the installation of fire detection and fixed fire fighting
arrangement in low rise buildings of different occupancy groups. The term 'Lowrise Building' shall include
all structures which are not taller than 20 m from the finished ground level and do not have more than six
floors.
The fire detection and fire fighting arrangement required for highrise buildings are specified in Appendix
D.
In addition to the general provisions covered under Chapter 4, the following requirements for lowrise
buildings shall be complied with.
Part 4 4-1
Fire Protection
Part 4
Fire Protection
4-2
Chapter 5
Specific Requirements for Various Occupancies
In addition to the general provisions specified in Chapter 4, the following requirements for Occupancy B
shall be complied with.
5.3.1 Educational buildings upto 2 storey height and having less than 100m2 floor area per floor shall not require
fixed fire detection and fire fighting arrangements.
5.3.2 Educational buildings having more than 2 storey shall be provided with manually operated electric fire
alarm system.
5.3.3 Portable fire fighting appliances shall be kept as per instruction of the concerned authority.
The following provisions shall be complied with for lowrise institutional buildings.
In addition to the general provisions, as detailed under Chapter 4, the following requirements shall be
complied with.
4-4
Chapter 5
Specific Requirements for Various Occupancies
In addition to the general provisions covered under Chapter 4, the following requirements for Occupancy
F shall be complied with.
ii) Office buildings more than 2 storey Manually operated electric fire alarm system shall
high or floor area more than 500m2 be provided along with portable fire extinguishers
iii) Other mercantile buildings more Automatic fire alarm system required along with
than 2 storey high and more than portable fire extinguishers.
500m2 in floor area
iv) Laboratories with precession Automatic fire alarm system and fixed automatic
instruments CO2 fire extinguishing system shall be provided in
addition to portable fire extinguishers.
v) Buildings dealing with flammable Automatic foam or CO2 or dry chemical fire
liquids extinguishing system required along with portable
fire extinguishers.
vi) Solvent storage in office Automatic foam or CO2 or dry chemical fire
extinguishing system required along with portable
fire extinguishers.
vii) Computer installation Automatic fire alarm system and fixed CO2 or
fixed vaporising liquid fire extinguishing system
required along with portable fire extinguishers.
viii) Electrical switch board room/sub- Automatic fire alarm and/or fixed CO2 or fixed
station vaporising liquid fire extinguishing system shall
be installed along with portable fire extinguishers.
ix) Space under false ceiling Automatic fire alarm system shall be installed.
ii) Other premises (other than shops, Automatic fire alarm system shall be provided
stores, markets etc.) along with portable fire extinguishers.
ii) Shopping complex under covered Automatic fire alarm and venting system, fixed
roof with areas more than 500m2 and portable CO2 fire extinguisher shall be
on each floor installed. Provision for portable fire pump with
relevant accessories and conservance of water
shall be provided along with trained personnel.
iii) Underground shopping complex Automatic fire alarm, sprinklers and fixed and
portable CO2 fire extinguisher shall be installed.
In addition to the general provision covered under Chapter 4, the following requirements for Occupancy G
shall be complied with.
b) Area above 750 m2 shall be fitted with Automatic sprinkler and/or automatic fire alarms system along
with portable fire extinguishers.
In addition to the general provisions covered under Chapter 4, the following requirements for Occupancy H
shall be complied with.
In addition to the general provisions covered under Chapter 4, the following requirements for the
occupancy group shall be complied with.
All hazardous occupancies shall be installed with Automatic Fire Alarm and Sprinkler System. CO2 or foam
or dry chemical extinguishing system shall be installed as per direction of the Authority.
4-6
Chapter 5
Specific Requirements for Various Occupancies
Fire detection and fire fighting arrangements shall be installed as and where directed and approved by the
Authority.