Manual 37615B SPM-D2-10 - Synchronizing Unit

SPM-D2-10/X & SPM-D2-10/XN


The SPM-D2-10/X & SPM-D2-10/XN controller outputs can be configured for the following signals and may re-
quire the use of an external jumper between terminals.

Versions

NOTE
Only one controller output may be configured as three-step controller.

- Three-step controller via relay manager


- Control of n/f: Parameter "f control type" = THREESTEP
n+/f+ = Relay connected to terminals 45/46
n-/f- = Relay connected to terminals 47/48
- Control of V: parameter "V control type" = THREESTEP
V+ = Relay connected to terminals 45/46
V- = Relay connected to terminals 47/48

- Analog controller output


- Control of n/f: Parameter "f control type" = ANALOG
Current output (mA) = no external bridge/jumper necessary
Voltage output (V) = external bridge/jumper between 8/9
Connect the Controller to terminals 9/10
- Control of V: Parameter "V control type" = ANALOG
Current output (mA) = no external bridge/jumper necessary
Voltage output (V) = external bridge/jumper between 11/12
Connect the controller to terminals 12/13

- PWM controller output


- Control of n/f: Parameter "f control type" = PWM
PWM output = external bridge/jumper between 8/9
Connect the controller to terminals 9/10

Connection of the controllers

Setting: 'THREESTEP' (three-position controller)


max. 250 Vac
B A

Relay output

The relay has to be decoupled.

Figure 4-14: Controller - SPM-D2-10/X & XN - three-position controller

Terminal Description Amax


45 2.5 mm²
raise Speed / Frequency controller
46 2.5 mm²
or
47 2.5 mm²
lower Voltage controller
48 2.5 mm²

© Woodward Page 19/68