Electronic Instrumentation
Pair, triad and quad - 300V - 105°C - PLTC - UL 13
Alarm and Fire Detection Systems
Applications
Electronic instrumentation, analog and digital signal circuits (4-20mA). Fire-
detection alarm systems
Features
Temperature rating: 105ºC maximum.
Voltage rating: 300V.
Construction requirements: As per UL 13 Type PLTC and UL 2250 Type ITC.
Fire Requirements: As per UL 1685.
Conductor requirements: As per ASTM B8, Class B.
Description
Conductor: Annealed electrolytic copper, 7-wire strading, class B.
Insulation: PVC.
Identification:
- Pair:
- Triad:
AI MILIAR
- Quad:
Lay length: 50 mm (20 twists/m).
Unshielded pair: Polyester tape wrap.
Shield: Aluminium-polyester tape helical wrap plus tinned-copper drain-wire
conductor, 7-wire stranding, class B.
Sheath: Red PVC, fire-retardant, sunlight-resistant.
Stripping: Polyamide ripcord under the sheath.
Outstanding Features
AI MILIAR ®
Unshielded pair
Direct burial Alarm and Fire Special Marking Sequentially Fire-retardant Hydrocarbon-
Marked resistant
Optionals
Insulation: High-density polyethylene, UL Listed PLTC.
Armour: Zinc-plated steel served-wire helical armour or aluminium interlock armour
plus red PVC sheath; fire-retardant; sunlight-resistant. These cables are UL
certified for direct earth burial.
1 WWW.MARLEW.COM.AR These specifications are provided as references and could be changed without previous notice.
AI MILIAR ®
Electronic Instrumentation
Pair, triad and quad - 300V - 105°C - PLTC - UL 13
Alarm and Fire Detection Systems
Alternatives
Construction requirements: As per ICEA S 73-532 (300V and 600V), British
Standard 5308, EN 50288-7 and NBR 10300.
Materials: These data are relevant to the standard version of this cable. Other
solutions can be made to order based on the different materials and construction
alternatives described in the technical information appendix.
Installation
Assembly: Minimum bend radius is 7xOD (unarmoured versions) and 12xOD
(armoured versions).
Maximum pulling tension: 5daN/mm2 on copper conductors. Wire-armoured
cables can withstand 10daN/mm2 on the armour wires.
Assembly temperature: 5ºC or higher.
AI MILIAR
Sequentially marked
sheath.
AI MILIAR ®
Shielded quad
Electrical Characteristics
Electric resistance at 20ºC in DC Ohm/km 35.78 35.78 22.78 22.78 14.25 14.25 8.94 8.94 5.63 5.63
Mutual capacitance between pF/m 98 180 85 165 112 210 109 203 121 228
conductors
Characteristic impedance Ohm 76 41 88 50 66 35 68 37 62 33
Mutual inductance between uH/km 588 588 641 641 544 544 553 553 522 522
conductors
2 WWW.MARLEW.COM.AR These specifications are provided as references and could be changed without previous notice.
AI MILIAR ®
Electronic Instrumentation
Pair, triad and quad - 300V - 105°C - PLTC - UL 13
Alarm and Fire Detection Systems
AI MILIAR
Shielded triad 16 18 AI 6200 6.7 78 AI 6200 H 6.7 10.8 246
Shielded triad 14 18 AI 6300 8.3 116 AI 6300 H 8.3 12.5 318
Shielded triad 12 18 AI 6800 9.3 159 AI 6800 H 9.3 13.5 382
Shielded quad 20 22 AI 9000 5.7 50 AI 9000 H 5.7 9.3 187
Shielded quad 18 20 AI 9100 6.5 70 AI 9100 H 6.5 10.6 234
Shielded quad 16 18 AI 9200 7.5 101 AI 9200 H 7.5 11.7 286
Shielded quad 14 18 AI 9300 9.0 146 AI 9300 H 9.0 13.2 364
Shielded quad 12 18 AI 9800 10.7 214 AI 9800 H 10.7 14.9 469
3 WWW.MARLEW.COM.AR These specifications are provided as references and could be changed without previous notice.