Type Code Legend for Configured Transfer Switches

Start Circuit Wires


( 2, 3 ) or N = None

G = Standard Generac
C = Closed transition Exerciser Options:
H = H-100 or G-100 compatible C = CPU Control is Selected
M = MPS S = Standard Exerciser W / Logic Control
D = Deluxe Exerciser W / Logic Control
Number of Poles N = None (HTS, MTS)
( 2, 3 or 4 )
Transfer Switch Enclosure
(See Note 3)
Amperage Rating
(See Note 1)
Accessories
(Y / N)

G T S 0 4 0 W - 2 A 2 L S N C N
Contactor Type Instrument Package
W = W-type available for 100 - 400 Amps (Y/N)
N = WN-type available for 600 - 2600 Amps
Y = Y-type available for 105 - 200 Amps System Control option:
B = Bypass Isolation type C = CPU Control
C = Closed Transition Voltage Code L = Adjustable Logic Control
(See Note 2) T = Adj. Logic Control with TTN function (GTS)
N = None (HTS, MTS)
Note 1:
Switch amperage rating is
displayed value multiplied by 10
e.g. 040 = 400 amps
260 = 2600 amps

Note 2:
Voltage Code:
A = 120 / 240 VAC (Single Phase)
G = 120 / 208 VAC (Three Phase - Wye)
J = 120 / 240 VAC (Three Phase - Delta)
K = 277 / 480 VAC (Three Phase - Wye)
L = 600 VAC (Three Phase - Wye)
M = 110 / 220 VAC (Single Phase)
N = 115 / 200 VAC (Three Phase -Delta)
P = 100 / 200 VAC (Three Phase - Delta) (Adjustable to 240V)
R = 231 / 400 VAC (Three Phase - Wye) (Adjustable to 380V or 416V)
S = 480 VAC (Three Phase - Wye)
X = Full Capacity All Voltages (Only with Direct Excitation)

Note 3:
Enclosure:
A = NEMA 1
B = NEMA 12
C = NEMA 3R
D = NEMA 12 W / Instrument Pkg.
E = NEMA 4 - Painted Mild Steel
F = NEMA 4X - Stainless Steel
P/N 0603550SSD REV. A