Professional Documents
Culture Documents
Pattern 2: Mass Sizing For Floor, Wall, or Ceiling in Indirect Sun
Pattern 2: Mass Sizing For Floor, Wall, or Ceiling in Indirect Sun
side. In other words, the sunlit side is isolated from 8”-thick brick 1
the living space. 12”-thick brick 1
This pattern is useful for isolated sun spaces and 8”-thick water wall 1
greenhouses. The storage wall may have high and
low vents or be unvented, as shown, without affect-
ing the values in the table. Example: You are considering adding an attached
The performance of the wall improves with solar greenhouse. The primary purpose of the
thickness up to about 18 inches but is not very greenhouse will be growing plants. The greenhouse
sensitive to variations in thickness within normal structure should therefore be isolated to avoid excess
buildable ranges. For brick walls, higher density humidity in the living space.
bricks (with water absorption of less than 6 percent) As the table shows, 1 square foot of 8-inch
are recommended over bricks of lower density. brick, l2-inch concrete, or 8-inch water wall (water
Note that the mass surface area refers to the area of containers) for each square foot of glazing will con-
the sunlit side only. veniently provide all of the required thermal mass.
around this mass material so that heat may be gained 8”-thick brick 2
by the living space from either side of the partial wall 6”-thick concrete 2
or from all sides of the water containers. Water containers 7 gal per sq ft of glazing
This pattern may represent a freestanding
masonry wall or a series of water containers.
The mass is assumed to be in full sun for at ing rather than growing. You'd like the sun space to
least 6 hours. As with Pattern 4, the wall thicknesses be open to the adjacent kitchen. Will a 3-foot high
listed are not very sensitive to variations, and the by 20-foot-Iong room divider constructed of 8-inch
wall surface area listed is for one side of the wall brick provide sufficient thermal mass?
only. Water containers are listed in the table at right
The area of the room divider exposed to direct
as gallons per square foot of glazing.
sunlight is 60 square feet. According to the tab1e,
Example: You plan to add a sun space with 160 square the room divider alone will account for only 30
feet of south-facing glazing. Unlike the example in square feet of glazing. You will probably need to
Pattern 4, however, you plan to use the space for liv- employ a Pattern 1 brick floor as well.
Lighting 19
Proper lighting around the home is important for safety, for reading, for Light and Seeing 528
working, for atmosphere, for the long-term health of your eyes, and now Light Sources 530
for economy and the environment. In order to understand why different Lamp Shapes and Bases 532
light sources and intensities are recommended for different applications,
Residential Lighting
you need to understand the relationships between light and seeing. Guidelines 534
Light Sources lists the efficiencies and color characteristics of more than
Meet the Code 538
30 incandescent, fluorescent, high-intensity-discharge, and light-emitting
diode (LED) lamps for use in and around the home.
Lamp Shapes and Bases illustrates the incredible variety of bulb shapes
and bases available today.
Perhaps the most useful section in this chapter is Residential Lighting
Guidelines, adapted from a publication of the California Lighting
Technology Center, designed to aid builders in complying with California’s
rigorous 2005 energy code.
Finally, we provide you with a checklist to make sure your lighting
design and techniques meet the code.
527
Light and Seeing
Light Units Light Measurements
The relationship between lighting units is displayed
in the illustration at right. A point light source with Illuminance =
a strength (candlepower) of 1 candela results in an 1 foot-candle =
1 lumen/sq ft
illuminance of 1 foot-candle, or 1 lumen per square
foot. Because a sphere of radius 1 foot has a surface
area of 12.57 square feet, the total light output is
1 foot
12.57 lumens.
Illumination levels are usually given in foot-
candles, although lumens per square foot is equiva- Source of
candlepower
lent. Total lamp output is always given in lumens. 1 candela
The intensity of light falling on a surface is
the illuminance. The intensity of light given off or
reflected by a surface is its luminance. For non-light- Illuminance Luminance
A B
emitting surfaces,
Luminance = illuminance × reflectivity
Example: What is the luminance of a surface of
reflectivity 0.50 when illuminated at an intensity of
Surface reflectivity = R
100 foot-candles? Luminance = illuminance × reflec- B=RxA
tivity = 100 footcandles × 0.50 = 50 footcandles
528 LIGHTING
Glare Glare Guidelines
An area within the visual field that has sufficient Luminance
luminance to cause either discomfort or a reduction Compared Areas Ratio, Max
in visual acuity is an area of glare. Direct glare is illu- Task to adjacent area 3 to 1
mination direct from a light source, such as a window Task to a remote dark surface 10 to 1
or exposed lamp. Reflected glare is light which has Task to a remote light surface 0.1 to 1
been reflected from a shiny or glossy surface, usually Window to adjacent wall 20 to 1
within the task area. For optimum visual comfort, the Task to any area within visual field 40 to 1
luminance of the task should be slightly greater than
the luminance of the surround. The table at right lists
maximum recommended luminance ratios.
are required to limit the arc current. Excluding the 1,400W sulfur 100
tiniest lamps, efficiencies range from about 70 to LED White, available 10–90
90 lumens per watt, including ballast power. Strong White, experimental to 150
points include long lamp life, low operating cost,
and low operating temperature. Compact fluores-
cent lamps (CFLs) are rapidly replacing incandes-
Lamp Efficiencies
cent lamps in residential applications.
High-intensity discharge (HID) lamps 4,000
emit light directly from electric arcs through metal
vapor. Color rendition is inappropriate for resi-
dential applications, but efficiencies range up to
3,000
144 lumens per watt.
Light Output, lumens
530 LIGHTING
Characteristics of Some Commercially Available Lamps
Color Output, Power, Lumens
Type Description Temp, °K CRI Lumens Watts per Watt
Incandescent A19, frosted, 25 watt 2,900 — 357 25 14
A19, frosted, 40 watt 2,900 — 460 40 12
A19, frosted, 60 watt 2,950 — 890 60 15
A19, frosted, 75 watt 3,000 — 1,210 75 16
A19, frosted, 100 watt 3,050 — 2,850 150 18
12V quartz-halogen, 20 watt 2,900 — 300 19.4 15
12V quartz-halogen, 45 watt 3,100 — 980 44.5 22
Fluorescent Dulux® EL, 11 watt 3,000 82 600 11 54
Dulux EL, 19 watt 3,000 82 1,200 19 63
Deluxe warm white 2,950 74 1,550 30 52
Warm white 3,000 52 2,360 30 79
Designer 3000K 3,000 67 3,300 40 83
Royal white 3,000 80 2,400 30 80
Octron® 3100K 3,100 75 3,650 40 91
White 3,450 57 1,900 30 63
Octron 3500K 3,500 75 3,650 40 91
Natural white 3,600 86 3,050 55 55
Designer 4100K 4,100 67 8,800 95 93
Octron 4100K 4,100 75 3,650 40 91
Deluxe cool white 4,100 89 2,100 40 53
Lite white 4,150 48 4,300 60 72
Cool white 4,200 62 3,150 40 79
Design 50 5,000 90 1,610 30 54
Daylight 6,300 76 1,900 30 63
HID Mercury, Warmtone 3,300 52 3,700 100 37
Mercury, Brite White Deluxe 4,000 45 3,650 100 37
Mercury, clear 5,900 22 3,380 100 34
Metal halide, clear 3,200 65 6,800 100 68
Metal halide, coated 3,900 70 16,000 250 64
High-pressure sodium, Lumalox 2,000 22 8,850 100 89
High-pressure sodium, Unalox 1,900 20 11,700 150 78
LED A19, warm white 3,000 — 43 1.3 33
A19, cool white 8,000 — 42 1.3 32
PAR38, warm white 3,000 — 182 4.5 40
PAR38, pure white 5,500 — 230 5.0 46
Chandelier, warm white 3,000 — 52 2.4 22