Professional Documents
Culture Documents
CA Expansion Tanks
Taco CA Expansion tanks are full acceptance Captive Air expansion tanks that provide
separation of air and water. Tough, durable and long lasting. The Taco CA is available in a
variety of sizes and capacities to fit your application.
-2-
Applications
Air Control Through Not maintaining minimum pres- fixed temperature reducing the
Pressure Control sures will create air problems. pressure reduces the amount of air
All hydronic systems operate Water contains a certain amount that can be dissolved or entrained.
under a variable amount of pres- of entrained air. If this air comes For example at 100˚F and 80 PSIA
sure. For closed systems the pres- out of solution at lower pressures, water can contain 8% air by vol-
sure varies primarily due to the it can increase corrosion rates of ume. At 100˚F and 20 PSIA the
expansion of water as it is heated metals within the system. In addi- percentage decreases to 2%.
or cooled. As the water is heated tion, air can form pockets at the
the pressure increases and as top of pipes and coils of terminal The conclusion is that air is least
the water is cooled the pressure units. These air pockets can actually soluble in water at lowest pres-
decreases. restrict or block flow in a hydronic sure. Air separators should there-
piping system. This is referred to as fore be located at these points.
The pressure in a closed system “air locking”. The lowest pressure in a system
varies between a minimum and a is typically at the expansion tank,
maximum. The minimum is con- Figure 1 shows a solubility curve since this is the point of no pres-
trolled by the fill valve and the for air in water. Note that at a sure change and the location of the
initial fill pressure of the expan- fill valve. Therefore, the general
18%
the tank. 6% 90
80
70
4% 60
50
PSIA
40
30
If the pressure is not maintained
2%
20
10
32 50 75 100 125 150 175 200 212
between these limits then the sys- TEMPERATURE (DEGREE F)
FAN COIL
TACO
CIRCULATOR
TACO
TWIN TEE
TACO
AIR SEPARATOR
TACO PUMP
TACO TACO
MULTI-PURPOSE SUCTION
TACO
VALVE DIFFUSER
EXPANSION
TANK
BOILER
-3-
Applications
FAN COIL
TACO
CIRCULATOR
TACO
TWIN TEE
TACO 4900
AIR SEPARATOR
TACO PUMP
TACO
TACO SUCTION
MULTI-PURPOSE DIFFUSER
VALVE
TACO
EXPANSION
TANK
CHILLER
For multi-story buildings this is The solubility of air in water at this is to install additional air separators
important. If the system pressure pressure and 40˚F is 45%. At the at upper levels of the building. A
is not maintained above atmo- top of the building, assuming, 10 psi hydronic system can have multiple
spheric at the top of the building positive pressure, the solubility is air separators, but should have
then not only will air come out only 4%. only one expansion tank. These air
of solution, but air can actually be separators should be high efficiency
drawn into the system. This will Obviously air will come out of separators similar to Taco’s 4900.
result in loss of system perfor- solution at the top of the building See Taco Catalog #400-1.4 for
mance with areas of low and no with the expansion tank and air additional information.
flow in this portion of the system. separator located at the bottom. By
“over pumping”, to maintain 40 psi Another solution is to locate the
For high rise buildings this is espe- at the top of the building, the solu- expansion tank and air separator at
cially important. Frequently the bility of air goes back up to 10%. the top of the building where the
expansion tank, air separator and pressure is the lowest and the air
fill valve are located at lower levels For pumps located at upper levels
of the building this is even more is least soluble in water. This will
of the building. At upper levels air require the running of a dedicated
will come out of solution as the problematic. Pumps in these loca-
tions can actually be attempting to line from the top of the building to
pressure decreases. This is similar the suction of the system circulat-
to what divers experience as the pump air. For centrifugal pumps the
point at which their head falls off ing pump. This will also reduce the
“bends”. One solution, which size of the expansion tank since the
designers and maintenance per- is in the range of 3% to 5% air vol-
ume in water. difference between the initial fill or
sonnel learned over time, was to minimum pressure and relief valve
“over pump” the system through Maintenance personnel and field or maximum pressure can be larger.
high pump heads. This increased engineers report many instance of
the pressure at upper levels of the poor pump performance due to Not maintaining maximum pres-
building and forced air back into unknown causes. A large portion sure can result in several problems,
the system. of these mysterious problems have including burst diaphragm or blad-
turned out to be secondary pumps ders in partial expansion captive
For example, in a 50 story building, air tanks, weeping relief valves and
the static pressure at the bottom located above expansion tanks.
A better solution to “over pumping” failure of components
of the system could be 250 psi.
-4-
Applications
Causes of over system pressuriza- The tank must now be sized for the This permanent separation allows the
tion can be undersized expansion initial fill volume plus the volume of tank to be precharged on the air side
tanks, water logged air cushion any expanded water. This makes the of the bladder to the minimum oper-
plain steel expansion tanks and tank much larger. ating or fill pressure. This eliminates
burst diaphragms or bladders in the initial water volume needed to
As air is released through air vents,
Captive Air tanks. compress the air from atmospheric
the air cushion in the tank can be
pressure to the system minimum (fill)
absorbed into the system fluid leaving
Pressure Control Through pressure. This allows the bladder
the tank water logged and eliminating
Air Control expansion tank to be charged to the
the system pressure control provided
Many systems designed in the past fill pressure without the introduc-
by the plain steel tank. When this
and some designed today, attempt to tion of system fluid offering a siz-
occurs the expanded water volume
control air by means of an old style able reduction in the required tank
must now seek a new outlet which is
air cushion plain steel tank and air volume (see figure 5 A). The use of
normally the relief valve or thru the
vents in the piping. a Captive Air expansion tank often
rupture of one of the other system
allows the reduction in required tank
componets.
The air cushion plain steel tank uses sizes up to 80% compared to air
a tank filled with water and an air A better solution is to use a Captive cushion or plain steel tanks.
cushion at the top of the tank for Air tank. In a Captive Air tank the air
During system operation any expanded
water to expand into as it is heated. is held captive by the use of a blad-
water, in the diaphragm or bladder,
The initial atmospheric air in the der or diaphragm with the expanded
compresses the precharge air to the
tank must be initially compressed to water being held on one side of the
maximum pressure. This compressed
the fill pressure. This requires an ini- diaphragm or bladder and the air on
air cushion then pushes the fluid back
tial charge or fill of water to accom- the other side.
into the system when it contracts.
plish this as shown in Figure 4.
Figure 4
Plain steel pressurization process -5-
Applications
This can be seen in the following System fill pressure of 10 psig, This is a difference of greater than
example problem. System volume of 3000 gallons, 81% reduction in required tank size
System: Chilled water at 40˚F with steel piping system, System fill
System volume: 3000 gallons pressure of 65 psig and a 90 psig Another advantage of the perma-
System piping : Steel maxiumum operating pressure. nent separation of air and water in
a Captive Air tank is to eliminate
The ASHRAE formula for plain Sizing a plain steel expansion tank the absorption of air back into the
steel expansion tank sizing is: [(v2/ v1) – 1] – 3aΔt water that is found in air cushion
Vt = Vs or plain steel tanks.
[(v2/ v1) – 1] – 3aΔt
Vt = Vs (Pa/ P1) – (Pa/ P2)
(Pa/ P1) – (Pa/ P2) Location of Expansion Tank
For Location of the expansion tank in
Where the system will also affect system
Vs = 3000 gallons
vt = volume of expansion tank, gal performance.
v1 = .01602 ft3/lb (40˚F)
vs = volume of water in system, gal v2 = .01613 ft3/lb (100˚F)
The expansion tank is the point of
t1 = lower temperature, ˚F Pa = 14.7 psia
no pressure change in the system.
P1 = 65psig +14.7psia = 79.7psia
t2 = higher temperature, ˚F This can be seen from Boyle’s Law:
P2 = 90psig+14.7 psia = 104.7 psia
Pa = atmospheric pressure, psia a = 6.5x 10-6 in/in˚F for steel
P1V1/T1 = P2V2 /T2
P1 = pressure at lower Dt = 60˚F
temperature, psia
If the temperature (T1 and T2) and
P2 = pressure at higher Vt = 388.83 gallons
temperature, psia volume (V1 and V2) are constant
with the pump on or off, then the
v1 = specific volume of water at Sizing of a Captive Air
lower temperature, ft3/lb pressure (P1 and P2) must also
expansion tank
remain constant.
v2 = specific volume of water at
higher temperature, ft3/lb Pa= P1
Therefore the point of connection
a = linear coefficient of thermal
expansion, in./in. -˚F of the expansion tank to the system
[(v2/ v1) – 1] – 3aΔt
Vt = Vs is a point of no pressure change.
= 6.5 x 10 in./in. -˚F for steel
-6
Typically located at the suction side
1 – (Pa/ P2)
= 9.5 x 10-6 in./in. -˚F for copper of the system pumps.
For
DT= (t2 - t1), ˚F Vs = 3000 gallons
V1 = .01602 ft3/lb (40˚F)
Chilled water sizing example: V2 = .01613 ft3/lb (100˚F)
Sizing a plain steel tank for a chilled Pa = 79.7psia (due to tank precharge)
water system with a temperature P1 = 65psig + 14.7psia = 79.7psia
range of 40˚F to 100˚F (ambient P2 = 90psig + 14.7psia = 104.7psia
temperature). a = 6.5x 10-6in/in F for steel
Dt = 60˚F
Vt = 71.55 gallons
-6-
Applications
To prevent air from being drawn Therefore, the general rule of not affect the pressure in the tank.
into the system the pressure in the thumb in hydronic systems is that If there are multiple tanks in the
system must be everywhere above “Expansion tanks should be locat- system then the pump head will
atmospheric pressure. ed on the suction side of pumps.” affect the pressure in the tank.
The pump will be able to transfer
The location of the expansion Multiple expansion tanks will cause water from one tank to the other
tank relative to the pump suction pressure problems in systems. The depending on the pressure dif-
will then determine if the system location of the expansion tank in ference generated by the pump
is everywhere above atmospheric the system is the point of no pres- between the tanks.
pressure. This can be seen in the sure change. The pump head does
following figures.
TACO
CHILLER
in the system the pressure is above
atmospheric.
Figure 7 – Expansion tank located on suction side of pump
-7-
Applications
FAN COIL
Figure 8 is a system with two
expansion tanks. The point of no
TACO
EXPANSION
pressure change will be some-
TACO
TANK
where between the two tanks.
CIRCULATOR
TACO
TWIN TEE POINT OF NO PRESSURE CHANGE
IS BETWEEN EXPANSION TANKS
Therefore, the general rule of
TACO
thumb in hydronic systems is that
MULTI-PURPOSE
VALVE
TACO
“Multiple expansion tanks in a
TACO PUMP
AIR SEPARATOR
system is not recommended”
since unstable pressure conditions
TACO
EXPANSION
will result.
TANK
CHILLER
Types of Expansion Tanks
Figure 8 – Multiple expansion tanks in system Air Cushion Plain Steel
Expansion Tank
FAN COIL
TACO
CIRCULATOR
TACO
tional and industrial applications
MULTI-PURPOSE
VALVE
TACO
for the control of pressure in
TACO PUMP AIR SEPARATOR
hydronic systems. The air cushion
plain steel tank uses a tank filled
with water and an air cushion at
CHILLER
-8-
Applications
the air is “recycled” to provide a Partial Acceptance Captive Air Partial Acceptance
cushion in the expansion tank, this Diaphragm Expansion Tank Captive Air Bladder
system is called an “Air Control” Taco CX partial acceptance Expansion Tank
system. As noted previously the air Captive Air diaphragm expansion Taco CBX partial accep-
cushion in the tank can be deplet- tanks are applied in commercial, tance bladder Captive
ed due to absorption of air into institutional and Air expansion tanks are
the water. It can also be depleted industrial applica- applied in commercial,
by loosing air through air vents in tions for the con- institutional and indus-
the piping. Care must also be taken trol of pressure in trial applications for the
to insure that piping between the hydronic systems. control of pressure in
air separator and the plain steel Diaphragm tanks use hydronic systems. CBX
expansion tank is pitched at least a diaphragm to per- bladder tanks use a field replace-
3 degrees (Figure 9) to facilitate manently separate able bladder to permanently sepa-
the migration of captured air back the air and water. rate the air and water.
into the expansion vessel. Systems In a diaphragm tank the air is held This permanent separation allows
with plain steel expansion tanks captive by the use of a diaphragm the tank to be precharged on the
must not have automatic air vents with the expanded water being air side to the minimum operat-
installed as this will lead to the loss held on one side of the diaphragm ing or fill pressure. This eliminates
of the expansion tank air cushion. and air on the other. many gallons of water to compress
if air is lost in the tank then the This permanent separation allows atmospheric pressure air in an air
tank will become water logged. the tank to be precharged on the cushion or plain steel tank to the
With a water-logged expansion air side to the minimum operat- fill pressure. This allows the reduc-
tank, the expanded water must ing or fill pressure. This eliminates tion in Captive Air expansion tank
now seek a new outlet which can many gallons of water to compress sizes of up to 80% compared to air
be the relief valve on one of the atmospheric pressure air in an air cushion or plain steel tanks.
major components. cushion or plain steel tank to the
As note previously the tank must fill pressure. This allows the reduc- In a bladder tank the bladder is not
be sized for the expansion of the tion in Captive Air expansion tank attached to the tank wall like a dia-
water in the system plus the ini- sizes of up to 80% compared to air phragm tank. Rather it is suspend-
tial charge of water to compress cushion or plain steel tanks. ed inside the tank very much like a
atmospheric air in the tank to In a diaphragm tank the diaphragm balloon. Expanded water flows into
the fill pressure. This makes the is attached to the tank wall and the inside of the bladder. Air is on
tank much larger. The tank is also cannot move inside the tank. As a the outside of the bladder between
subject to corrosion with the pres- result the tank has a limited accep- the bladder and the tank. As a
ence of air and oxygen in the tank. tance volume. In addition, there is result no water is in contact with
some water in contact with the the tank wall minimizing corrosion
Applications tank wall providing an opportunity In a partial acceptance bladder tank
• Smaller systems
for corrosions. the bladder is of limited accep-
• Lower cost tance volume and does not stretch.
• Ceiling mounted to Applications As a result, if there is an overpres-
save floor space • Smaller systems
sure condition in the system the
• Lower cost bladder will burst, again, very much
like a balloon.
Applications
-9- • Larger systems
• Lower cost
Applications
Full Acceptance Captive Air This permanent separation allows the tank. As a result no water is in
Bladder Expansion Tank the tank to be precharged on the contact with the tank wall minimiz-
Taco CA full acceptance blad- air side to the minimum operat- ing corrosion.
der Captive Air expansion tanks ing or fill pressure. This eliminates
are applied in many gallons of water to compress In a full acceptance bladder tank
commercial, atmospheric pressure air in an air the bladder is of full acceptance
institutional cushion or plain steel tank to the volume and can expand to the full
and industrial fill pressure. This allows the reduc- volume of the tank. As a result, the
applications tion in Captive Air expansion tank bladder will not burst if the system
for the control sizes of up to 80% compared to air experiences an overpressure con-
of pressure cushion or plain steel tanks. dition.
in hydronic In a bladder tank the bladder is
systems. CA not attached to the tank wall like Applications
• Larger systems
tanks use a a diaphragm tank. Rather it is sus-
field replace- pended inside the tank very much • Systems where reliability
able bladder to like a balloon. Expanded water and lower maintenance
costs are important
permanently flows into the inside of the blad-
separate the der. Air is on the outside of the
air and water. bladder between the bladder and
-10-
Selection Procedure
-11-
Selection Procedure
EXAMPLE 2
Problem:
Select an expansion tank for a
Calculation of Net system expansion –
heating water installation. The
mechanical room and expansion Net System Expansion
tank are located on the roof. First = Vs {[(v2/ v1)-1] – 3 α Δt}
cost is a major consideration.
System piping copper.
= 1000 {[(.01692/.01602) -1] – 3 (9.5x10-6) 200}
Conditions:
System volume 1,000 gallons. = 1000 {.05047}
Minimum temperature = 40 F
Maximum temperature = 240 F = 50.48 gallons
Building height = 50 ft
Relief Valve at boiler = 50 psig Calculate required tank volume –
Sizing of a Captive Air
expansion tank [(v2/ v1) – 1] – 3aΔt
Vt = Vs
Pa= P1 1 – (Pa/ P2)
[(v2/ v1) – 1] – 3aΔt
Vt = Vs Vt = 1000 {[(.01692/.01602) -1] – 3 (9.5x10-6) 200}/ (1 – 24.04/64.7)
1 – (Pa/ P2)
= 80.32 gallons
v1= .01602 ft3/lb (40˚F)
Because first cost is a major consideration select a partial acceptance
v2= .01692 ft3/lb (240˚F)
Captive Air bladder tank model CBX425. This tank is lower first cost
α=9.5x 10-6in/in F for copper piping than a full acceptance Captive Air tank. However, it is subject to a
Δt=200 F burst bladder under over pressure conditions. Acceptance volume of
Determine minimum pressure – the tank is 61 gallons. The volume of the tank is 112 gallons.
Minimum pressure equals static
pressure plus 5 psi positive pressure
at top of the building (assume 10 ft
of static pressure).
P1
= 10ft x .434 psi/ft + 5 psi
(positive pressure) + 14.7 psia
= 24.04 psi
Maximum pressure equal the
relief valve setting
P2 = 50 psig +14.7 psia
= 64.7 psia
-12-
Product Data
TANK H B D R SHIPPING
VOLUME HEIGHT DIAMETER DIAMETER RADIUS WEIGHT SYSTEM
Model CONNECTION
Number
GAL. LIT. INCH MM INCH MM INCH MM INCH MM LBS. Kg SIZE
CA90-125 23 90 29-1/8 740 16 406 20 508 4-1/4 108 120 55 1" NPT (25.4mm)
CA140-125 37 140 40-1/8 1019 16 406 20 508 4-1/2 114 195 88 1" NPT (25.4mm)
CA215-125 57 215 58-7/8 1495 16 406 20 508 4-1/2 114 290 132 1" NPT (25.4mm)
CA300-125 79 300 57-3/4 1467 20 508 24 610 5 127 320 145 1-1/2" NPT (38.1mm)
CA450-125 119 450 77-3/8 1965 20 508 24 610 5 127 400 181 1-1/2" NPT (38.1mm)
CA500-125 132 500 85-3/4 2178 20 508 24 610 5 127 420 191 1-1/2" NPT (38.1mm)
CA600-125 158 600 71-7/8 1826 24 610 30 762 6-1/4 159 460 209 1-1/2" NPT (38.1mm)
CA700-125 185 700 80-5/8 2048 24 610 30 762 6-1/4 159 525 238 1-1/2" NPT (38.1mm)
CA800-125 211 800 89-7/8 2283 24 610 30 762 6-1/4 159 590 268 1-1/2" NPT (38.1mm)
CA900-125 238 900 73-1/8 1857 30 762 36 914 7-7/16 189 690 313 1-1/2" NPT (38.1mm)
CA1000-125 264 1000 79 2007 30 762 36 914 7-7/16 189 790 358 1-1/2" NPT (38.1mm)
CA1100-125 291 1100 85-1/4 2165 30 762 36 914 7-7/16 189 865 392 1-1/2" NPT (38.1mm)
CA1200-125 317 1200 91 2311 30 762 36 914 7-7/16 189 940 426 1-1/2" NPT (38.1mm)
CA1300-125 344 1300 97 2464 30 762 36 914 7-7/16 189 980 445 1-1/2" NPT (38.1mm)
CA1400-125 370 1400 103 2616 30 762 36 914 7-7/16 189 1020 463 1-1/2" NPT (38.1mm)
CA1500-125 396 1500 73-3/8 1864 40 1016 48 1219 10-15/16 278 1200 544 1-1/2" NPT (38.1mm)
CA1600-125 422 1600 76-5/8 1946 40 1016 48 1219 10-15/16 278 1380 626 1-1/2" NPT (38.1mm)
CA1800-125 475 1800 83-1/2 2121 40 1016 48 1219 10-15/16 278 1515 687 1-1/2" NPT (38.1mm)
CA2000-125 528 2000 90-3/8 2296 40 1016 48 1219 10-15/16 278 1650 748 1-1/2" NPT (38.1mm)
CA2500-125 660 2500 107-1/8 2721 40 1016 48 1219 10-15/16 278 1838 834 1-1/2" NPT (38.1mm)
CA3000-125 792 3000 94-1/8 2391 44 1118 54 1372 11-7/16 291 2025 919 2" NPT (50.8mm)
CA4000-125 1056 4000 120-3/4 3067 44 1118 54 1372 11-7/16 291 2400 1089 2" NPT (50.8mm)
CA5000-125 1320 5000 150-1/4 3816 44 1118 54 1372 11-7/16 291 3100 1406 2" NPT (50.8mm)
CA7500-125 1980 7500 128-3/4 3270 62 1575 72 1829 11-1/2 292 3850 1746 3" NPT (76.2mm)
CA10000-125 2640 10000 158-1/4 4020 62 1575 72 1829 11-1/2 292 4500 2041 3" NPT (76.2mm)
System
Charging Valve Enclosure R Connection
(SEE TABLE)
Lifting Ring
H
Lifting Ring
B
D
-13-
Mechanical Specifications
-14-
Mechanical Specifications
-15-
Mechanical Specifications
H. Select system relief valve K. Clean and flush glycol system N. Feed glycol solution to system
capacity so that it is greater before adding glycol solution. through make-up line with
than make-up pressure Refer to Section 15189. pressure regulator, venting
reducing valve capacity. system high points.
Select equipment relief L. Feed glycol solution to system
valve capacity to exceed through make-up line with O. Perform tests determin-
rating of connected pressure regulator, venting ing strength of glycol and
equipment. system high points. water solution and submit
written test results.
I. Pipe relief valve outlet to M. Feed glycol solution to system
nearest floor drain. through make-up line with
pressure regulator,
J. Where one line vents several venting system high points.
relief valves, make cross Set to fill at ___ psi.
sectional area equal to sum
of individual vent areas.
-16-
Notes
-17-
Notes
-18-
Notes
-19-
Taco quality
through & through
Taco Inc., 1160 Cranston Street. Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.taco-hvac.com