You are on page 1of 2

HR12-580WL

Specification
Cells Per Unit 6
Voltage Per Unit 12
Capacity 580W@15min-rate to 1.67V per cell @25℃
Weight Approx. 47.0 Kg (Tolerance±1.5%)
Internal Resistance Approx. 3.8 mΩ
Terminal F12(M8)
Max. Discharge Current 1550A (5 sec)
The HR (High Rate) series Valve Regulated
Short Circuit Current 3150A
Lead Acid (VRLA) battery is designed for heavy
Design Life Could Reach 15 years load discharge applications with 15 years
Recommended Maximum Charging 46.5 A
design life in float service. By using strong
Current grids and specially designed active material
C10 146.2AH the HR series is with lower I.R, lower self
Reference Capacity
C20 155.0AH discharge rate, high power, and longer service
Standby Use Voltage 13.6 V~13.8 V @ 25℃ life performance. Generally the HR series
offers 30% more power output than the standard
Cycle Use Voltage 14.6 V~14.8 V @ 25℃
range. Suitable for high power standby and
Discharge: -20℃~60℃ cycling situation, such as UPS, datacenter,
Operating Temperature Range Charge: 0℃~50℃ electric tools et al.
Storage: -20℃~60℃
Normal Operating Temperature Range 25℃±5℃
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charge batteries before using.

Container Material A.B.S. UL94-HB, UL94-V0 Optional.

Dimensions
340 173 Φ16 Length 340±2mm (13.4 inches)
M8
Width 173±2mm (6.81 inches)
Height 280±2mm (11.0 inches)
5

Total Height 287±2mm (11.3 inches)


Terminal Value
280
287

40.5

M5 6~7 N*m
M6 8~10 N*m
M8 10~12 N*m
265
F12 Terminal Unit: mm

Constant Current Discharge Characteristics : A (25℃)

F.V/Time 5MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN


1.60V 5 4 1 .1 4 6 3 .3 4 16 .7 3 3 1.1 26 5.9 1 9 4 .9 1 1 2 .1 8 3.0
1.67V 5 0 0 .7 4 3 4 .7 3 91 .0 3 1 3.8 24 8.1 1 8 5 .8 1 0 6 .8 7 9.0
1.70V 4 7 9 .9 4 1 9 .4 3 76 .9 3 0 4.1 23 8.6 1 8 0 .6 1 0 3 .7 7 6.6
1.75V 4 5 3 .2 3 9 8 .4 3 53 .9 2 8 9.9 23 2.1 1 7 5 .5 1 0 2 .0 7 4.9
1.80V 4 2 6 .3 3 7 7 .4 3 30 .8 2 7 5.4 22 5.2 1 7 0 .1 1 0 0 .0 7 3.1
1.85V 3 9 7 .8 3 5 4 .9 3 06 .6 2 5 9.7 21 7.3 1 6 3 .8 9 7.6 7 0.9
Constant Power Discharge Characteristics : WPC (25℃)

F.V/Time 5MIN 8MIN 10MIN 15MIN 20MIN 30MIN 60MIN 90MIN


1.60V 9 65 838 75 9 60 6 48 9 3 59 2 07 154
1.67V 9 02 794 71 9 58 0 46 0 3 46 1 99 148
1.70V 8 74 775 70 1 56 9 44 8 3 40 1 96 145
1.75V 8 36 746 66 7 54 9 44 1 3 34 1 95 144
1.80V 7 98 717 63 2 52 9 43 4 3 29 1 94 142
1.85V 7 60 688 59 8 50 9 42 8 3 23 1 93 141
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
HR12-580WL
Discharge Characteristics Curve Charge Characteristic Curve For Standby Use
Temperature:25℃ Constant Voltage Charge Characteristics
(V/cell)
Charge Charge Charging
Volume Voltage Current
2.16 % (V)
130
Terminal Voltage (V)

2.00
120 2.40 0.1
110 Charged Volume
100
1.84 2.30 0.08
90
80 Charging voltage
1.68 70 2.20 0.06
76.6A
60 After 50% Discharge
463.3A 194.4A 112.1A After 100% Discharge
1.52 50 2.10 0.04
40
30
1.36 2.00 0.02
20
10 Charging Current
0
1 2 3 4 5 10 15 20 25 30 40 50 60 70 80 90 0 0
0 4 8 12 16 20 24 28 32 36 40
Discharge Time(min) Charging Time(h)

Cycle Life In Relation To Depth Of Discharge Relationship Between Charging Voltage And Temperature

120 2.70

100
2.60

Charge Voltage (v )
Cycle use
2.43~2.47VPC@25℃
80
Capacity(%)

2.50
60
100% 80% 50%
DOD DOD DOD 2.40
40

20
2.30
Standby use
2.27~2.30VPC@25℃
0 2.20
200 400 600 800 1000 1200 1400
-20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃
Number of Cycles Temperature (℃)

Temperature Effects On Capacity Storage Characteristics

/Ce ll
580 W
Capacity (% )
Capacity (% )

Temperature (℃)
Storage Time(months)

Effect Of Temperature On Long Term Life Life Characteristics Of Standby Use

25 Testing conditions: floating charge


Temperature: 25℃(77℉)
120
Lift Expectancy (y ears)

20

100
15
80
Capacity(%)

10
60

5 40

20
0
0 10 20 30 40 50 0
0 2.5 5.0 7.5 10.0 12.5 15.0
Temperature (℃) Life expectancy (years)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

SHENZHEN RITAR POWER CO.,LTD. Add: 10th Floor, Tower C, 1st Building, Software Industry Base, No.81, Xuefu Road, Nanshan District, Shenzhen,
Guangdong, China 518057
URL: www.ritarpower.com Tel: +86-755-33981668/83475380 Fax: +86-755-83475180 E-mail: sales@ritarpower.com Version 17A-0