RL2-300(2V300Ah)

Specification
Cells Per Unit 1
Voltage Per Unit 2
Nominal Capacity 300Ah@10hour-rate to 1.80V per cell @25℃
Weight Approx. 16.5 Kg (Tolerance±3.0%)
Internal Resistance Approx. 0.72 mΩ
Terminal F10(M8)
Max. Discharge Current 1500A (5 sec)
Short Circuit Current 2910A RL series is a general purpose battery with
Design Life 20 years (Float charging) 20 years design life in float service. It meets
with heavy duty grids, thicker plates, special
Max. Charging Current 60 A additives and advanced AGM valve regulated
C1 165.0AH technology, the RL series battery provides
C3 232.2AH consistent performance and long service life.
Reference Capacity
C5 261.5AH The new grid design effectively reduces the
C10 300.0AH internal resistance, which provides higher
2.27 V~2.30 V @ 25℃ specific energy density and excellent high
Standby Use Voltage Temperature Compensation: -3mV/℃/Cell rate discharge characteristics. It is suitable
for communications back-up power and
2.43 V~2.47 V @ 25℃ EPS/UPS applications.
Cycle Use Voltage Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: -0℃~50℃
Storage: -20℃~60℃
Normal Operating Temperature Range 25℃±5℃
ISO 9001 ISO 14001 OHSAS 18001
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge be stored for up to 6 months at 25℃ and then recharging
than 3% at 25℃.Please charge batteries before using.

Container Material A.B.S. UL94-HB, UL94-V0 Optional. MH 28539 G4M20206-0910-E-16

Dimensions
Φ20 Length 170±2mm (6.69 inches)
M8
Width 150±2mm (5.91 inches)
Height 330±2mm (13.0 inches)
5
150

Total Height 342±2mm (13.5 inches)


342
330

Terminal Value
M5 6~7 N*m
M6 8~10 N*m
102
M8 10~12 N*m
170
F10 TERMINAL Unit: mm

Constant Current Discharge Characteristics : A (25℃)


F.V/Time 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR
1.60V 470.9 296.1 183.3 112.9 84.6 68.1 56.6 38.0 31.6
1.65V 441.2 284.2 177.0 109.3 82.0 66.3 55.1 37.6 31.3
1.70V 413.2 271.7 171.3 105.7 79.8 64.5 53.7 37.0 30.8
1.75V 384.5 259.7 165.0 102.0 77.4 62.8 52.3 36.5 30.4
1.80V 355.1 248.2 158.7 98.3 75.0 61.0 51.0 35.9 30.0
1.85V 294.6 213.8 142.3 90.1 69.3 56.7 47.6 33.7 28.2
Constant Power Discharge Characteristics : WPC (25℃)
F.V/Time 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR
1.60V 823.2 537.8 344.5 213.9 161.6 130.8 109.1 74.3 62.2
1.65V 782.7 521.7 334.6 208.1 157.3 127.7 106.7 73.6 61.5
1.70V 744.0 503.6 325.7 202.4 153.7 124.7 104.3 72.6 60.7
1.75V 702.5 486.3 315.7 196.2 149.7 122.0 102.0 71.8 60.0
1.80V 657.8 469.5 305.4 190.1 145.7 118.9 99.7 70.7 59.3
1.85V 553.6 408.4 275.6 175.2 135.3 110.9 93.3 66.5 55.9
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
The battery must be fully charged before the capacity test. The C 10 should reach 95% after the first cycle and 100% after the third cycle.
RL2-300(2V300Ah)
Discharge Characteristics Curve Charge Characteristic Curve For Standby Use
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.40
2.16 Charge Volume

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 Charge Voltage 2.30

Charge Volume (%)


2.00

80 0.10 2.20
1.84
0.1C 0.05C
1.68
0.25C 0.17C 60 0.06 2.10
0.55C After 50% Discharge
1C After 100% Discharge
1.52 40 0.04 2.00

1.36 20 0.02 1.90


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 1.80
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life In Relation To Depth Of Discharge Relationship Between Charging Voltage And Temperature

120 2.70

100 2.60
Charge Voltage (v ) Cycle use
80 2.43~2.47VPC@25℃
Capacity(%)

2.50

60
100% 50% 30%
DOD DOD DOD 2.40
40

20 2.30
Float charging
2.27~2.30VPC@25℃
0 2.20
400 800 1200 1600 2000 2400 2800
-20 -10 0 10 20 30 40 50
Number of Cycles Temperature (℃)

Temperature Effects On Capacity Storage Characteristics


120 100

100 0℃
0 .1 C A 80
Capacity (% )
Capacity (% )

80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect Of Temperature On Long Term Life Charge Characteristic Curve For Standby Use

25 Testing conditions: float charging Temperature: 25℃(77℉)


120
Lift Expectancy (y ears)

20
100

15 80
Capacity(%)

60
10

40

5
20

0 0
0 10 20 30 40 50 0 4 8 12 16 20 24
Temperature(℃) Life expectancy (years)
(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.