HT12-200(12V200Ah)

Specification
Cells Per Unit 6
Voltage Per Unit 12
Nominal Capacity 200Ah@10hour-rate to 1.80V per cell @25℃
Weight Approx. 63.0 Kg (Tolerance±3.0%)
Internal Resistance Approx. 4.0 mΩ
Terminal F16(M8)/F12(M8)
Max. Discharge Current 2000A (5 sec)
Design Life 15 years (Float charging)
Max. Maximum Charging 60 A
Current HT series is High-temperature series battery
C3 153.9AH with 15 years design life in float service. It
Reference Capacity
C5 174.0AH meets with IEC, JIS, BS, GB/T and YD/T
C10 200.0AH standards. With advanced AGM valve
C20 210.0AH regulated technology and high purity raw
13.6 V~13.8 V @ 25℃ material, the HT series battery maintains
Standby Use Voltage
Temperature Compensation: -3mV/℃/Cell high consistency for better performance and
14.6 V~14.8 V @ 25℃ reliable standby service life. It is designed
Cycle Use Voltage for using under high temperature conditions.
Temperature Compensation: -4mV/℃/Cell
Discharge: -20℃~60℃
Operating Temperature Range Charge: -10℃~60℃
Storage: -20℃~60℃
Normal Operating Temperature Range 35℃±5℃
RITAR Valve Regulated Lead Acid (VRLA) batteries can
be stored for up to 6 months at 25℃ and then recharging
Self Discharge is recommended. Monthly Self-discharge ratio is less
than 3% at 25℃.Please charge batteries before using. ISO 9001 ISO 14001 OHSAS 18001

Container Material A.B.S. UL94-HB, UL94-V0 Optional.

Dimensions
Φ20 Length 522±2mm (20.6 inches)
205 M8 Width 240±2mm (9.45 inches)
522 240
Height 219±2mm (8.62 inches)
5

Total Height 224±2mm (8.82 inches)


Terminal Value
140
224
219

M5 6~7 N*m
M6 8~10 N*m
M8 10~12 N*m
F10 Terminal
Unit: mm

Constant Current Discharge Characteristics : A (25℃)


F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 723.1 601.5 388.9 226.6 136.0 107.4 85.2 72.3 49.4 41.3 21.7
1.65V 696.4 584.2 378.5 221.3 132.3 104.6 83.1 70.5 48.9 40.9 21.5
1.70V 651.4 554.2 362.9 215.2 128.8 101.4 80.8 68.8 48.3 40.2 21.3
1.75V 606.6 523.1 350.3 208.9 124.6 98.8 79.0 67.3 47.6 39.8 21.0
1.80V 558.8 486.7 338.6 201.2 121.2 97.2 77.2 65.8 46.9 39.4 20.8
1.85V 454.1 409.3 292.4 181.1 111.7 90.5 72.4 61.5 44.2 37.1 20.2
Constant Power Discharge Characteristics : WPC (25℃)
F.V/Time 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 723.1 601.5 388.9 226.6 136.0 107.4 85.2 72.3 49.4 41.3 21.7
1.65V 696.4 584.2 378.5 221.3 132.3 104.6 83.1 70.5 48.9 40.9 21.5
1.70V 651.4 554.2 362.9 215.2 128.8 101.4 80.8 68.8 48.3 40.2 21.3
1.75V 606.6 523.1 350.3 208.9 124.6 98.8 79.0 67.3 47.6 39.8 21.0
1.80V 558.8 486.7 338.6 201.2 121.2 97.2 77.2 65.8 46.9 39.4 20.8
1.85V 454.1 409.3 292.4 181.1 111.7 90.5 72.4 61.5 44.2 37.1 20.2
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
The battery must be fully charged before the capacity test. The C 10 should reach 95% after the first cycle and 100% after the third cycle.
HT12-200(12V200Ah)
Discharge Characteristics Curve Charge Characteristic Curve For Standby Use
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.40
2.16 Charge Volume

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 Charge Voltage 2.30

Charge Volume (%)


2.00

80 0.10 2.20
1.84
0.1C 0.05C
1.68
0.25C 0.17C 60 0.06 2.10
0.55C After 50% Discharge
3C 2C 1C After 100% Discharge
1.52 40 0.04 2.00

1.36 20 0.02 1.90


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 1.80
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life In Relation To Depth Of Discharge Relationship Between Charging Voltage And Temperature
2.70
120

100 2.60

Charge Voltage (v )
Cycle use
80 2.43~2.47VPC@25℃
Capacity(%)

2.50

60
100% 80% 30%
DOD DOD DOD 2.40
40

2.30
20
Float charging
2.27~2.30VPC@25℃
0 2.20
200 400 600 800 1000 1200 1400
-20 -10 0 10 20 30 40 50

Number of Cycles Temperature (℃)

Temperature Effects On Capacity Storage Characteristics


120 100

100 0℃
0 .1 C A 80
Capacity (% )

Capacity (% )

80 0 .2 C A
60
10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
2 .0 C A
3 .0 C A 20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect Of Temperature On Long Term Life Life Characteristics Of Standby Use


Testing conditions: float charging Temperature: 25℃(77℉)
20
120
Lift Expectancy (y ears)

16 100

80
12
Capacity(%)

60
8
40

4
20

0 0
0 10 20 30 40 50 0 3 6 9 12 15 18
Temperature(℃) Life expectancy (years)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

HENGYANG RITAR POWER CO.,LTD. Add: No.1 Huagong Road, Songmu Industrial Park, Shigu District, Hengyang, Hunan, China 421001