Professional Documents
Culture Documents
Specification
Cells Per Unit 1
Voltage Per Unit 2
Nominal Capacity 1000Ah@10hr-rate to 1.8V per cell @25℃
Weight Approx. 77.0 Kg (Tolerance±2%)
Internal Resistance Approx. 0.45 mΩ
Terminal F10(M8)
Max. Discharge Current 3800A (5 sec)
Design Life 20 years (floating charge)
Maximum Charging Current 200.0A
C24 1113AH
C48 1250AH
C240 1318AH
2.25 V~2.30 V @ 25℃
108
Float Charging Voltage
Temperature Compensation: -3mV/℃/Cell
2.37 V~2.40 V @ 25℃
Cycle Use Voltage
Temperature Compensation: -4mV/℃/Cell Φ20
680
645
M8
Discharge: -40℃~60℃
5
Operating Temperature Range Charge: -20℃~50℃
Storage: -40℃~60℃
Normal Operating Temperature Range 25℃±5℃
Valve Regulated Lead Acid (VRLA) batteries
F10 TERMINAL
can be stored for up to 6 months at 25℃ and
Self Discharge then recharging is recommended. Monthly Length 233±1mm (9.17 inches)
Self-discharge ratio is less than 2% at 25℃. Width 210±1mm (8.27 inches)
Height 645±1mm (25.4 inches)
Please charged batteries before using.
Total Height 680±1mm (26.8 inches)
Container Material A.B.S. UL94-HB, UL94-V0 Optional. Torque Value 10~12 N*m
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.50
Charge Volume
2.16
Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
120 2.60
100
2.50
Charge Voltage (v )
Cycle use
80
2.37~2.40VPC@25℃
2.40
Capacity(%)
60
100% 80% 50% 30%
DOD DOD DOD DOD 2.30
Float charging
40
2.25~2.30VPC@25℃
2.20
20
2.10
0 1000 2000 3000 4000 5000 6000 7000
-20 -10 0 10 20 30 40 50
100 0℃
0 .1 C A 80
0 .2 C A
Capacity (% )
Capacity (% )
80
60 10℃
60
20℃
1 .0 C A 40
40℃ 30℃
40
20
20
0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)
Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
25 2.20
2.15
Battery Voltage (V)
Lift Expectancy (y ears)
20
2.10
2.05
15
2.00
10
1.95
1.90
5
1.85
0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100