You are on page 1of 2

OPzV12-200(12V200Ah)

OPzV series is Valve Regulated Lead Acid battery that adopts immobilized
GEL and Tubular Plate technology to offer high reliability and performance.
The Battery is designed and manufactured according to DIN standards and
with die-casting positive grid and patented formula of active material OPzV
series exceeds DIN standard values with more than 18 years floating design
life at 25 ℃ and It is the best solution for cyclic use under extreme operating
conditions.
Specification
Cells Per Unit 6
ISO 9001 ISO 14001 OHSAS 18001
Voltage Per Unit 2
Nominal Capacity 200Ah@10hr-rate to 1.80V per cell @25℃
Weight Approx. 69.5Kg (Tolerance±3.0%) MH 28539 G4M20206-0910-E-16

Internal Resistance Approx. 5.5 mΩ


Terminal F14(M8)
Dimensions Unit: mm
Max. Discharge Current 2000A (5 sec)
Design Life 20 years (floating charge) 521 268

Max. Charging Current 40.0 A

225
C3 157.0AH

220
C5 176.0AH
Reference Capacity
C10 200.0AH
C20 214.2AH
Φ18
205
13.5 V~13.8 V @ 25℃ M8
Float Charging Voltage
Temperature Compensation: -3mV/℃/Cell

5
14.2 V~14.4 V @ 25℃
Cycle Use Voltage
129

Temperature Compensation: -4mV/℃/Cell


Discharge: -40℃~60℃
Operating Temperature Range Charge: -20℃~50℃ F14 Terminal
Storage: -40℃~60℃
Normal Operating Temperature Range 25℃±5℃
RITAR Valve Regulated Lead Acid (VRLA) batteries can Length 521±2mm (20.5 inches)
be stored for up to 6 months at 25℃ and then recharging
Self Discharge Width 268±2mm (10.6 inches)
is recommended. Monthly Self-discharge ratio is less
than 2% at 20℃.Please charged batteries before using. Height 220±2mm (8.66 inches)
Total Height 225±2mm (8.86 inches)
Container Material A.B.S. UL94-HB, UL94-V0 Optional. Torque Value 10~12 N*m

Constant Current Discharge Characteristics : A(25 ℃)


F.V/ Time 10min 15min 30min 1h 2h 3h 5h 8h 10h 20h
1.60V 327.3 262.7 173.9 119.8 74.20 57.51 37.81 25.46 21.40 11.24
1.65V 306.9 248.3 167.7 116.2 71.80 56.26 37.00 25.06 21.00 11.03
1.70V 280.6 231.4 160.3 112.3 69.40 54.39 36.20 24.66 20.60 10.82
1.75V 256.9 213.2 149.8 106.4 67.00 52.32 35.19 24.26 20.40 10.71
1.80V 223.9 190.7 139.2 100.0 63.80 50.03 33.99 23.66 20.00 10.50
1.85V 186.2 165.1 124.0 91.14 59.00 46.71 32.38 22.66 19.14 10.05

Constant Power Discharge Characteristics : WPC(25℃)


F.V/ Time 10min 15min 30min 1h 2h 3h 5h 8h 10h 20h
1.60V 513.4 426.0 319.6 227.0 141.8 110.7 73.60 50.33 42.20 22.16
1.65V 500.3 417.5 311.2 221.5 137.8 108.8 72.19 49.52 41.60 21.84
1.70V 474.8 401.2 300.5 215.6 134.0 105.5 70.79 48.92 41.00 21.53
1.75V 430.8 372.5 283.3 205.0 130.0 102.1 69.18 48.12 40.60 21.32
1.80V 370.6 337.6 265.8 193.6 124.2 97.57 66.77 46.92 39.80 20.90
1.85V 306.5 283.2 238.7 177.4 115.2 91.34 63.75 44.91 38.20 20.06
(Note) The above characteristics data are average values obtained within three charge/discharge cycle not the minimum values.
The battery must be fully charged before the capacity test. The C 10 should reach 95% after the first cycle and 100% after the third cycle.
OPzV12-200(12V200Ah)
Discharge Characteristics Curve Charge Characteristic Curve for Cycle Use(IU)
Temperature:25℃(77℉) Temperature:25℃(77℉)
(V/cell)
120 0.14 2.50
Charge Volume
2.16

Charge Voltage (VPC)


Charge Current (CA)
Terminal Voltage (v )

100 0.12 2.40

Charge Volume (%)


2.00 Charge Voltage
80 0.10 2.30
1.84
0.1C 0.05C
0.25C 0.17C 60 0.06 2.20
1.68 After 50% Discharge
0.50C
After 100% Discharge
1C 40 0.04 2.10
1.52

1.36 20 0.02 2.00


Charge Current
0
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 0.00 1.90
min h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28

Discharge Time Charging Time(h)

Cycle Life in Relation to Depth of Discharge Relationship Between Charging Voltage and Temperature
120 2.60

100
2.50

Charge Voltage (v )
Cycle use
80
2.37~2.40VPC@25℃
Capacity(%)

2.40

60
100% 80% 50% 30%
DOD DOD DOD DOD 2.30
Float charging
40
2.25~2.30VPC@25℃
2.20
20

2.10
0 -20 -10 0 10 20 30 40 50
800 1600 2400 3200 4000 4800 5600
Number of Cycles Temperature (℃)

Temperature Effects on Capacity Storage Characteristics


120 100

100 0℃
0 .1 C A 80
Capacity (% )
Capacity (% )

80 0 .2 C A
60 10℃

60
20℃
1 .0 C A 40
40℃ 30℃
40

20
20

0 0
-20 -10 0 10 20 30 40 50 0 2 4 6 8 10 12 14 16 18 20 22 24
Temperature (℃) Storage Time(months)

Effect of Temperature on Long Term Life Relationship of OCV And State of Charge(20℃)
25 2.20

2.15
Battery Voltage (V)
Lift Expectancy (y ears)

20
2.10

2.05
15

2.00

10
1.95

1.90
5
1.85

0 1.80
0 10 20 30 40 50 0 10 20 30 40 50 60 70 80 90 100
Temperature(℃) State Of Capacity (%)

(Note) All above information shall be changed without prior notice, Ritar reserves the right to explain and update the latest information.

HENGYANG RITAR POWER CO.,LTD. Add: No.1 Huagong Road, Songmu Industrial Park, Shigu District, Hengyang, Hunan, China 421001
URL: www.ritarpower.com Tel: +86-734-8595528 Fax: +86-734-8595518 E-mail: sales@ritarpower.com Version 20A-0