You are on page 1of 12

Substation

Transformers
Safety Notes for Operation

Do not make any connections that are not authorized by the RTE® Nameplate and
Connection Diagram.

Do not energize a transformer without properly made ground connections.

Poor ground connection may result in personal injury or damage to the


equipment.

Do not tamper with interlocks, alarm and control circuits.

Do not remove hand holes, accessories, or cover plates while the transformer is
energized.

Do not change connections of a transformer that is under excitation.

Do not operate the tap changer while the transformer is energized from either the H.V. or
L.V. side.

Injury or death may result as well as damage to the equipment.

Do not break the seal of a de-energized transformer without first reducing the internal
pressure to zero.

Do not lift or move a transformer without adequate equipment and precautions.

See section under “Handling of Transformer”.

© 1989 Cooper Power Systems


Table of Contents
Instructions for Liquid-Immersed Transformers

Page
Receiving, Handling, and Storage ............................................................... 1
Installation ................................................................................................... 1
Location ....................................................................................................... 1
Connections ......................................................................................... 2
Final Inspection .................................................................................... 2
Accessories .................................................................................................. 3
Liquid Level, Temperature, and Pressure-Vacuum Gauges .................. 3
Pressure Relief Device, Winding Temperature Gauge, and Fans ......... 4
Bushings ............................................................................................... 5
Tap Changer.......................................................................................... 7
Insulating Liquid ................................................................................... 7
Maintenance ................................................................................................ 7
Filtering ................................................................................................. 8
Spare Parts and Service .............................................................................. 8
Applicable Standards ................................................................................... 8
R-Temp® Fluid .............................................................................................. 8

These instructions do not purport to cover all details or variations in


equipment, nor to provide for every possible contingency to be met in
connection with installation, operation, or maintenance. Should further
information be required or ff particular problems arise which are not
covered in this manual, contact a factory representative at:

Cooper Power Systems


RTE Power Products
1319 E. Lincoln Avenue
Waukesha, Wisconsin 53186-5374
Telephone: (414) 549-5000
Telex: 260203
Fax: (414) 549-1488
Instructions for
Liquid Immersed Transformers

Receiving many as necessar y to distribute the weight


uniformly.
Inspection and Acceptance To pull, attach pulling eyes to the holes in the base
RTE® substation transformers are shipped com- at either end of the transformer.
pletely assembled, tested, and filled with insulating Do not attach pulling lines to moldings or other
liquid, ready for immediate service. sheet metal parts of the transformer.
NOTE: It is important that a thorough inspection
of the transformer be made before it is Storage
removed from a truck or railroad car. Whenever possible, the transformer should be
stored at its permanent location.
1. Insure that all parts listed on the bill of The insulating liquid should be at its proper level
lading are present. and the gas space pressurized to approximately two
2. Before unloading the transformer, PSIG.
make an inspection to detect any signs
Then it should be tightly sealed so that no moisture
of damage or mishandling of the trans- or air can enter the tank. Periodic inspection should
former and any accessory parts which determine that the pressure gauge does not remain
may have been shipped separately. at zero, and proper liquid level is maintained at all
3. If any damage from rough handling is times.
detected or shortages are noticed,
The transformer should not be stored in the pres-
write a brief description on the freight ence of corrosive gases such as chlorine, etc.
bill. Nor mally, the transformer is Exterior surfaces of the transformer should be
shipped FOB point of manufacture, maintained against rust and corrosion.
and it is the customer’s responsibility
to file a claim against the carrier. If the Before placing a transformer into service after an
extended storage time, check the dielectric strength
transformer was shipped FOB destina- of the insulating liquid, fans, alarm, and controll
tion, notify the RTE Power Products circuits.
Customer Service Group. RTE Power
Products will, with the inspector’s
report, take the necessary steps to file Installation
a claim against the carrier. Location
The transformer should be located on a concrete
pad of sufficient strength to support the weight of
Handling the unit. The pad must be level. The location of the
For unloading, lifting hooks are provided near the transformer, whether indoor or outdoor, should pro-
top of the transformer case. Cable pull angles vide for adequate accessibility, ventilation and ease
should not be over 30° from vertical. Otherwise, of inspection for the unit. The transformer should be
spreaders should be used to hold the lifting cables at least 24 inches from any obstruction. Location in
apart to avoid any bending of the structure or lifting areas of corrosive chemicals should be avoided.
hooks. RTE substation transformers are built to operate at
WARNING: Do not attempt to lift the transformer altitudes up to 3300 feet at 30° average and 40° C
by placing a continuous loop of cable maximum ambient, unless otherwise specified.
or chain around the unit or lifting Before operating a standard transformer at higher
lugs. altitudes, contact RTE Power Products.
If the transformer cannot be lifted by crane, it may Adequate ventilation must be provided. When
be skidded or moved with rollers. When jacking a installed indoors, the room air inlets should be
transformer to insert rollers underneath it, insure located at floor level; the air outlets should be locat-
that at least two jacks are used and that two adja- ed as high as the room will permit. The number and
cent corners are raised simultaneously and evenly size of the air inlets depends upon the rating of the
to avoid warping the base. Jacks may be placed transformer. In general, about 20 square feet each
only at the corners of the transformer base. of inlet and outlet area should be provided for each
1000 kVA of transformer capacity. If the ventilation
Do not place jacks under cooler assemblies, valves, system is adjustable, it should be locked perma-
or sheet metal parts. When using rollers, use as nently open to avoid overheating of the transformer
1
in case of an operator’s error. 4. Current transformer circuits, if supplied, have
secondaries either shorted or connected
Connections through their load.
5. Tap changer is operative and properly posi-
WARNING: Do not change connections on a tioned.
transformer that is under excita- 6. The correct transformer ratio exists for units
tion; do not make any connec- furnished with internal terminal board.
tions, except as authorized by the 7. There is no grounding of windings that are
nameplate or connection diagram. not intended to be grounded. A 1000 volt
megger test is recommended.
Connections must be made without placing undue 8. There is continuity in all windings.
stress on the bushing terminals. Conductors should 9. The dielectric strength of the insulating liquid
be securely fastened in place and supported prop- is 30 kV minimum when new. (Refer to
erly, with allowance for expansion and contraction. section for “Testing Insulating Liquid” in this
manual.)
Make sure that the tap connection is proper for the 10. The neutral and ground connections have
required voltage. Changes in tap connections must been properly made.
be done ONLY with the transformer high voltage
and low voltage circuits completely “DE-ENER- If an internal inspection is required, assure that:
GIZED”. 1. There is no evidence of moisture.
2. All available bolted connections are tight.
Transformers equipped with an internal terminal 3. There have been no shifting of any parts or
board are normally shipped with the higher voltage any other damage.
connected, unless otherwise specified by the
customer. The external inspection should determine that:
1. All scratches have been painted.
A secure, effective low resistance ground is essen- 2. The bushings are clean.
tial for protection. The transformer must be ground- 3. The accessories are operative.
ed permanently by connecting a heavy ground 4. There are no tools, or other objects, left on
cable to the ground pad located at the bottom of top of the transformer.
the tank. If the transformer is designed for operation 5. The liquid level is correct.
in a solidly grounded neutral system, the neutral 6. The transformer holds positive pressure.
connection should be solidly and permanently 7. The manhole covers are tightly bolted.
grounded with minimum resistance. 8. All protective covers are closed and bolted
tight.
WARNING: A poor ground may result in per- 9. The mechanical relief device is reset.
sonal injury or damage to the
equipment. Important Notes:
1. Whenever it is necessary to open a liquid-
Lightning arresters are recommended for every filled transformer, insure that the liquid
transformer installation. Arresters of proper rating temperature is higher than the outside air
should be located as close as possible to the trans- temperature. Otherwise, moisture condensa-
former terminations. tion may occur internally, which could lead to
the failure of the transformer.
When alarm contacts are supplied with the trans- 2. Before breaking the seal of any hand hole,
former accessories, a connection box may be manhole, or bushing hole, bleed internal
provided to facilitate the ter mination of the pressure to zero by means of the air test
customer’s cable or conduit. valve. Only authorized persons should be
permitted on top of the transformer and every
Final Inspection precaution should be taken to avoid dropping
The final inspection can be done in three major objects into the transformer. Workers should
steps: Electrical, Internal and External. not have anything in their pockets, such as
Electrical inspection should determine that: pens, pencils, coins, etc.; and their clothing
1. All external connections have been made should not have loose metal buttons, badges,
properly. (phasing of connections to terminal buckles, etc. Wrist watches should also be
bushings, etc.) removed.
2. All connections are tight and secure. 3. Seals should not be broken when there is
3. All accessory contact circuits are operational. fog, rain, or snow, or if there is any evidence
of condensation on the transformer tank. It
should be remembered that a very slight
amount of moisture in the transformer may
decrease the dielectric strength of the liquid to

2
a dangerous level. perature sensitive element is mounted in a leak-
proof well, permitting removal of the thermometer
without lowering the oil level. The device is fur-
Accessories nished with an additional red pointer to show the
Liquid Level Gauge highest temperature attained since the last reset. To
reset the maximum indicator, turn the knob in the
center of the dial.
The thermometer can be furnished with an SPDT
contact for high temperature alarm and an SPST
contact for fan circuit energizing or low temperature
alarm. For wiring and contact settings, refer to the
connection diagram furnished with the transformer.

Pressure-Vacuum Gauge

A liquid level indicator is provided to aid in the sys-


tematic inspection of the transformer under load. It
consists of a float-arm inside the tank, an indicating
pointer and a magnetic coupling between the two
across a liquid tight separation.
The gauge may be furnished with SPDT (Single
Pole Double Throw) alarm contacts, to give a
remote annunciation of low liquid level. For contact The pressure-vacuum gauge indicates whether the
wiring and terminal points, see the accessory con- gas space in the tank is under positive or negative
nection diagram furnished with the transformer. pressure. The pressure will vary depending on the
transformer temperature. If the transformer is
de-energized or operating under light load in low
Liquid Temperature Gauge ambients, the pressure may be negative.
NOTE: If the indicator reads zero and does not
change under any load condition, the transformer
should be checked for a possible leak in the seal.

* If sufficient air has been absorbed by the liquid


during shipment or storage, the transformer may
operate indefinitely in the vacuum range, depend-
ing upon the loading conditions. This, in itself, is
not cause for concern, provided the pressure
vacuum gauge does not remain on zero for
any length of time - an indication of a leak.

The unit may be equipped with a pressure vacuum


switch with two SPDT contacts for remote alarm on
positive and negative pressure. For wiring and
contact ratings, see diagram furnished with the
transformer.

When required, the pressure gauge is furnished in


The temperature gauge is furnished to indicate the combination with a pressure regulator that will
top liquid temperature in the tank in °C. The tem- automatically bleed off gas or add make-up air to

3
the tank if the pressure exceeds 7.0 PSIG positive perature gauge as optional equipment.
or 3.0 PSIG negative. The pressure regulator is fit- A temperature sensitive stem is mounted in a
ted with a valve and fitting to take gas samples or leakproof well, permitting removal of both the instru-
add make-up air (or nitrogen). ment and stem without lowering the liquid level. The
well is heated by both the surrounding liquid and a
Pressure Relief Device heater element which is energized from a current
transformer mounted inside the tank to simulate the
hot spot winding temperature gradient. The combi-
nation of the two temperatures is indicated on the
gauge. An additional red pointer is furnished to
show the highest temperature attained since the
last reset. The maximum indicator is resettable by
means of a push button through the bottom of the
dial bezel.
The gauge has one separate single pole, N.O. con-
tacts, and two SPDT (Single Pole Double Throw)
switches for fan control and alarm circuits. For
wiring the contact settings, refer to the connection
diagram furnished with the transformer.
The equipment is calibrated to indicate the hottest
spot of the transformer windings. All contacts are
factory set to operate at the temperatures shown in
the connection diagram.
If readjustment of the contacts is desired, consult
the factory for detailed instruction.

Substation transformers may be furnished with a


mechanical pressure relief device. The device is
mounted on the transformer cover. It consists of a
self-resetting, spring-loaded, diaphragm, and a Transformer Cooling Fans
mechanical operation indicator. Should the tank
pressure increase above that for which the device is
set, the gas pressure will lift the diaphragm, and let
the gas escape quickly. Immediately after the pres-
sure returns to normal, the diaphragm will reset and
reseal the transformer. A mechanical indicator will
protrude vertically, which must be reset manually to
indicate subsequent operations.

Contacts are optional. For wiring information, see


the accessory wiring diagram.

Winding Temperature Gauge

In order to increase the transformer load without


overheating the windings, a set of fans can be fur-
nished as an optional item.
Fan control consists of a contact on either the liquid
temperature gauge or the winding temperature
Transformers may be furnished with a winding tem- gauge (when furnished), and "Manual-Auto" control

4
switch. A starter contactor is used only when fan through the wall. The alternative means of gaining
capacity exceeds the alarm switch duty rating. access to the connections is through the manhole.
When reinstalling the bushing, cement a new gasket
For continuous run, the switch is turned to the in the gasket recess on the underside of the flange
“Manual” position. In the “Auto” position, the fans to insure that the gasket is properly seated in the
are controlled by the contacts on the temperature groove. A flat washer and lock washer should be
gauge. For contact and temperature settings, refer placed between the mounting nut and the flange.
to the auxiliary connection diagram. After the nuts are finger tight, each one should be
tightened to a torque of 60-inch pounds. (Plus 5,
WARNING: Fan guards are furnished and Minus 5) After completion, pressure test the trans-
installed for your protection. former.
Do not remove fan guards or A variety of bushings are available of the porcelain
probe with long objects into type, when it becomes necessary to bring leads
the fan. through the tank cover. Such bushings, when
required, will be described in supplementary leaflets
Refer to wiring schematic for control equipment forming a part of the complete instruction book.
supplied.

High Voltage Bushings Low Voltage Bushings

High voltage leads for ratings 2.4 kV and up are


normally brought through the case end wall using a
porcelain bushing. To prevent excessive mechanical
loading of the bushing, only flexible connections
should be made to the bushing terminal. The bush- Low voltage leads for ratings in the 1.2 kV Class are
ing should not be used as a structural member to normally brought through the tank wall using an
support other current carrying parts. indoor bushing. This is a cast resin or porcelain
Care must be taken in handling the bushing to avoid bushing.
cracking the porcelain, or damaging its surface. The bushing should not be used as a structural
Should it become necessary to replace a bushing member. As a rule, only flexible connection should
or its gasket, proceed as follows: be made to the air or liquid terminals of the bushing.
If, however, a “dead weight” connector load is to be
Vent the tank to the atmosphere through the air test supported by the bushing, a moment of 1200-inch
valve, until pressure is zero. Lower the liquid level to pounds, as determined by the moment arm from the
a point below the bushing level. Remove the nuts center of gravity of the load, perpendicular to a
and washers used to clamp the flange of the bush- plane passing through the underside of the metal
ing. Pull the bushing outward as far as necessary to flange, should be considered a maximum. Avoid
replace the gasket and/or to unfasten the cable con- rigid connections between the bushing and other
nection at bushing inner end. Only in rare bus supports to eliminate thermal expansion forces
circumstances will there be insufficient slack in the to the bushing.
cable leads to facilitate bushing replacement
If a bushing is damaged and leaking transformer
coolant, contact RTE Power Products for proper
repair procedures.

5
Removing and Replacing Removing
Bushings 1. Unscrew and remove the top terminal cap,
exposing the threaded stud end of the draw
lead cable. In some cases, the threaded stud
Bushing construction falls into two general cate- will be held by a pin which must also be
gories: “draw lead” type as represented by figure 1 removed.
and bottom-connected types with a fixed center
stud as represented by the low voltage bushing on 2. Fasten a pull wire, cord or rod to the stud in
page 5. order to guide the lead through the bushings
bore and prevent it from falling into the open-
The method for removing bushings will differ ing when the bushing is removed. (In some
depending upon the type of construction. The two cases, the lead will be of sufficient thickness
methods are dealt with separately in the written to be self supporting, and if so, this part of
material that follows. the procedure can be omitted).
Before any work commences, standard safety pre- 3. Remove the bushing mounting clamp nuts at
cautions must be observed which include: the tank to release the mounting clamp plate
and free the bushing for removal.
• De-energizing the transformer 4. Remove the bushing, guiding the draw lead
• Grounding all circuits to and from the trans- conductor and terminal stud through the base
former to discharge any stored energy and of the bushing.
prevent accidental re-energizing.
Replacing
• Locking “open” disconnect switches in the
supply lines to and from the transformer. Replacement draw lead type bushings can be
installed by following the removal procedure in
• If the transformer is under vacuum or reverse order.
pressure, this should be relieved.
The gasket under the bushing mounting flange and
• If the bushing to be removed is below the liq- the “top gasket” should be new or in good condition
uid level, lower the level sufficiently to to ensure a positive seal. The gasket mating sur-
prevent loss. faces must be clean and smooth.
• Store any liquid removed, that will be The threaded stud is keyed to the inside of the
returned to the transformer, in scrupulously bushing to prevent rotation while the terminal cap is
clean, dry, sealed containers that will protect being tightened. It is important to have the threaded
from the atmosphere and contaminants. stud correctly seated. This can be accomplished by
pulling the stud upwards, and turning it until it is
Removing and Replacing aligned and seated.
Draw Lead Type Bushings
Removing and Replacing Bottom
Connected Fixed Stud
Type Bushings
Removing
1. Remove inspection cover (man hole) nearest
to bushing, only after all precautions outlined
under “Removing and Replacing Bushings”
have been taken.
2. Unbolt the connections - usually flexible straps
- from the bottom end of the bushing stud.
3. Remove the bushing mounting clamp nuts at
the tank to release the mounting clamp plate
and free the bushing for removal.
4. Removing the bushing.

Replacing
Replacement bushings can be installed by follow-
ing the removal procedure in the reverse order.
The gasket under the bushing mounting flange
should be new, or in good condition, and the gas-
ket mating surfaces must be clean and smooth.

6
After installing and connecting the new bushing, Maintenance
replace the inspection opening cover, making cer-
tain the gasket is in good condition and the gasket Periodic Inspection
mating surfaces are clean and smooth. 1. External: Check the condition of the paint and
Return any liquid removed to the transformer and finish periodically, especially when the trans-
check for the correct level. former is exposed to inclement atmospheric
conditions. If weathering takes place, clean
A brief pressure test of the transformer at 5 PSI to the tank thoroughly and repaint with an RTE
confirm the integrity of the seals around all open- Power Products approved paint. Wipe off any
ings above the liquid level is recommended. A solu- insulating liquid that might have been spilled
tion of soap and water will give indication of a leak on the surface. Occasionally, inspect and
by the presence of bubbles. tighten all bolted joints and check for leaks.
2. Regularly inspect all gauges. The liquid level
De-Energized Tap Changer must remain normal, considering the tempera-
ture effect. Refill when samples have been
taken. Prolonged periods of zero pressure
could indicate a gas leak and should be
checked out. The liquid temperature should not
rise higher than the design value on the name-
plate, plus ambient temperature.
3. Liquid samples should be taken periodically
and analyzed as indicated under ”Sampling”. It
is recommended that you keep a log of the
test values to determine when reconditioning
or replenishing service is required.

Sampling Insulating Liquid


NOTE: A sample of the liquid should be taken when
the unit is warmer than the surrounding air to avoid
condensation of moisture on the liquid. Liquid
samples must be drawn from the sampling valve
located at the bottom of the transformer tank.
A clean and dry bottle is required. Rinse bottle
three times with the liquid being sampled. Make
sure liquid being sampled is representative of liquid
The tap changer provides a means of changing the in the unit.
voltage ratio of a de-energized transformer without
breaking the transformer seal. It is operated by Containers used for sampling liquid should be large
means of a rotatable handle located on the side of mouth glass bottles.
the transformer. The tap changer is normally pro- Test samples should be taken only after the liquid
vided with five positions, as indicated on the tap has settled for some time, varying from eight hours
changer dial plate and transformer instruction for a barrel to several days for a large transformer.
nameplate. Cold insulating liquid is much slower in settling.
WARNING: Do not operate the tap changer Liquid samples from the transformer should be
while the transformer is energized. taken from the sampling valve at the bottom of the
tank.
Insulating Liquid When sampling, a metal or non-rubber hose must
be used because oil dissolves the sulfur found in
The insulating liquid in RTE substation transform- rubber, and will prove harmful to the conductor
ers is either oil or R-Temp Fluid. When makeup liq- material in the transformer. When drawing samples
uid is required, use only approved fluids of the from the bottom of the transformer or large tank,
same type that is in the transformer. It is important sufficient liquid must first be drawn off to ensure
to maintain the proper liquid level in the transformer that the sample will be from the bottom of the tank,
at all times by periodically observing the liquid level and not the liquid stored in the sampling pipe.
gauge. In addition, the dielectric strength of the
insulating liquid must be maintained at a high
value. Testing Insulating Liquid
It is recommended that a sample be taken of the For testing the dielectric strength of insulating
liquid and tested within one week after energiza- liquids, follow the technique as specified by the
tion, and annually thereafter. American Society for Testing Materials in the

7
method entitled, “The Standard Method for Testing R-Temp Fluid-Filled
Electrical Insulating Oils” #D-877.
Transformers
If, at any time, the dielectric strength of the liquid
drops below 26 kV, it should be filtered until it tests Periodic maintenance tests should be performed on
at 26 kV or better. essentially the same schedule as would be used for
conventional mineral oil-filled transformers of similar
application. The same type of sampling techniques
Filtering Oil should be used. Basic recommended tests for R-
Oil or R-Temp fluid can be filtered by means of a fil- Temp fluid-filled transformers are dielectric strength,
ter press. The filter press is effective for removing all moisture content, and flash and fire point.
types of foreign matter, including finely divided car-
bon and small amounts of moisture. The purifier Dielectric Strength
equipment consists of a specifically proportioned fil- Although the transformer should operate satisfacto-
ter press, a positive volume gear pump, driving rily with a fluid dielectric strength of 22 kV, an R-
motor, combined drip pan and mixing tank, neces- Temp fluid dielectric strength below 25 kV is an indi-
sary piping, valves, strainer, gauges and a drying cation of excessive contamination. In this case, the
oven. R-Temp fluid should be replaced or filtered to
Filtration should be continued until the dielectric test remove the moisture or particulate contamination.
of the insulating liquid is 26 kV or better. The dielectric strength of R-Temp fluid should be
NOTE: When filtering R-Temp fluid, the filtering tested in accordance with ASTM D-877.
equipment must be free of contaminants and other
liquids. The presence of other liquids may alter the Flash and Fire Points
physical and electrical characteristics of the R-Temp Relatively small percentages (2-3%) of conventional
fluid. This could result in a lower fire point. transformer oil or other contaminants may substan-
tially reduce the flash and fire point of R-Temp fluid.
Spare Parts and Service If it is suspected that the fluid may have been
We suggest that you keep one set of gaskets for exposed to this type of contamination, the flash and
the hand hole and any gasket-type bushings used. fire point should be measured in accordance with
other renewal par ts may be ordered through ASTM D-92. A fire point lower than 300°C probably
Cooper Power Systems. When ordering parts or indicates some contamination by lower fire point
requesting service, give a complete description of material. If flash or fire points fall below the mini-
the par t or the problem to the Cooper Power mum values required, retrofilling may be required.
Systems representative and give the complete seri-
al number as listed on the nameplate. Drain and Refill
If it is necessary to drain and refill the transformer,
Applicable Standards special care should be taken to avoid the entrap-
ment of gas bubbles in the system. Sufficient time
should be allowed between refilling and energiza-
1. NEMA Publication TR-98, (Latest Issue) tion of the transformer to be sure that any gas
“Guide for Loading oil Immersed Power bubbles created during the process have been
Transformers with 65°C Average Winding dissipated.
Rise.” Request Section 419-0 for additional handling
2. ANSI Publication C57.93, (Latest Issue) guidelines for R-Temp fluid.
“Guide for Installation and Maintenance of
Oil Immersed Transformers.”
3. IEEE Publication #64, (Latest Issue) “Guide
for Acceptance and Maintenance of
Insulating Oil in Equipment.”
4. ASTM Specification #D-877 “The Standard
Method of Testing Electrical Insulating Oils.”

8
TRANSFORMER PRODUCTS
1900 E. North Street
Waukesha, WI 53188-3899
(414) 547-1251

Printed in U.S.A.

You might also like