You are on page 1of 1

BILL OF MATERIALS

EXISTING FLEXIBLE NO. DESCRIPTION MANUF. PART NO.


COPPER BRAID
1 CIRCUIT SWITCHER (OFE) S&C SERIES 2030 A WHB 11/22/04 PRELIMINARY
EXISTING SWITCH
LEG NEAREST CIRCUIT
OPERATING ROD 2 SWITCH, SIDE BREAK DISC. 69KV, 1200 AMPS, COPPER (OFE) CLEVELAND PRICE G17 0 WHB 12/17/04 CONSTRUCTION
SWITCHER CONTROL PANEL
3 TERMINAL LUG, 500 CU TO 4 HOLE PAD, BRONZE ANDERSON SWH-080-C
GROUND CONNECTOR
TAB 4 TERMINAL LUG, 500 CU TO 4 HOLE PAD, BRONZE ANDERSON SWH-080-C-Y90
EXISTING
GROUND WIRE 5 TERMINAL LUG, 1 1/2" CU TUBE TO FLAT, BRONZE ANDERSON STF4-14C
6 PARALLEL GROOVE, 500 CU/500 CU, BRONZE ANDERSON LC-404
EXISTING 7 CABLE, 500, 37 STR. CU SOUTHWIRE -
COLUMN LEG
8 GROUND WIRE, 4/0, 19 STR CU SOUTHWIRE -

NEW SWITCH OPERATOR 9 PIPE, 1 1/2" SCH 40, CU - -


PLATFORM 10 CONDUIT, 2" LIQUIDTIGHT FLEX CARLON -
11 CONDUIT, 2" SCH 40 , PVC CARLON -
12 ELBOW, 90°, 2" SCH 40, PVC CARLON -
13 ELBOW, 45°, 2" SCH 40, PVC CARLON -
NEW SWITCH
OPERATOR PLATFORM 14 CONDUIT CONNECTOR, STEEL, W/ SEALING LOCK NUT AND PLASTIC BUSHING, 2" LIQUIDTIGHT FLEX CONDUIT CARLON -
NEW 4/0 CU. TO 15 CONDUIT ADAPTER, FEMALE, 2" PVC TO 2" FLEX CONDUIT CARLON -
EXISTING GROUND
GRID CONDUCTOR. 16 GROUND CONNECTOR, BOLTED, CABLE TO BAR BURNDY G-B29
17 BOLT, HEX HD. 1/2" X 1-3/4" LG S.S. ANDERSON -
18 NUT, HEX HD. 1/2" S.S. ANDERSON -
NEW 4/0 CU. TO
EXISTING GROUND 19 WASHER, BELLEVILLE, 1/2" S.S. ANDERSON -
GRID CONDUCTOR. EXISTING GROUND
NEW 4/0 CU. TO 20 SWITCH OPERATOR PLATFORM, 2' X 4' GALV. STEEL - -
EXISTING GROUND WIRE TO GROUND
GRID. 21 TIE WRAP, WEATHERPROOF - -
GRID CONDUCTOR.
NEW 4/0 CU. TO
22 BI-METALLIC TRANSITION PLATE ANDERSON TP-C
EXISTING GROUND 23 SPLIT BOLT, 4/0 CU TO 4/0 CU BURNDY KS31
GRID CONDUCTOR.
NEW 4/0 CU. TO 24 GROUND CONNECTOR, BOLTED, 2 CABLE BURNDY GC2929
EXISTING GROUND 25 GROUND CONNECTOR, COMPRESSION TAP BURNDY YGHP29C29
GRID CONDUCTOR.
26 CONDUIT COUPLING, 2" SCH 40 PVC CARLON -
27 CONTACT SEALANT ANDERSON -
28 CONDUIT COUPLING, 2" PVC CONDUIT CARLON -

BY-PASS SW
7'-0" 7'-0"
(NOT USED)
BY-PASS SW. (NOT USED)
5'-0" 5'-0"

EXISTING HARDWARE

EXISTING 500 CU CABLE


NOTES:
1. CONTRACTOR SHALL FIELD FABRICATE ANY ATTACHMENT BRACKET OR FIELD DRILL
ANY HOLES REQUIRED IN EXISTING STEEL FOR THE INSTALLATION OF GANG
OPERATED SWITCH AND/OR OPERATING ARM/RODS.
2. 4/0, 19 STR CU CABLE TO BE RUN WITH THE CONDUITS FROM THE CIRCUIT SWITCHER
CONTROL CABINET TO THE CABLE TRENCH, WHERE IT SHALL BE CONNECTED TO THE
EXISTING CABLE TRENCH GROUND WIRE. IF TRENCH IS NOT GROUNDED, THEN RUN
THE 4/0 GROUND WIRE WITH THE NEW CONTROL CABLE BACK TO THE SWITCHGEAR
AND MAKE CONNECTION THERE.
EXISTING LIGHTNING 3. MINIMUM PHASE-TO-GROUND CLEARANCE OF 2'-1" MUST BE MAINTAINED. (2'-5"
ARRESTER
RECOMMENDED)
4. CONTRACTOR RESPONSIBLE FOR VERIFYING MATERIAL.
NEW 69KV, 350 BIL 5. CONTRACTOR RESPONSIBLE FOR VERIFYING LOCATIONS OF EXISTING EQUIPMENT
INSULATORS AND STRUCTURES OUTSIDE CLOUDS.
SEE NOTE 1 SEE NOTE 6 1 6. CLOUDS REPRESENT AREAS OF WORK TO BE PERFORMED AS PART OF THIS
NEW 1 1/2 CU. PIPE PROJECT.
SEE NOTE 6 1 BUS 7. EXISTING XFMR TO BE RELOCATED FROM DANVILLE, ROCK SPRINGS SUBSTATION.

3'-0"
NEW 2000A CU.
BUS DUCT

REFERENCE DRAWINGS:
SEE NOTE 3 7'-0" 7'-0"
R 113382GA01-0 GENERAL ARRANGEMENT
PH 2'-5
. T " (M 113382EL01-1 SUBSTATION ELEVATION
O IN
G .)
ND 113382RF01-A SITE & GRADING PLAN (REF. DWG 71P89-S-1)
113382RF02-A FOUNDATION PLAN & SECTIONS (REF. DWG 71P89-S-2)
113382RF03-A LONGITUDINAL SECTION THRU SUBSTATION (REF. DWG 71P89-S-3)
EXISTING BUS DUCT
113382RF04-A WESTINGHOUSE METAL CLAD SWITCHGEAR (REF. DWG B8306-3C & B8306-1U)
THROAT ON SWGR
113382RF05-A 2000A 15KV BUS RUN (WESTINGHOUSE ELEC. (REF. DWG 6959D49)
GN .)
O IN
D

113382RF06-A EXISTING XFMR TO BE RELOCATED FROM DANVILLE, SWEDWOOD


20'-11"
. T (M

SUBSTATION (REF. DWG 352738-3803)


PH 10"

USE EXISTING SWITCH


R

OPERATOR AND ARM IF


(MIN.)
12'-6"

17'-2116"

PRACTICAL. 113386-PP01-03-0 WORSHAM ST BRIDGE - 12KV ALT. DELIVERY PLAN & PROFILE
9'-93 4"

(SEE NOTE 1) SEE DETAIL 1 UNDERGROUND DUCT 1 OF 6 (REF. DWG PP01-03, REV. 0)

SWITCH OPERATOR
PLATFORM SEE DETAIL 2 EXISTING
TRENCH
8'-0"

T.O.C. EL. 414.5'


TOP OF EXISTING
FINISHED
3'-0"

TRENCH
GRADE 3'-3" 6'-10" 4'-1"
EL. 411.5'
NEW BUS DUCT SUPPORTS T.O.G.
SHALL NOT INTERFERE EXISTING XFMR FDN CONNECT 4/0 TO
WITH FULL OPENING OF EXISTING CONNECT 4/0 TO EXISTING
XFMR CONTROL PANEL GROUND GRID GROUND GRID
SEE DETAIL 2 FOR
OPERATOR PLATFORM
10'-1" 12'-11" GROUNDING DETAILS.

16'-6" 4/0 TO RUN WITH CONDUIT TO


4/0 TO RUN WITH CONDUIT TO
CABLE TRENCH (SEE NOTE 2)
CABLE TRENCH (SEE NOTE 2)
33'-0"

UC SYNERGETIC, LLC.
123 North White Street
Fort Mill, SC 29715
VA License No. 0407005765

You might also like